| Plan Review Stops For Permit 10060218 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2011-02-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-02-02 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-02-02 |
Time |
17:48 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2010-12-21 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-12-09 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-12-21 |
Time |
10:41 |
Sent To |
FIRE |
|
| Notes |
| 2010-12-21 10:43:50 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE HAVE ENGINEER PROVIDE INFORMATION AS TO HOW | | | HE DETERMINED THAT COMBUSTIBLE CONSTRUCTION IS | | | PERMITTED IN THIS BUILDING, SEE FBC CHAPTER 6. THIS | | | COMMENT MAY BE ADDRESSED VIA EMAIL OR TELEPHONE AND, | | | AFTER THIS ISSUE IS RESOLVED, THE PERMIT CAN BE ISSUED | | | (WITH PROVISO IF NECESSARY). | | | | | | | | 2010-12-09 14:54:08 | BUILDING |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2010-08-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-08-23 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-08-23 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2010-08-23 15:00:36 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1-2. ADDRESSED. | | | | | | 3. FROM PREVIOUS LIST - SHOW HOW EXITING IS AFFECTED, | | | FBC10. DECLARE OCCUPANCY CLASSIFICATION FOR EACH AREA, | | | AND SHOW HOW EXITING IS AFFECTED. IT APPEARS THAT YOU | | | ARE CREATING A NEW EGRESS PATH, NOT CLEAR WHERE THE | | | EXIT IS, OCCUPANT LOAD NOT STATED, HOW WILL THE | | | ADDITIONAL OCCUPANTS WHICH MAY ELECT TO EXIT IN THIS | | | DIRECTION AFFECT THE CURRENT EXITING CAPACITY? HOW WILL | | | EXIT LIGHTING BE AFFECTED? | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-06-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-06-09 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-06-09 |
Time |
10:19 |
Sent To |
E |
|
| Notes |
| 2010-06-09 10:26:39 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE EXPLAIN THE "WIND INFORMATION" ON THE PLAN. | | | THIS STATES THAT THIS IS AN INTERIOR RENOVATION, WHY IS | | | THERE WIND INFORMATION ON THE PLAN? | | | | | | 2. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED | | | IMPROVEMENT. NO INFORMATION WAS PROVIDED, IS A PAGE | | | MISSING? | | | | | | 3. SHOW HOW EXITING IS AFFECTED, FBC10. DECLARE | | | OCCUPANCY CLASSIFICATION FOR EACH AREA, AND SHOW HOW | | | EXITING IS AFFECTED. IT APPEARS THAT YOU ARE CREATING A | | | NEW EGRESS PATH, NOT CLEAR WHERE THE EXIT IS, OCCUPANT | | | LOAD NOT STATED, HOW WILL THE ADDITIONAL OCCUPANTS | | | WHICH MAY ELECT TO EXIT IN THIS DIRECTION AFFECT THE | | | CURRENT EXITING CAPACITY? HOW WILL EXIT LIGHTING BE | | | AFFECTED? | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-06-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2010-06-10 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2010-06-10 |
Time |
10:05 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2011-02-03 |
|
|
Cont ID |
|
| Sent By |
ddaniels |
Date |
2011-02-03 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
ddaniels |
Date |
2011-02-03 |
Time |
14:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2010-12-21 |
|
|
Cont ID |
|
| Sent By |
ddaniels |
Date |
2010-12-21 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
ddaniels |
Date |
2010-12-21 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2010-12-21 15:31:49 | ***************DENIED******************** | | | | | | 1. PROVIDE ALL PLAN SHEETS ONLY TWO SUBMITTED PLAN | | | SHEETS (A-1), (A-2), BUT THE INFORMATION UNDER SHEET | | | A-1 INDICATES THAT THERE ARE FOUR TOTAL NUMBER SHEETS. | | | PLEASE EXPLAIN | | | | | | 2. IN THE EXITSTING CONDITIONS /DEMOLITION FLOOR | | | LAYOUT, CORRECT SPELLING OR VERB-AGE "HIGHT" TO HEIGHT | | | OR HIGH. | | | | | | 3. PROVIDE EXIT SIGN AND EMERGENCY LIGHTING FOR NEWLY | | | CREATED EXIT ACCESS ROUTE. | | | | | | TO EXPIDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED | | | | | | CAPTAIN DERRICK DANEILS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2010-08-02 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-08-02 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-08-02 |
Time |
12:45 |
Sent To |
B |
|
| Notes |
| 2010-08-02 12:52:19 | *****APPROVED PROVISO***** | | | | | | 1) PROVIDE EXIT SIGN AND EMERGENCY LIGHTING FOR NEWLY | | | CREATED EXIT ACCESS ROUTE. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6730 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2010-06-10 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2010-06-10 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2010-06-10 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2010-06-10 12:48:41 | *****APPROVED***** | | | | | | | | | 1. THERE IS ONLY ONE SUBMITTED PLAN SHEET (A-1), BUT | | | THE INFORMATION UNDER SHEET # A-1 INDICATES THAT THERE | | | ARE FOUR TOTAL NUMBER OF SHEETS. PLEASE EXPLAIN | | | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 3. PLEASE EXPLAIN/VERIFY THE FOLLOWING: 1) IF THIS IS | | | AN INTERIOR PROJECT, WHAT'S THE RATIONALE FOR THE WIND | | | LOAD INFORMATION? 2) OCCUPANCY USE OF SINGLE - FAMILY | | | DWELLING? | | | | | | 4. IN THE EXISTING CONDITIONS/DEMOLITION FLOOR LAYOUT, | | | CORRECT SPELLING OF VERB-AGE "HIGHT" TO HEIGHT OR HIGH. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2010-12-09 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-12-09 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-12-09 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2010-12-09 14:56:30 | TO BUILDING SH |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-07-15 |
|
|
Cont ID |
|
| Sent By |
vmolina |
Date |
2010-07-15 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-07-15 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2010-08-02 11:06:06 | TO FIRE | | | | | | | | 2010-07-15 11:54:03 | GAVE TO SHILL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2010-06-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
vmolina |
Date |
2010-06-09 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2010-06-09 08:40:32 | UNDER 5K BUILDING |
|
|