Plan Review Details - Permit 10060179
Plan Review Stops For Permit 10060179
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-06-17 Cont ID  
Sent By jwitmer Date 2010-06-17 Time 14:28 Rev Time 5.50
Received By jwitmer Date 2010-06-17 Time 14:28 Sent To  
Notes
2010-06-17 14:30:27BUILDING PLAN REVIEW
 PERMIT: 10060179
 ADD: 512 SPENCER DR
 CONT: M. J. SIMPSON CORP.
 TEL: (954)275-5205
  
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISOS:
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET AD-1.01 NOTE NUMBERS 4 & 5 & SHEET A-1.01,
 DOOR # 104-6 & 104-7 AND A-6.01 INDICATE THE REMOVAL
 AND REPLACEMENT OF DOORS. THE DOOR SCHEDULE INDICATE NO
 FIRE RATING. THIS WALL APPEARS TO BE A 4 HR FIRE WALL
 REQUIRING THESE DOORS TO HAVE 3 HOUR OPENING
 PROTECTIVES. 2007 FBC-B TABLE 715.4.
  
 2) SHEET AD-1.01 NOTES 3 & 16 INDICATE THE REMOVAL OF
 STOREFRONT WINDOWS AND DOORS, SHEET A-1.01 INDICATE NEW
 STOREFRONT DOORS, THE S-1 SHEET PROVIDES THE ASSOCIATED
 POSITIVE & NEGATIVE PRESSURES, THE CONTRACTOR WILL NEED
 TO SUPPLY PRODUCT APPROVALS FOR THESE NEW COMPONENTS
 AND CLADDING.
  
 2A) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 3A ) STOREFRONT EXTERIOR GLAZED DOORS.
 3B) STOREFRONT WINDOWS ADJACENT TO STOREFRONT DOORS &
 CLERESTORY
 3C) 3 HOUR FIRER RATED DOORS
  
 2B) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3) SHEET A-1.01 NEW ACCESSIBLE RAMP INDICATES THE
 BOTTOM LANDING TO BE A DISTANCE OF 4???-8??? LONG,
 PLEASE REFER TO 11-4.8.4(2) THE BOTTOM OF EACH RAMP
 SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL
 CLEARANCE.
  
 4) SHEET A-1.01 NOTE 28 INDICATES THE INSTALLATION OF
 NEW LANDING AND STAIRS. A-1.02 DETAILS 4 & 5 INDICATE A
 SECTION THROUGH THE STAIR BUT NO REFERENCE TO THE
 REQUIRED HANDRAILS FBC-B 1009.10 , 1012 & 11-4.1.3.8(D)
 .
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-06-10 Cont ID  
Sent By btrobaug Date 2010-06-10 Time 14:10 Rev Time 0.00
Received By btrobaug Date 2010-06-10 Time 11:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-08-12 Cont ID  
Sent By mcarsill Date 2010-08-12 Time 12:51 Rev Time 0.00
Received By mcarsill Date 2010-08-12 Time 12:39 Sent To  
Notes
2010-08-12 12:51:45CARDINAL NEWMAN HIGH SCHOOL
 512 SPENCER DRIVE
 PERMIT NUMBER 10060179
  
  
 1. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM INSTALLATION OR REMODELING.
  
 2. NEW 3 HOUR FIRE SHUTTER IS TO BE DROP TESTED TO
 ENSURE PROPER OPERATION AFTER INSTALLATION. ADDITIONAL
 FUSIBLE LINKS WILL BE NEEDED TO TEST THE DOOR. THE TEST
 OF THE DOOR SHALL BE WITNESSED BY A REPRESENTATIVE OF
 THE BUREAU OF FIRE PREVENTION.
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-06-21 Cont ID  
Sent By mawillia Date 2010-06-21 Time 15:32 Rev Time 0.00
Received By mawillia Date 2010-06-21 Time 15:10 Sent To  
Notes
2010-06-21 15:32:34*****APPROVED*****
  
  
 PLAN SHEETS AD1.01, A-LS, A-1.01, A-6.01, E2.2, AND
 FA2.1 WERE STAMPED, INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-06-28 Time   Rev Time 0.00
Received By vmolina Date 2010-06-07 Time 11:42 Sent To  
Notes
2010-06-07 11:44:02B-1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-06-28 Cont ID  
Sent By rregueir Date 2010-06-28 Time 16:07 Rev Time 0.00
Received By rregueir Date 2010-06-28 Time 14:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-06-21 Cont ID  
Sent By lwagner Date 2010-06-21 Time 10:35 Rev Time 0.00
Received By lwagner Date 2010-06-17 Time 14:49 Sent To  
Notes
2010-06-21 10:35:531" COLD WATER REQUIRED IF FLUSH VALVE TYPE WATER CLOSET

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2010-08-19 Cont ID  
Sent By shill Date 2010-08-19 Time 18:34 Rev Time 0.00
Received By shill Date 2010-08-19 Time 18:34 Sent To  
Notes
2010-08-19 18:35:06OK PER JOHN DICKINSON CONTRACTOR PLAN REVIEWER LICENSE
 PX 3182

Review Stop Z ZONING
Rev No 1 Status P Date 2010-06-22 Cont ID  
Sent By jroach Date 2010-06-22 Time 18:04 Rev Time 0.00
Received By jroach Date 2010-06-22 Time 18:04 Sent To  
Notes
***NONE***