Plan Review Details - Permit 10060181
Plan Review Stops For Permit 10060181
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-07-21 Cont ID  
Sent By lmartine Date 2010-07-21 Time 15:30 Rev Time 0.00
Received By lmartine Date 2010-07-21 Time 15:30 Sent To  
Notes
2010-07-21 15:31:15OK TO ISSUE AS RE-STAMP, PER DOUG

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-14 Cont ID  
Sent By jwitmer Date 2010-06-14 Time 11:24 Rev Time 1.50
Received By jwitmer Date 2010-06-14 Time 11:24 Sent To  
Notes
2010-06-14 11:50:14BUILDING PLAN REVIEW
 PERMIT: 10060181
 ADD: 255 EVERNIA ST
 CONT: COMPLETE PROPERTY MANAGEMENT, INC
 TEL: (561)632-1669
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE PLANS SUBMITTED ARE COPIES FROM THE ORIGINAL
 PERMIT. THEY ARE NOT SIGNED NOR SEALED BY THE DESIGNER
 OF RECORD.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 2) THE SUBMITTED PLANS ALSO ARE DESIGNED UNDER THE 2004
 FBC, THE CURRENT CODE EDITION IS THE 2007FBC-BUILDING
 W/ 2009 SUPPLEMENTS, AND 2007 EXISTING BUILDING CODE W/
 2009 SUPPLEMENTS. 2007 EXIST BUILDING CODE- 401.4 A
 DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 3) SHEET A3/ DETAIL # 3 INDICATES A STAIR AND GAURDRAIL
 SYSTEM, SHEET A-1 HAS A REVISION # 1 INDICATING THE
 GAURD RAIL SYSTEM SHOP DRAWINGS AARE TO BE SUBMITTED
 FOR APPROVAL. THE CITY DOES NOT HAVE ANY APPROVALS FOR
 SHOP DRAWINGS . 8 PAGES OF SHOP DRAWINGS WERE SUBMITTED
 FOR THE MEZANINE STEEL FRAMING AND STAIR LOCATION, BUT
 NOT THE GUARD RAIL SYSTEM.
 SHEET A3/ DETAIL #3 FAILS TO INDICATE THE HEIGHT OF THE
 HEIGHT OF THE GUARD RAIL ( FBC-B 1013.2) NOR THE
 HANDRAILS REQUIRED BY FBC-B 1012. THE PLANS ARE MISSING
 THE HANDRAIL EXTENSIONS REQUIRED BY 1012.5 &
 11-4.9.5(2).
  
 4) THE LAST REVISION SUBMITTED UNDER THE EXPIRED PERMIT
 07020610 REVIEW DATE2-19-08 WAS DENIED BY MYRON JACOBS.
 IT IS UNCLEAR IF THIS REVISION IS A FIELD MODIFICATION
 THAT MAY NEED TO BE READDRESSED SINCE THE PLANS HAVE
 NOT BEEN UPDATED, 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-07-21 Cont ID  
Sent By lmartine Date 2010-07-21 Time 15:37 Rev Time 0.00
Received By lmartine Date 2010-07-21 Time 15:37 Sent To  
Notes
2010-07-21 15:39:04OK TO ISSUE AS RE-STAMP PER DOUG

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-06-22 Cont ID  
Sent By jleahy Date 2010-06-22 Time 09:25 Rev Time 0.00
Received By jleahy Date 2010-06-22 Time 09:25 Sent To  
Notes
2010-06-22 09:27:2610 SEE BUILDING PALNS EXAMINER NOTES FOR COMMENTS,
 THESE ARE COPIED DRAWINGS???? TWO DIFFERENT REVISIONS?
 SAME PAGE
  
 JAKE LEAHY
 561-805-6740

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-07-21 Cont ID  
Sent By lmartine Date 2010-07-21 Time 15:39 Rev Time 0.00
Received By lmartine Date 2010-07-21 Time 15:39 Sent To  
Notes
2010-07-21 15:40:19OK TO ISSUE AS RESTAMP PER DOUG

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-06-21 Cont ID  
Sent By mawillia Date 2010-06-21 Time 16:20 Rev Time 0.00
Received By mawillia Date 2010-06-21 Time 15:34 Sent To  
Notes
2010-06-21 16:20:17*****UNSAT*****
  
  
 THE APPROPRIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE FOLLOWING COMMENTS HAVE BEEN ADDRESSED:
  
 1. ADDRESS THE BUILDING PLAN REVIEWER'S COMMENTS.
  
 2. THE CURRENT EDITIONS OF THE CODES SHALL BE
 REFERENCED - 2007 FLORIDA FIRE PREVENTION CODE, 2006
 NFPA 101, 2005 NFPA 70, 2004 NFPA 241
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-21 Cont ID  
Sent By hmoser Date 2010-07-06 Time 15:21 Rev Time 0.00
Received By lmartine Date 2010-06-09 Time 08:49 Sent To  
Notes
2010-06-09 08:54:47B-18

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-07-06 Cont ID  
Sent By hmoser Date 2010-07-06 Time 15:17 Rev Time 0.00
Received By hmoser Date 2010-07-06 Time 15:01 Sent To  
Notes
2010-07-06 15:21:23NO MECHANICAL PLANS SUBMITTED .
 CALLED JOE MECHANICAL CONTRACTOR IS GOING TO SUBMIT HIS
 OWN PLANS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732 .

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-07-21 Cont ID  
Sent By lmartine Date 2010-07-21 Time 15:40 Rev Time 0.00
Received By lmartine Date 2010-07-21 Time 15:40 Sent To  
Notes
2010-07-21 15:41:19OK TO ISSUE AS RE-STAMP PER DOUG

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-06-17 Cont ID  
Sent By lwagner Date 2010-06-17 Time 11:21 Rev Time 0.00
Received By lwagner Date 2010-06-17 Time 11:17 Sent To  
Notes
2010-06-17 11:18:381ST REVIEW
 ACTION: DENIED
  
 PLEASE SEE COMMENTS FROM BLDG REVIEW
 1) THE PLANS SUBMITTED ARE COPIES FROM THE ORIGINAL
 PERMIT. THEY ARE NOT SIGNED NOR SEALED BY THE DESIGNER
 OF RECORD.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  