Plan Review Details - Permit 10060173
Plan Review Stops For Permit 10060173
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-09 Cont ID  
Sent By jwitmer Date 2010-08-09 Time 11:15 Rev Time 0.00
Received By jwitmer Date 2010-08-09 Time 11:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-10 Cont ID  
Sent By jwitmer Date 2010-06-10 Time 12:31 Rev Time 0.00
Received By shill Date 2010-08-24 Time 17:50 Sent To  
Notes
2010-06-10 12:43:36BUILDING PLAN REVIEW
 PERMIT: 10060173
 ADD: 201 S NARCISSUS # 120
 CONT: BEST INTERIOR CONSTRUCTION
 TEL: (561)640-3010
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A.3 INDICATES THE USE OF WOOD LAMINATE
 FLOORING. PLEASE PROVIDE DOCUMENTATION INDICATING
 COMPLIANCE WITH FBC-B 805.1 APPLICATION. COMBUSTIBLE
 MATERIALS INSTALLED ON OR EMBEDDED IN FLOORS OF
 BUILDINGS OF TYPE I OR II CONSTRUCTION SHALL COMPLY
 WITH SECTIONS 805.1.1 THROUGH 805.1.3.
  
 2) SHEET A.4 PROVIDES ELEVATIONS FOR VARIOUS CEILINGS
 BUT NO ADDITIONAL INFORMATION IS PROVIDED FOR THE TYPE
 OF CEILING MATERIALS, FRAMING, AND OR HANGING
 MATERIALS.
  
 3) PLANS DO NOT PROVIDE FOR WALL FINISHES, 803.1
 GENERAL. INTERIOR WALL AND CEILING FINISHES SHALL BE
 CLASSIFIED IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR
 FINISH MATERIALS SHALL BE GROUPED IN THE FOLLOWING
 CLASSES IN ACCORDANCE WITH THEIR FLAME SPREAD AND
 SMOKE-DEVELOPED INDEXES.
  
 4) SHEET A.2 THE LIFE SAFETY PLAN DOES NOT INDICATE
 WHERE DISPLAYS RACKS OR OTHER ASSOCIATED SALES ITEMS
 ARE LOCATED WITHIN A MERCANTILE OCCUPANCY.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-08-24 Cont ID  
Sent By shill Date 2010-08-24 Time 17:52 Rev Time 0.00
Received By shill Date 2010-08-24 Time 17:51 Sent To  
Notes
2010-08-24 17:54:21OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER PX3182
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-06-15 Cont ID  
Sent By btrobaug Date 2010-06-15 Time 12:20 Rev Time 0.00
Received By btrobaug Date 2010-06-14 Time 15:57 Sent To  
Notes
2010-06-15 12:20:34 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1*** SHOW COMPLIANCE ON THE PLAN. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATING THE
 WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT
 CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES
 ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS.
  
 2} 13-415.1.AB.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING.
 A. A CONTROL DEVICE SHALL BE INSTALLED THAT
 AUTOMATICALLY TURNS LIGHTING OFF WITHIN 30 MINUTES OF
 ALL OCCUPANTS LEAVING A SPACE, EXCEPT SPACES WITH
 MULTISCENE CONTROL, IN THE FOLLOWING:
 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS,
 LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE
 CLASSROOMS).
 2. CONFERENCE/MEETING ROOMS.
 3. EMPLOYEE LUNCH AND BREAK ROOMS.
  
 3}220.14 (G) SHOW WINDOWS. SHOW WINDOWS SHALL BE
 CALCULATED INACCORDANCE WITH EITHER OF THE FOLLOWING:
 (1) THE UNIT LOAD PER OUTLET AS REQUIRED IN OTHER
 PROVISIONS
 OF THIS SECTION
 (2) AT 200 VOLT-AMPERES PER 300 MM (1 FT) OF SHOW
 WINDOW
 **** LOCATE SAME ON THE PLAN AND IN THE PANEL SCHEDULE
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-08-13 Cont ID  
Sent By mcarsill Date 2010-08-13 Time 11:14 Rev Time 0.00
Received By mcarsill Date 2010-08-13 Time 11:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-06-10 Cont ID  
Sent By mawillia Date 2010-06-10 Time 14:40 Rev Time 0.00
Received By mawillia Date 2010-06-10 Time 13:42 Sent To  
Notes
2010-06-10 14:16:41*****DENIED*****
  
  
 1. THE FLOOR PLAN AS SHOWN ON SHEET A.2, MORE REFLECTS
 THAT OF A BUSINESS OCCUPANCY RATHER THAN A MERCANTILE
 OCCUPANCY AS INDICATED IN THE PROJECT DATA INFORMATION.
  
