Plan Review Details - Permit 10060234
Plan Review Stops For Permit 10060234
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-06-10 Cont ID  
Sent By jwitmer Date 2010-06-10 Time 13:35 Rev Time 0.77
Received By jwitmer Date 2010-06-10 Time 13:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-06-16 Cont ID  
Sent By btrobaug Date 2010-06-16 Time 15:03 Rev Time 0.00
Received By btrobaug Date 2010-06-16 Time 11:06 Sent To  
Notes
2010-06-15 16:57:19 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} NOTE #2 ON SHEET #2 INCORRECTLY STATES THAT MOTION
 SENSORS ARE NOT REQUIRED FOR BUILDINGS LESS THAN 5000
 SF PER 2007 FBC13-415.AB.1. THAT SECTION SITES OPTIONS
 FOR THE REQUIRED AUTOMATIC LIGHTING CONTROLS FOR THE
 ENTIRE BUILDING IF OVER 5000 SF. THE SECTION REQUIRING
 SPACE CONTROL IS THE FOLLOWING:
  
 13-415.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED BY
 CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE
 CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL
 LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE SHALL BE
 READILY ACCESSIBLE AND LOCATED SO THE OCCUPANTS CAN SEE
 THE CONTROLLED LIGHTING.
  
 A. A CONTROL DEVICE SHALL BE INSTALLED THAT
 AUTOMATICALLY TURNS LIGHTING OFF WITHIN 30 MINUTES OF
 ALL OCCUPANTS LEAVING A SPACE, EXCEPT SPACES WITH
 MULTISCENE CONTROL, IN THE FOLLOWING:
  
 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS,
 LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE
 CLASSROOMS).
  
 2. CONFERENCE/MEETING ROOMS.
  
 3. EMPLOYEE LUNCH AND BREAK ROOMS.
  
 THESE SPACES ARE NOT REQUIRED TO BE CONNECTED TO OTHER
 AUTOMATIC LIGHTING SHUTOFF CONTROLS.
  
 TO FACILITATE THE ISSUANCE OF THIS PERMIT THIS REVIEW
 IS APPROVED WITH EXCEPTION AND A REVISION IS REQUIRED
 TO CORRECT THE ABOVE LISTED DEFICIENCY.
  
 THIS REVISION IS REQUIRED TO BE SUBMITTED AND APPROVED
 PRIOR TO THE FIRST ELECTRICAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-06-17 Cont ID  
Sent By mawillia Date 2010-06-17 Time 15:06 Rev Time 0.00
Received By mawillia Date 2010-06-17 Time 14:48 Sent To  
Notes
2010-06-17 15:03:23*****APPROVED*****
  
 PLAN SHEETS 1 AND 2 WERE STAMPED, INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-14 Cont ID  
Sent By btrobaug Date 2010-07-14 Time 10:29 Rev Time 0.00
Received By btrobaug Date 2010-06-09 Time 08:47 Sent To  
Notes
2010-06-09 08:47:13B-12

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-06-17 Cont ID  
Sent By lwagner Date 2010-06-17 Time 10:11 Rev Time 0.00
Received By lwagner Date 2010-06-17 Time 09:59 Sent To  
Notes
2010-06-17 10:12:23PLUMBING PERMIT REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2010-07-14 Cont ID  
Sent By astelly Date 2010-07-14 Time 09:21 Rev Time 0.00
Received By astelly Date 2010-07-14 Time 09:21 Sent To  
Notes
***NONE***