Plan Review Details - Permit 10060054
Plan Review Stops For Permit 10060054
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-07-01 Cont ID  
Sent By jwitmer Date 2010-07-01 Time 14:53 Rev Time 0.77
Received By jwitmer Date 2010-07-01 Time 14:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-08 Cont ID  
Sent By jwitmer Date 2010-06-08 Time 12:27 Rev Time 4.50
Received By jwitmer Date 2010-06-08 Time 12:27 Sent To  
Notes
2010-06-08 12:29:02BUILDING PLAN REVIEW
 PERMIT:10050105/
 REVISION: 10060054
 ADD: 500 FERN ST
 CONT: MINUTEMAN CONSTRUCTION
 TEL: (561)644-9426
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE BUILDING TYPE: II-B, UNPROTECTED / SPRINKLED
  
 1) COVERSHEET INDICATES THE LEVEL OF ALTERATION TO BE
 LEVEL 1. PLEASE REVIEW 2007 FBC EXIST BLDG CODE SECTION
 404.1.
 404.1 SCOPE. LEVEL 2 ALTERATIONS INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION
 OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION
 OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT.
  
 2) SHEET A-1:
 2A) IN THE UPPER RIGHT CORNER OF THE PLANS, THEY SHOW
 AN EXISTING VERTICAL EXIT ENCLOSURE WITH TWO ISSUES:
  
 2A)(1) THE VERTICAL EXIT ENCLOSURE DOES NOT HAVE ??
 HOUR FIRE RATED DOORS SEPARATING IT FROM THE REMAINDER
 OF THE EXIT ACCESS CORRIDORS. SINCE THERE IS NO
 SEPARATION THE HORIZONTAL EXTENSION OF THE VERTICAL
 EXIT ( 1 HR/ FBC- 1020.1) WOULD BE CONSIDERED A EXIT
 PASSAGEWAY REQUIRING THE CONTINUATION OF ONE HOUR RATED
 WALLS WITH ONE HOUR OPENING PROTECTIVE???S ( FBC-TABLE
 715.4 SHAFTS/ EXIT ENCLOSURES & EXIT PASSAGE WAYS).
  
 2A)(2) THE PLANS SHOW AN EXISTING ELEVATOR SHAFT WITH
 DOORS OPENING INTO THE VERTICAL EXIT. PERMIT #
 91-B-02716 ON THE FIRST FLOOR INDICATED THE SHAFT TO BE
 WALLED UP AND THE PLANS ALSO INDICATE SHOP DRAWINGS
 WITH A NEW INFILL OF THE SECOND FLOOR WITHIN THE
 ELEVATOR SHAFT WITH STEEL SHOP DRAWINGS, ELIMINATING
 THE USE OF THE ELEVATOR.
 2007 FBC 1020.1 ELEVATOR SHAFTS SHALL NOT OPEN INTO AN
 EXIT ENCLOSURE.
  
 2B) THE CORRIDORS WITH WALL TAG #4 INDICATE A 1 HR
 RATING BUT THE PLANS DO NOT INDICATE THE CONSTRUCTION
 OF THE OTHER NEW WALL TYPES. NO OTHER WALL TAGS ARE
 INDICATED. PLANS WILL NEED TO IDENTIFY WALL
 CONSTRUCTION BY STUD TYPE MATERIAL, SIZE, SPACING AND
 WALL FINISH MATERIALS. FBC-B 106.1.2 ADDITIONAL
 INFORMATION REQUIRED,
 FBC-B 603.1 & FBC-B TABLE 1017.1.
 2C) DOOR IDENTIFICATION INDICATES F.R. I TAKE THIS TO
 BE FIRE RATED DOORS BUT THERE IS NO LEGEND TO PROVIDE
 THE HOURLY RATING REQUIRED 2007 FBC-B TABLE 715.4 AND
 IF THERE IS TO BE ANY GLAZED OPENINGS WITHIN THE FIRE
 RATED DOORS (TABLE 715.5 & TABLE 715.5.3.
  
