Plan Review Details - Permit 10060200
Plan Review Stops For Permit 10060200
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-06-24 Cont ID  
Sent By mawillia Date 2010-06-24 Time 15:29 Rev Time 0.00
Received By mawillia Date 2010-06-24 Time 14:11 Sent To  
Notes
2010-06-24 14:26:27*****APPROVED****
  
  
 HAVING RECEIVED FAXED INFORMATION IN ADDRESSING
 PREVIOUS COMMENTS, PLAN SHEET FP-1 OF 1 WAS STAMPED,
 INITIALED, AND DATED; READY FOR PERMIT ISSUANCE.
  
 CAPT. MICHAEL WILLIAMS
 FIRE PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-06-11 Cont ID  
Sent By wjolin Date 2010-06-11 Time 09:57 Rev Time 0.00
Received By wjolin Date 2010-06-10 Time 15:56 Sent To  
Notes
2010-06-10 16:43:10*****DENIED*****
  
 1) USING THE PIPE SCHEDULE METHOD TO MODIFY AN EXISTING
 HYDRAULICALLY CALCULATED SYSTEM IS NOT PERMITTED BY
 NFPA 13.
  
 2) WHEN SYSTEM PRESSURE EXCEEDS 100 PSI, PROVIDE
 HANGERS THAT PREVENT UPWARD MOVEMENT FOR END OF LINE
 PENDENT SPRINKLERS OR ARMOVERS EXCEEDING 12" IN LENGTH.
  
 3) PROVIDE ADDRESS AND SUITE NUMBER (IF APPLICABLE) IN
 TITLEBLOCK.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-10 Cont ID  
Sent By wjolin Date 2010-06-10 Time 16:44 Rev Time 0.00
Received By wjolin Date 2010-06-08 Time 08:00 Sent To  
Notes
2010-06-08 08:01:46IN FIRE BOX