| Plan Review Stops For Permit 10060200 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2010-06-24 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2010-06-24 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2010-06-24 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2010-06-24 14:26:27 | *****APPROVED**** | | | | | | | | | HAVING RECEIVED FAXED INFORMATION IN ADDRESSING | | | PREVIOUS COMMENTS, PLAN SHEET FP-1 OF 1 WAS STAMPED, | | | INITIALED, AND DATED; READY FOR PERMIT ISSUANCE. | | | | | | CAPT. MICHAEL WILLIAMS | | | FIRE PLAN REVIEW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2010-06-11 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-06-11 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-06-10 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2010-06-10 16:43:10 | *****DENIED***** | | | | | | 1) USING THE PIPE SCHEDULE METHOD TO MODIFY AN EXISTING | | | HYDRAULICALLY CALCULATED SYSTEM IS NOT PERMITTED BY | | | NFPA 13. | | | | | | 2) WHEN SYSTEM PRESSURE EXCEEDS 100 PSI, PROVIDE | | | HANGERS THAT PREVENT UPWARD MOVEMENT FOR END OF LINE | | | PENDENT SPRINKLERS OR ARMOVERS EXCEEDING 12" IN LENGTH. | | | | | | 3) PROVIDE ADDRESS AND SUITE NUMBER (IF APPLICABLE) IN | | | TITLEBLOCK. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6730 | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-06-10 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-06-10 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-06-08 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2010-06-08 08:01:46 | IN FIRE BOX |
|
|
|