 2. ONLY ONE FIRE EXTINGUISHER COULD BE LOCATED. PROVIDE
 ADDITIONAL FIRE EXTINGUISHER(S) TO SATISFY THE 75'
 TRAVEL DISTANCE.
  
 3. SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
 SPECIFY INTERIOR FLOOR MATERIAL IN TERMS OF CLASS I OR
 CLASS II.
  
 4. NO FIRE SPRINKLER HEAD LAYOUT FOR THE NEW FLOOR
 SHOWN. WILL THE PROJECT'S SCOPE OF WORK HAVE CAUSE FOR
 THESE DEVICES TO BE RELOCATED / REMODELED ?
  
 5. ON PAGE 1 OF THE FLORIDA ENERGY EFFICIENCY CODE'S
 PROJECT SUMMARY INFORMATION DOES NOT CORRELATE WITH THE
 PLAN. FOR EXAMPLE, 1) THE NUMERICAL ADDRESS, 2)
 OCCUPANCY TYPE, 3) TENANT SPACE NUMBER, 4) SQUARE
 FOOTAGE OF THE PROJECT
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-05 Cont ID  
Sent By lmartine Date 2010-08-05 Time 12:02 Rev Time 0.00
Received By lmartine Date 2010-08-05 Time 12:02 Sent To  
Notes
2010-08-05 12:02:31B--7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-04 Cont ID  
Sent By lmartine Date 2010-08-02 Time 18:35 Rev Time 0.00
Received By lmartine Date 2010-06-07 Time 11:57 Sent To  
Notes
2010-06-07 12:01:14B-3

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-09-01 Cont ID  
Sent By rregueir Date 2010-09-01 Time 09:29 Rev Time 0.00
Received By rregueir Date 2010-08-30 Time 11:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-06-24 Cont ID  
Sent By rregueir Date 2010-06-24 Time 15:27 Rev Time 0.00
Received By rregueir Date 2010-06-24 Time 15:27 Sent To  
Notes
2010-06-24 15:28:39REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. AC2, WATER SOURCE HEAT PUMP SCHEDULE, FRESH AIR,
 STATES SEE CALCS. I WAS UNABLE TO LOCATE THE
 CALCULATIONS REFERENCED ON THE PLAN. PLEASE PROVIDE
 CALCULATIONS, FBC M 403.2.
  
 2. PROVIDE INFORMATION REGARDING EXHAUST FOR THE TOILET
 ROOM, FBC M TABLE 403.3.
  
 3. PLEASE INCLUDE THE SYMBOL R (ENCIRCLED) IN THE
 LEGEND. THIS SYMBOL IS SHOWN AT THE THREE RETURNS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-08-10 Cont ID  
Sent By lwagner Date 2010-08-10 Time 15:15 Rev Time 0.00
Received By lwagner Date 2010-08-09 Time 13:39 Sent To  
Notes
2010-08-10 15:15:11EXISTING SUITE #1 TYPE M- 91 OCCUPANTS
 NEW SUITE #2 TYPE M - 134 "
 TOTA 225 - EXISTING RESTROOMS OK

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-06-23 Cont ID  
Sent By lwagner Date 2010-06-23 Time 12:44 Rev Time 0.00
Received By lwagner Date 2010-06-23 Time 10:35 Sent To  
Notes
2010-06-23 12:44:08PLUMBING PLAN REVIEW #1
 DENIED:
  
 1. SHEETS A.0, A.3, P-1, P-2
 SHEET A.0 LISTS THE AREA AS 4,022 SQUARE FEET. SEPERATE
 FACILITIES WILL BE REQUIRED FOR EACH SEX.
 403.2 SEPARATE FACILITIES. WHERE PLUMBING FIXTURES ARE
 REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR
 EACH SEX.
 EXCEPTIONS:
 1. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR
 DWELLING UNITS AND SLEEPING UNITS.
 2. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR FOOD
 SERVICE ESTABLISHMENTS WHICH SEAT 10 PERSONS OR LESS.
 3. SEPARATE FACILITIES SHALL NOT BE REQUIRED IN
 BUSINESS AND MERCANTILE OCCUPANCIES WITH A TOTAL FLOOR
 AREA OF 3,000 SQUARE FEET (279 M2) OR LESS.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2010-08-02 Cont ID  
Sent By astelly Date 2010-08-02 Time 14:20 Rev Time 0.00
Received By astelly Date 2010-08-02 Time 14:20 Sent To  
Notes
***NONE***