Plan Review Details - Permit 10060072
Plan Review Stops For Permit 10060072
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-06-10 Cont ID  
Sent By lmartine Date 2010-06-10 Time 15:41 Rev Time 0.00
Received By lmartine Date 2010-06-10 Time 15:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-06-09 Cont ID  
Sent By jleahy Date 2010-06-09 Time 14:26 Rev Time 0.00
Received By jleahy Date 2010-06-09 Time 14:08 Sent To  
Notes
2010-06-09 14:24:07PLAN STILL HAS WRONG CIRCUITS LISTED PLEASE CHECK PANEL
 SCHEDULE AGAINST BRANCH CIRCUITS.
  
 BATH FANS 277V ?
  
 OUTLET UNDER BACK BAR IN THE FRONT FOR ROPE LIGHTING
 CAN NOT BE CONTROLED BY A DIMMER.
  
 A/C HANDLER MAY REQUIRE DISCONNECT BY UNIT (WITHIN
 SIGHT)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-06-11 Cont ID  
Sent By mawillia Date 2010-06-11 Time 14:47 Rev Time 0.00
Received By mawillia Date 2010-06-11 Time 14:29 Sent To  
Notes
2010-06-11 14:46:59*****REVISION #3, DATED 5/18/10, APPROVED*****
  
 REVISED PLAN SHEETS L-S.1, A-2.2, A-2.3, A-4.0, AND
 E-2.0 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-07-01 Cont ID  
Sent By rregueir Date 2010-07-01 Time 11:36 Rev Time 0.00
Received By rregueir Date 2010-07-01 Time 11:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-06-18 Time   Rev Time 0.00
Received By vmolina Date 2010-06-02 Time 13:05 Sent To  
Notes
2010-06-02 13:09:44B-19

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-07-01 Cont ID  
Sent By rregueir Date 2010-07-01 Time 11:35 Rev Time 0.00
Received By rregueir Date 2010-07-01 Time 11:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-06-18 Cont ID  
Sent By hmoser Date 2010-06-18 Time 11:03 Rev Time 0.00
Received By hmoser Date 2010-06-18 Time 11:03 Sent To  
Notes
2010-06-18 11:04:55PLAN DENIED
 DUCT SIZES NOT MARKED ON PLAN .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2010-06-07 Time   Rev Time 0.00
Received By lwagner Date 2010-06-07 Time 10:20 Sent To  
Notes
2010-06-07 10:43:43REVISION OK