 2D) THE BOX OFFICE INDICATES THE USE OF A SLIDING GLASS
 WINDOW WHICH AS SHOWN IS STILL LOCATED WITHIN A EXIT
 PASSAGE WAY REQUIRING A ONE HOUR WALL RATING AS WELL AS
 A ONE HOUR OPENING PROTECTIVE PER TABLE 715.4. THE
 OTHER ISSUE WITH THIS AREA THE WALL RATING IS
 ELIMINATED, PLEASE REVIEW 2007 FBC-B TABLE 1017.1 FOR
 ASSEMBLY OCCUPANCIES.
  
 2E) THE PERFORMANCE SPACE WILL NEED TO INDICATE WHERE
 THE PUBLIC SEATING IS LOCATED AS WELL AS THE STAGE
 LOCATION, PLEASE PROVIDE A LIFE SAFETY PLAN FOR BOTH
 THE FIRST AND SECOND FLOORS. 2007 FBC-B 106.3.5.1.1
 MINIMUM PLAN REVIEW REQUIREMENTS.
  
 2F) COSTUME SHOP- IS THIS A MERCANTILE OR RETAIL AREA?
  
 2G) SCENE SHOP PLEASE PROVIDE ADDITIONAL INFORMATION.
 WHAT IS THE PURPOSE OR USE OF THIS SPACE, WILL SCENES
 AND PROPS BE STORED THERE OR WILL THEY BE BUILT THERE.
 IF THE SCENES ARE BEING BUILT THERE WILL THERE BE
 CONSTRUCTION DUST AS SAW DUST?
 COMBUSTIBLE DUST. FINELY DIVIDED SOLID MATERIAL THAT IS
 420 MICRONS OR LESS IN DIAMETER AND WHICH, WHEN
 DISPERSED IN AIR IN THE PROPER PROPORTIONS, COULD BE
 IGNITED BY A FLAME, SPARK OR OTHER SOURCE OF IGNITION.
 COMBUSTIBLE DUST WILL PASS THROUGH A U.S. NO. 40
 STANDARD SIEVE.
 DEFLAGRATION. AN EXOTHERMIC REACTION, SUCH AS THE
 EXTREMELY RAPID OXIDATION OF A FLAMMABLE DUST OR VAPOR
 IN AIR, IN WHICH THE REACTION PROGRESSES THROUGH THE
 UNBURNED MATERIAL AT A RATE LESS THAN THE VELOCITY OF
 SOUND. A DEFLAGRATION CAN HAVE AN EXPLOSIVE EFFECT.
  
 PLEASE REVIEW FBC-B TABLE 414.5.1 EXPLOSION CONTROL
 REQUIREMENTS- COMBUSTIBLE DUST.
  
 2H) SCENE SHOP DOOR TYPE # 2, IS MISSING THE 12??? ON
 THE CORRIDOR SIDE ON THE LATCH SIDE OF DOOR. 2007 FBC-B
 11-4.13.6 MANEUVERING CLEARANCES AT DOORS.
  
 2I) THE TYPICAL STAIR DETAIL PROVIDED HAS ALL
 REFERENCES AND DIMENSIONS TO THE 2007 FBC-RESIDENTIAL
 CODE PLEASE UPDATE TO THE CORRECT CODE REFERENCES. THE
 DETAIL INDICATES THE USE OF ????? T & G FLOORING, NOTE
 TYPE I / TYPE II CONSTRUCTION FBC-B 1009.5 STAIRS ARE
 TO BE BUILT OF THE SAME MATERIALS WITH THE TYPE
 PERMITTED FOR THE TYPE OF CONSTRUCTION AS THE BUILDING
 TYPE.
  
 2J) PLEASE PROVIDE FLOOR AND FRAMING DETAILS FOR THE
 DJ???S RAISED FLOOR. FBC-B 603.1, FBC-B 1009.5 & FBC-B
 1009.1 HANDRAILS.
  
