Plan Review Details - Permit 10060133
Plan Review Stops For Permit 10060133
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2010-06-08 Cont ID  
Sent By dlauderm Date 2010-06-08 Time 15:30 Rev Time 1.00
Received By dlauderm Date 2010-06-08 Time 15:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-06-24 Cont ID  
Sent By mawillia Date 2010-06-24 Time 18:52 Rev Time 0.00
Received By mawillia Date 2010-06-24 Time 17:58 Sent To  
Notes
2010-06-24 18:56:17*****APPROVED*****
  
 THE PLAN WAS FIRE-STAMPED ACCORDINGLY; READY FOR PERMIT
 ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-06-16 Cont ID  
Sent By mawillia Date 2010-06-16 Time 15:48 Rev Time 0.00
Received By mawillia Date 2010-06-16 Time 12:37 Sent To  
Notes
2010-06-16 15:53:12*****DENIED*****
  
 1) PROVIDE CHECK VALVE IN FEED MAIN FROM FIRE
 DEPARTMENT CONNECTION.
  
 2) PROVIDE DETAIL OF FIRE DEPARTMENT CONNECTION.
  
 3) FLUSH THE FIRE MAINS PER NFPA 24.
  
 4) DOCK "B" IS NOT REFERENCED ANYWHERE ON SHEET C-4.
  
 5) PROVIDE NUMERICAL ADDRESS OF JOB IN THE TITLEBLOCK.
  
 6) PROVIDE ONLY SHEETS PERTINENT TO FIRE PROTECTION;
 IRRIGATION PLANS ETC. NOT WANTED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6722
 561-805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-23 Cont ID  
Sent By vmolina Date 2010-06-23 Time 10:47 Rev Time 0.00
Received By vmolina Date 2010-06-23 Time 10:47 Sent To  
Notes
2010-06-23 10:47:46IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-17 Cont ID  
Sent By rmcdouga Date 2010-06-16 Time 12:37 Rev Time 0.00
Received By rmcdouga Date 2010-06-07 Time 09:34 Sent To  
Notes
2010-06-07 09:34:47IN ENG. BOX