Plan Review Details - Permit 10060221
Plan Review Stops For Permit 10060221
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-08-24 Cont ID  
Sent By rmcdouga Date 2010-08-24 Time 14:04 Rev Time 0.00
Received By rmcdouga Date 2010-08-24 Time 14:04 Sent To  
Notes
2010-08-24 14:13:49REVISION REQUIRED
  
 1) SUBMIT PRODUCT APPROVALS FOR THE DOUBLE OUTSWING
 FRONT DOORS.
  
 2) THE PRODUCT APPROVALS FOR THE LARGE AND SMALL GARAGE
 DOORS DO NOT HAVE ADEQUATE DESIGN PRESSURES.
  
 3) THE PRODUCT APPROVAL FOR THE ONE HOUR FIRE RATED
 GLASS BLOCK (VISTABRIK) HAS A MAXIMUM WIDTH OF 4'-0"
 AND THE PLANS HAVE A 6'-0" WIDE OPENING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-08-23 Cont ID  
Sent By rmcdouga Date 2010-08-23 Time 16:00 Rev Time 0.00
Received By rmcdouga Date 2010-08-23 Time 16:00 Sent To  
Notes
2010-08-23 16:07:472007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT PRODUCT APPROVALS FOR THE DOUBLE OUTSWING
 FRONT DOORS.
  
 2) THE PRODUCT APPROVALS FOR THE LARGE AND SMALL GARAGE
 DOORS DO NOT HAVE ADEQUATE DESIGN PRESSURES.
  
 3) THE PRODUCT APPROVAL FOR THE ONE HOUR FIRE RATED
 GLASS BLOCK (VISTABRIK) HAS A MAXIMUM WIDTH OF 4'-0"
 AND THE PLANS HAVE A 6'-0" WIDE OPENING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-21 Cont ID  
Sent By rmcdouga Date 2010-06-21 Time 10:33 Rev Time 0.00
Received By rmcdouga Date 2010-06-21 Time 07:41 Sent To  
Notes
2010-06-21 09:28:292007 FBC W/2009 REVISIONS
 NSFR
  
 DENIED BY BUILDING
  
 1) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025
  
 2) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND
 THE PLANS SPECIFY EXPOSURE B. PLEASE CORRECT THE
 EXPOSURE AND INCREASE WINDLOAD PRESSURES ACCORDINGLY.
 REVIEW PRODUCT APPROVALS FOR THE INCREASED PRESSURE
 REQUIREMENTS.
  
 3) PROVIDE COPIES OF SUBDIVISION COVENANTS THAT ALLOW
 EMERGENCY EGRESS FROM THE BEDROOMS ON THE ZERO LOT LINE
 ACROSS THE ADJACENT PROPERTY TO THE PUBLIC WAY. FBC
 R310
  
 4) ON SHEET A1 THE ATTIC ACCESS DETAIL SPECIFIES R-11
 INSULATION AND THE ENERGY CALCULATION REQUIRES R-30.
 PLEASE CORRECT.
  
 5) SUBMIT 2 SETS OF PRODUCT APPROVALS FOR THE ONE HOUR
 FIRE RATED GLASS BLOCK, REQUIRED ON THE ZERO LOT LINE.
 DCA RULE 9B-72.
  
 6) SUBMIT 2 SETS OF PRODUCT APPROVALS FOR THE HURRICANE
 STRAPS AND CONNECTORS AS REQUIRED BY DCA RULE 9B-72.
 THE FLORIDA PRODUCT APPROVAL NUMBERS OR MIAMI DADE NOA
 NUMBERS CAN BE LISTED WITH THE CONNECTORS IN THE TRUSS
 CONNECTOR SCHEDULE ON THE PLANS.
  
 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. FBC
 106.3.3 CITY AMENDMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-08-19 Cont ID  
Sent By jleahy Date 2010-08-19 Time 08:53 Rev Time 0.00
Received By jleahy Date 2010-08-19 Time 08:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-06-14 Cont ID  
Sent By btrobaug Date 2010-06-14 Time 12:57 Rev Time 0.00
Received By btrobaug Date 2010-06-14 Time 07:33 Sent To  
Notes
2010-06-14 12:55:49 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER
 250.118, SIZED PER 250.122.
  
 2} 210.52 (E)(1) ONE-FAMILY AND TWO-FAMILY DWELLINGS.
 FOR A ONE-FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY
 DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE
 RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT GRADE
 LEVEL AND LOCATED NOT MORE THAN 2.0 M (61/2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING.***NO RECEPTACLE IS LOCATED IN THE FRONT OF
 THE RESIDENCE.
  
 3} THE "OPTIONAL" WHIRLPOOL AND WINE COOLER REF. SHOWN
 ON THE PLAN SHOULD BE LISTED IN THE AND CALCULATED IN
 THE PANEL SCHEDULE.408.4, 220, 2008 NEC.
  