 2K) BOTH EXIT ACCESS CORRIDORS AND EXIT PASSAGE WAYS
 INDICATE THE USE OF CARPETED FLOORS, PLEASE COMPLY WITH
 FBC-B 804.4.1 MINIMUM CRITICAL RADIANT FLUX. INTERIOR
 FLOOR FINISH AND FLOOR COVERING MATERIALS IN EXIT
 ENCLOSURES, EXIT PASSAGEWAYS AND CORRIDORS SHALL NOT BE
 LESS THAN CLASS I IN GROUPS I-2 AND I-3 AND NOT LESS
 THAN CLASS II IN GROUPS A, B, E, H, I-4, M, R-1, R-2
 AND S. IN ALL AREAS, FLOOR COVERING MATERIALS SHALL
 COMPLY WITH THE DOC FF-1 "PILL TEST" (CPSC 16 CFR, PART
 1630).
  
 2L) PLANS WILL ALSO NEED TO SHOW COMPLIANCE WITH
 INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY
 OCCUPANCY FBC-B TABLE 803.5.
  
 3) SHEET A-2:
 3A) THE REHEARSAL STUDIO DOORS LABELED # 2 BOTH ARE
 MISSING THE REQUIRED 18??? PULL SIDE OF DOORS FBC-B
 11-4.13.6.
  
 3B) DRESSING ROOM DOORS LABELED # 2 BOTH ARE MISSING
 THE REQUIRED 18??? PULL SIDE OF DOORS FBC-B 11-4.13.6.
  
 3C) THE DESIGN CLASSROOM OUT SWING DOOR # 2 SWINGS OVER
 50% OF THE REQUIRED CORRIDOR WIDTH. FBC-B 1008.1.8.8.
  
 3D) THE PLANS INDICATE THE CORRIDORS TO BE RATED,
 PARTIALLY SEE STUDENT WORK ROOM?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 3E) THE STUDENT WORK ROOM IS PART OF THE CORRIDOR AND
 ALSO INDICATES THE USE OF CARPET, PLEASE SHOW
 COMPLIANCE WITH 804.4.1 MINIMUM CRITICAL RADIANT FLUX.
 INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS IN
 EXIT ENCLOSURES, EXIT PASSAGEWAYS AND CORRIDORS SHALL
 NOT BE LESS THAN CLASS I IN GROUPS I-2 AND I-3 AND NOT
 LESS THAN CLASS II IN GROUPS A, B, E, H, I-4, M, R-1,
 R-2 AND S. IN ALL AREAS, FLOOR COVERING MATERIALS SHALL
 COMPLY WITH THE DOC FF-1 "PILL TEST" (CPSC 16 CFR, PART
 1630).
  
 3F) THE PLANS INDICATE ELEVATOR DOORS BUT NO RATING,
 FBC-B TABLE 715.4.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-07-13 Cont ID  
Sent By btrobaug Date 2010-07-13 Time 14:41 Rev Time 0.00
Received By btrobaug Date 2010-07-13 Time 14:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-06-09 Cont ID  
Sent By btrobaug Date 2010-06-09 Time 12:38 Rev Time 0.00
Received By btrobaug Date 2010-06-09 Time 11:35 Sent To  
Notes
2010-06-09 12:37:59THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
  
 1} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE
 13-415.1AB.1.1 FOR TIME CLOCK REQUIREMENTS. ALL THAT IS
 REQUIRED FOR THE ELECTRICAL REVIEW IS THE BASIC
 PRESCRIPTIVE REQUIREMENTS. SEE 13-415.2.AB.5 INTERIOR
 LIGHTING POWER, SCOPE.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 2} SUBMIT A LEGEND OF FIXTURE TYPES AND WATTAGES ON THE
 PLAN TO CORRELATE WITH THE ONES IN THE CALCULATIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-07-23 Cont ID  
Sent By wjolin Date 2010-07-23 Time 15:59 Rev Time 0.00
Received By wjolin Date 2010-07-23 Time 15:58 Sent To  
Notes
2010-07-23 15:59:00*****APPROVED*****
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-07-23 Cont ID  
Sent By wjolin Date 2010-07-23 Time 15:58 Rev Time 0.00
Received By wjolin Date 2010-07-01 Time 14:37 Sent To  
Notes
2010-07-01 14:39:11INCOMING TO B-7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-01 Cont ID  
Sent By hmoser Date 2010-06-16 Time 14:56 Rev Time 0.00
Received By jwitmer Date 2010-06-02 Time 09:55 Sent To  
Notes
2010-06-02 10:00:26B-5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-07-13 Cont ID  
Sent By rregueir Date 2010-07-13 Time 13:26 Rev Time 0.00
Received By rregueir Date 2010-07-13 Time 13:26 Sent To  
Notes
2010-07-13 13:26:41REVISED M-1 AND M-2 DATED 7/8/2010

