Plan Review Details - Permit 10060137
Plan Review Stops For Permit 10060137
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-07-01 Cont ID  
Sent By jwitmer Date 2010-07-01 Time 11:37 Rev Time 1.77
Received By jwitmer Date 2010-07-01 Time 11:37 Sent To  
Notes
2010-07-01 11:40:22BUILDING PLAN REVIEW
 PERMIT: 10060137
 ADD: 1100 S DIXIE HWY
 CONT: RYCON
 TEL: (412)287-9961
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 ATRIUM WALL TO COMPLY WITH FBC-B 404.5 1 HOUR RATED
 WALL, STOREFRONT GLASS TO BE FIRE SPRINKLERED.
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-10 Cont ID  
Sent By jwitmer Date 2010-06-10 Time 08:29 Rev Time 2.22
Received By jwitmer Date 2010-06-10 Time 08:29 Sent To  
Notes
2010-06-10 09:53:19BUILDING PLAN REVIEW
 PERMIT: 10060137
 ADD: 1100 S DIXIE HWY
 CONT: TO BE DETERMINED ( RYCON)
 TEL: (412)287-9961
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) NO PERMIT APPLICATION, PLANS SUBMITTED WITH ONLY A
 PLAN/ PERMIT REVISION AND SUBMITTAL FORM. 105.1 THE
 CONTRACTOR SHALL FIRST MAKE APPLICATION TO THE BUILDING
 OFFICIAL AND OBTAIN THE REQUIRED PERMIT BEFORE THE
 START OF WORK.
  
 2) G002- REFERENECES THE CONSTRUCTION TYPE AS A TYPE
 IIB. THE BUILDING WAS ORIGINALLY BUILT UNDER THE 94 SBC
 AAND BUILDING TYPE II WHICH TRANSLATES INTO THE 2007
 FBC-B AS A BUIULDING TYPE I-B PLEASE UPDATE PLANS.
  
 3) G002 - CODE PLEASE UPDATE THE PLANS TO THE 2007
 FLORIDA BUILDING CODE WITH 2009 SUPPLEMENTS, & 2007
 FLORIDA EXISTING BUILDING CODE W/ 2009 SUPPLEMENTS.
 FL EXT BLDG CODE SECTION 401.4 A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF
 THIS CODE.
  
 4) G-002 FIRE RESISTANCE RATINGS REFRENENCE THE 2006
 IBC TABLE 600, PLEASE UPDATE TO THE FLORIDA CODES AND
 CORRECT SECTIONAND OR TABLE.
  
 5) SHEETS D100 & A100, ON THE INTERIOR DEMO PLAN NOTE
 #8 INDICATES THE ELIMINATION OF A SECURITY GRILLE BUT
 ON SHEET A100 THERE IS NO MENTION OF WALL TYPE
 CONFIGURATION AND OR IF THE WALL IS A RATED WALL? THIS
 WOULD APPEAR TO BE A SEPERATE TENANT WITH A CHICK-FIL-A
 FRANCHISE OCCUPYING THIS SPACE.FBC-B 708.1(7).
  
 6) PLEASE PROVIDE A COMPLETE PLAN OF THE PROPOSED
 TENANT SPACE. IT APPEARS FROM THE ORIGINAL PERMITED
 BUILDING PLANS ( 96012215):
  
 6A) THE TENANT SPACE HAS INCREASED INTO THE COMMON AREA
 OR RECEIVING AREA ?
  
 6B) PLANS ARE NOT CLEAR WITHIN THE RECEIVING AREA IF
 THE OVERHEAD GRILLE IS STILL THERE? OR REMOVED AND NEW
 WALL SYSTEM IS CURRENTLY IN PLACE OR WILL BE INSTALLED
 AS NEW WORK UNDER THIS PERMIT?
  
 6C) IF THE OVERHEAD GRILLE IS EXISTING AND NOT TO BE
 REMOVED, THEN THIS AREA WOULD BE CONSIDERED EXTERIOR OR
 REQUIRING PRODUCT APPROVALS FOR THE NEW WALK-IN
 COOLERS. RULE 9B-72 (31)(G) EXTERIOR WALK-IN COOLERS &
 FREEZERS. WILL NEED TO INDICATE COMPLIANCE WITH WIND
 PRESSURES AND ANCHORAGE FOR 140 MPH, COASTAL EXPOSURE,
 NOTE HEIGHT ADJUSTMENT FACTORS FOR BUILDING HEIGHT.
  