 4} THE LOCATION OF THE CONDESING UNITS MAY NOT COMPLY
 WITH THE WORKING CLEARANCE REQUIREMENTS FOR THE SERVICE
 AND DISCONNECTS PER 110.26.
  
 NOTE: THESE ITEMS WOULD HAVE BEEN REDLINED BY THE
 REVIEWER TO EXPEDITE THE START OF THE PROJECT IF THIS
 PLAN WAS NOT INTENDED TO BE MASTERED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-04 Cont ID  
Sent By lmartine Date 2010-08-04 Time 09:58 Rev Time 0.00
Received By lmartine Date 2010-08-04 Time 09:58 Sent To  
Notes
2010-08-04 09:59:41**************EXPEDITED****************
 2ND RUN
 R-5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-21 Cont ID  
Sent By rmcdouga Date 2010-06-21 Time 10:33 Rev Time 0.00
Received By rmcdouga Date 2010-06-09 Time 08:55 Sent To  
Notes
2010-06-10 16:29:11***************EXPEDITED******************
 6/10/10
2010-06-09 08:56:29R-8

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2010-09-07 Cont ID  
Sent By rmcdouga Date 2010-09-07 Time 13:46 Rev Time 0.00
Received By rmcdouga Date 2010-09-07 Time 13:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-06-21 Cont ID  
Sent By rmcdouga Date 2010-06-21 Time 09:41 Rev Time 0.00
Received By rmcdouga Date 2010-06-21 Time 09:41 Sent To  
Notes
2010-06-21 09:41:34IMPACT FEES REQUIRED.

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2010-08-24 Cont ID  
Sent By kdfreema Date 2010-08-24 Time 14:02 Rev Time 0.00
Received By kdfreema Date 2010-08-24 Time 14:02 Sent To  
Notes
2010-08-24 14:03:38***PROVISO***
  
 THE LANDSCAPE COMMENTS OF AUGUST 8, 2010 SHALL BE
 SATISFIED PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY.
  
 PLEASE CONTACT KELLY FREEMAN, GIS PLANNER, AT
 561-822-1458 WITH QUESTIONS.

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2010-08-06 Cont ID  
Sent By rkussner Date 2010-08-06 Time 16:32 Rev Time 0.00
Received By rkussner Date 2010-08-06 Time 16:32 Sent To  
Notes
2010-08-06 16:55:53***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. REPEAT COMMENT: SEPARATE LANDSCAPE AND IRRIGATION
 PERMITS ARE REQUIRED. TWO COPIES OF THE LANDSCAPE PLAN
 AND A COST ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL
 LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO UNIT
 COST SHALL BE SUBMITTED WITH THE LANDCAPE PERMIT
 APPLICATION.
  
 2. THE PROPOSED GRAVEL ALONG THE SIDE OF THE HOME SHALL
 NOT BE USED. THAT AREA SHALL BE SODDED OR LANDSCAPED
 WITH SHRUBS AND GROUND COVERS. GRAVEL CAN ONLY BE USED
 IN VERY NARROW AREAS.
  
 3. SUBMIT TWO COPIES OF THE IRRIGATION PLAN WITH THE
 IRRIGATION PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-06-11 Cont ID  
Sent By rkussner Date 2010-06-11 Time 12:12 Rev Time 0.00
Received By rkussner Date 2010-06-11 Time 12:12 Sent To  
Notes
2010-06-11 12:28:51***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. SEPARATE LANDSCAPE AND IRRIGATION PERMITS ARE
 REQUIRED. A COST ESTIMATE THAT INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST SHALL BE SUBMITTED WITH THE LANDCAPE PERMIT
 APPLICATION.
  
 2. SUBMIT TWO COPIES OF A COMPLETE LANDSCAPE PLAN,
 INCLUDING THE TABULATION NECESSARY FOR THE EVALUATION
 OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, INCLUDING THE XERISCAPE DESIGN
 OPTIONS.
  
 3. PURSUANT TO SECTION 94-448 (D) (2), THE LANDSCAPE
 PLAN SHALL CONTAIN ALL OF THE ITEMS ENUMERATED IN THIS
 SECTION.
  
 4. SUBMIT TWO COPIES OF THE IRRIGATION PLAN THAT SHOWS
 THE LAYOUT AND COMPONENTS OF THE SYSTEM. IT SHALL
 PROVIDE 120% COVERAGE TO ALL LANDSCAPED AREAS,
 INCLUDING THE RIGHT-OF-WAY.
  