 6D) PLEASE PROVIDE A NEW LS PLAN FOR THE EXSPANDED
 TENANT SPACE, 106.3.5.(7) / 1015.2.1 EXCEP(2) IT
 APPEARS THE OVER ALL DIAGONAL OF THE TENANT SPACE (WITH
 RECEIVING AREA INCLUDED) & WITH FIRE SPRINKLERS THE TWO
 EXIT ACCESS DOORWAYS APPEAR TO BE LESS THAN 1/3 THE
 OVERALL DIAGONAL APART.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-07-07 Cont ID  
Sent By dwise Date 2010-07-07 Time 11:52 Rev Time 0.00
Received By dwise Date 2010-07-07 Time 11:52 Sent To  
Notes
2010-07-07 11:54:53APPROVED WITH EXCEPTION:
 THE APPLICANT HAS FAILED TO PROVIDE THE REQUESTED POWER
 DENSITIES WHICH SATISFY FBC CHAPTER 13 SECTION 415.2
 ABC FOR ALLOWABLE WATTAGE FOR THE RENOVATED AREA.
 THE APPLICANT MUST SUBMIT A REVISION FOR REVIEW AND
 ACCEPTANCE PRIOR TO THE TIME OF INSTALLATION IN THE
 FIELD OR BE SUBJECT TO PENALTY REINSPECTION FEES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-06-24 Cont ID  
Sent By btrobaug Date 2010-06-24 Time 12:33 Rev Time 0.00
Received By btrobaug Date 2010-06-23 Time 11:14 Sent To  
Notes
2010-06-24 12:33:18 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE
 13-415.1AB.1.1 FOR TIME CLOCK REQUIREMENTS. ALL THAT IS
 REQUIRED FOR THE ELECTRICAL REVIEW IS THE BASIC
 PRESCRIPTIVE REQUIREMENTS. SEE 13-415.2.AB.5 INTERIOR
 LIGHTING POWER, SCOPE.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-06-30 Cont ID  
Sent By mcarsill Date 2010-06-30 Time 14:43 Rev Time 0.00
Received By mcarsill Date 2010-06-30 Time 14:03 Sent To  
Notes
2010-06-30 14:43:02PALM BEACH ATLANTIC UNIVERSITY
 1100 SOUTH DIXIE HIGHWAY
 PERMIT NUMBER 10060137
  
  
 1. THE EXIT SIGN IN THE PREP KITCHEN 103 IS TO BE
 REMOVED. THIS EXIT SIGN LEADS PERSONS TO AN AREA THAT
 DOES PROVIDE EXITING.
  
 2. ANY NEW HOODS OR FIRE SUPPRESSION SYSTEMS SHALL BE
 PROPERLY PERMITTED AND APPROVED PRIOR TO CONSTRUCTION.
  
 3. ON JUNE 30, 2010, THIS WRITER CONTACTED TIPTON
 ASSOCIATES AND SPOKE TO ERIN MORGAN. SHE WAS ADVISED
 THAT THE EXIT SIGN IS TO BE REMOVED FROM THE PREP
 KITCHEN AREA.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-06-25 Cont ID  
Sent By mawillia Date 2010-06-25 Time 16:02 Rev Time 0.00
Received By mawillia Date 2010-06-25 Time 15:18 Sent To  
Notes
2010-06-25 16:02:38****DENIED*****
  
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 3. PLEASE SEE BUILDING EXAMINER'S COMMENT #6D.
  
 4. PLEASE PROVIDE A DOOR SCHEDULE.
  
 5. AS SHOWN ON SHEET G002, ONE MAY EGRESS FROM PREP
 KITCHEN AREA [103] THROUGH A MARKED EXIT SINGLE DOOR
 INTO THE DRY STORAGE ROOM [104] . FROM THERE, IT IS
 SHOWN THAT ONE MUST PROCEED THROUGH AN UNMARKED EXIT
 DOUBLE DOORS TO CONTINUE EGRESS. PLEASE EXPLAIN WHAT
 AREA/ROOM IS BEYOND THESE DOUBLE DOORS.
  
 6. PLANS DO NOT INDICATE IF THE PROJECTED SCOPE OF WORK
 WILL HAVE CAUSE FOR THE FIRE ALARM AND/OR FIRE
 SPRINKLER DEVICES TO BE ALTERED TO ACCOMMODATE THE NEW
 FLOOR PLAN.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-25 Cont ID  
Sent By mawillia Date 2010-06-25 Time 15:21 Rev Time 0.00
Received By mawillia Date 2010-06-08 Time 08:28 Sent To  
Notes
2010-06-10 08:29:35INCOMING SENT TO C-13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-07-01 Cont ID  
Sent By jwitmer Date 2010-07-01 Time 12:51 Rev Time 0.00
Received By jwitmer Date 2010-07-01 Time 12:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-07-07 Cont ID  
Sent By dwise Date 2010-07-07 Time 10:53 Rev Time 0.00
Received By dwise Date 2010-07-07 Time 10:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-06-24 Cont ID  
Sent By rregueir Date 2010-06-24 Time 15:47 Rev Time 0.00
Received By rregueir Date 2010-06-24 Time 15:42 Sent To  
Notes
2010-06-24 15:47:00REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PROVIDE VENTILATION CALCULATIONS FOR ALL RECONFIGURED
 SPACES WITHIN THE WORK AREA IN ACCORDANCE WITH FBC-EB
 709.1 AND FBC-M 403.3. INCLUDE SPACE-BY-SPACE
 CALCULATIONS FOR OCCUPANCY CLASSIFICATION, OCCUPANT
 LOAD AND VENTILATION RATES IN ACCORDANCE WITH FBC-M
 TABLE 403.3.
  
 NOTE: COMMERCIAL KITCHEN EXHAUST/VENTILATION SYSTEM IS
 NOT PART OF THE SCOPE FOR THIS REVIEW. SEPARATE PLANS
 AND PERMIT APPLICATIONS ARE REQUIRED FOR HOOD SYSTEMS,
 SUPPRESSION SYSTEMS AND WALK-IN COOLERS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-06-24 Cont ID  
Sent By lwagner Date 2010-06-24 Time 12:27 Rev Time 0.00
Received By lwagner Date 2010-06-24 Time 10:04 Sent To  
Notes
2010-06-24 12:18:30*****PROVISO*****
  
 1. PLUMBER SHALL VERIFY THAT FLOOR SINKS LINES
 ARE CONNECTED TO GREASE TRAP/INTERCEPTOR.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2010-06-22 Cont ID  
Sent By jroach Date 2010-06-22 Time 17:00 Rev Time 0.00
Received By jroach Date 2010-06-22 Time 17:00 Sent To  
Notes
***NONE***