 5. IDENTIFY THE TYPE OF STREET TREE(S) TO BE PLANTED
 AND PROVIDE THE LOCATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-08-19 Cont ID  
Sent By rmcdouga Date 2010-08-19 Time 08:13 Rev Time 0.00
Received By rmcdouga Date 2010-08-18 Time 17:37 Sent To  
Notes
2010-08-19 08:36:05MECHANICAL PROVISO
  
 1) IF THE OPTIONAL DOOR IS INSTALLED BETWEEN THE FOYER
 AND HALL, ALTERNATIVE METHODS SHALL BE USED TO MAINTAIN
 BALANCED RETURN AIR AS REQUIRED BY FBCR M1602.4.
  
 2) OUTDOOR COMBUSTION AIR SHALL BE PROVIDED FOR THE GAS
 DRYER IN THE LAUNDRY ROOM AS REQUIRED BY FBCR G2407.6
 (304.6).

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-06-21 Cont ID  
Sent By rmcdouga Date 2010-06-21 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2010-06-21 Time 09:29 Sent To  
Notes
2010-06-21 09:41:022007 FBC W/2009 REVISIONS
 NSFR
  
 DENIED BY MECHANICAL
  
 1) THE RETURN AIR CAN NOT BE TAKEN FROM THE LAUNDRY
 ROOM. FBC R M1602.2 (2) & (3). PLEASE RELOCATE RETURN.
  
 2) THE MECHANICAL PLANS SPECIFY ONE HVAC SYSTEM AND THE
 ELECTRICAL PLANS SHOW TWO SYSTEMS. PLEASE COORDINATE
 THE ELECTRICAL PLANS (PANEL SCHEDULE, BREAKER SIZES,
 DISCONNECTS, ETC.) WITH THE MECHANICAL PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-08-18 Cont ID  
Sent By rmcdouga Date 2010-08-18 Time 17:37 Rev Time 0.00
Received By rmcdouga Date 2010-08-18 Time 17:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-06-21 Cont ID  
Sent By rmcdouga Date 2010-06-21 Time 07:16 Rev Time 0.00
Received By rmcdouga Date 2010-06-19 Time 07:56 Sent To  
Notes
2010-06-21 07:41:092007 FBC W/2009 REVISIONS
 NEW SFR
  
 DENIED BY PLUMBING
  
 1) THE ORIENTATION OF THE PLUMBING ON THE RISER DIAGRAM
 DOES NOT MATCH THE ARCHITECTURAL PLANS. PLEASE REVISE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2010-08-24 Cont ID  
Sent By kdfreema Date 2010-08-24 Time 14:01 Rev Time 0.00
Received By kdfreema Date 2010-08-24 Time 14:01 Sent To  
Notes
2010-08-24 14:02:06WILL BE TAKING 3 CAR GARAGE OPTION.

Review Stop Z ZONING
Rev No 2 Status F Date 2010-08-09 Cont ID  
Sent By kdfreema Date 2010-08-09 Time 13:47 Rev Time 0.00
Received By kdfreema Date 2010-08-09 Time 13:46 Sent To  
Notes
2010-08-09 13:52:15***FAILED***
  
 REPEAT COMMENT: SHEET S-5 SHOWS A THREE CAR GARAGE
 OPTION, HOWEVER, ALL OF THE OTHER PLAN SHEETS INDICATE
 A TWO CAR GARAGE. PLEASE REMOVE SHEET S-5 IF THAT
 OPTION WILL NOT BE TAKEN. IF THE OPTION WILL BE TAKEN,
 PLEASE REVISE THE OTHER SHEETS ACCORDINGLY SO
 EVERYTHING IS CONSISTENT.
  
 NEW COMMENT: A SURVEY IS REQUIRED TO BE PROVIDED. IT
 WAS INCLUDED WITH THE FIRST SUBMITTAL, BUT APPEARS TO
 HAVE BEEN REMOVED FROM THE PACKAGE.
  
 PLEASE CONTACT KELLY FREEMAN, GIS PLANNER, AT
 561-822-1458 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-06-16 Cont ID  
Sent By kdfreema Date 2010-06-16 Time 16:29 Rev Time 0.00
Received By kdfreema Date 2010-06-16 Time 16:29 Sent To  
Notes
2010-06-16 16:33:03***FAILED***
  
 1. THE SURVEY INCLUDED SEEMS TO INDICATE THAT THE THREE
 CAR GARAGE WILL BE THE MODEL CONSTRUCTED ON THIS
 PROPERTY, HOWEVER, MOST OF THE CONSTRUCTION DOCUMENTS
 ARE FOR THE TWO CAR GARAGE MODEL. PLEASE CLARIFY WHICH
 MODEL IS TO BE BUILT AND ENSURE THAT ALL OF THE PLAN
 SHEETS REFLECT THE SAME.
  
 PLEASE CONTACT KELLY FREEMAN, GIS PLANNER, AT
 561-822-1458 OR [email protected] WITH QUESTIONS.
  