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-06-16 Cont ID  
Sent By hmoser Date 2010-06-16 Time 12:40 Rev Time 0.00
Received By hmoser Date 2010-06-16 Time 10:15 Sent To  
Notes
2010-06-16 13:56:51PLANS DENIED
 1) PLEASE IDENTIFY WALLS WITH A KEY ON THE LIFE SAFTY
 PLANS .
 2) PLEASE PROVIDE A LIFE SAFTY PLAN WITH THE PLANS.
 3) PLEASE REFER TO SECTION 607.5.1 FIRE WALLS.
 4) PLEASE REFER TO SECTION607.7 FLEXIBLE DUCT AND AIR
 CONNECTORS .
 5) PLEASE REFER TO SECTION 607.8 LOCATION AND
 INSTALLATION DETAILS .
 6) PLEASE REFER TO TABLE 403.3 OUT DOOR VENTILATION
 PUBLIC SPACES ( TOILET ROOMS )
 7) PLEASE SHOW ON THE PLANS WHERE THE FRESH AIR
 CALCULATIONS ARE COMING FROM .
 8) PLEASE IDENTIFY THE EQUIPMENT ON THE PLANS (AHU #1
 AND THE SIZE OF EQUIPMENT)
 9) PLANS MUST BE CEILED BY ARCHITECT OR ENGINEER .
 10) PLEASE REFER TO SECTION 601.4 BALANCED RETURN AIR .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-07-08 Cont ID  
Sent By lwagner Date 2010-07-08 Time 08:05 Rev Time 0.00
Received By lwagner Date 2010-07-07 Time 08:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-06-15 Cont ID  
Sent By lwagner Date 2010-06-15 Time 13:06 Rev Time 0.00
Received By lwagner Date 2010-06-09 Time 14:23 Sent To  
Notes
2010-06-09 14:42:09PLUMBING REVIEW
 DENIED:
  
 SHEETS A-1 & A-2:
 WATER CLOSETS IN STALLS IN ACCESSIBLE STALLS SHALL
 COMPLY WITH FIGURE 30E
 FBC 2007 11-4.1.3(11) TOILET FACILITIES. IF TOILET
 ROOMS ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE
 TOILET ROOM SHALL COMPLY WITH SECTION 11-4.22.
 WATER CLOSETS IN ACCESSIBLE STALLS SHALL COMPLY WITH
 FIGURE 30E
  
 SHEET P-1
 1. FBC 2004 WPB AMENDMENTS106.3.5.1.3 : DOMESTIC WATER
 RISER DIAGRAM REQUIRED.
  
 2. A VENT IS REQUIRED BETWEEN THE 2 SHOWERS- FBC 2007
 PLUMBING 901.2.1 VENTING REQUIRED. EVERY TRAP AND
 TRAPPED FIXTURE SHALL BE VENTED IN ACCORDANCE WITH ONE
 OF THE VENTING METHODS SPECIFIED IN THIS CHAPTER.
  
 3. THE VERTICAL DRY VENT BETWEEN THE SHOWERS MAY SERVE
 AS THE CURCUIT VENT FOR THE 4 WATER CLOSETS ON THE
 SECOND FLOOR
 911.2 VENT CONNECTION. THE CIRCUIT VENT CONNECTION
 SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM FIXTURE
 DRAINS. THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 AND SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905.
 THE CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE
 OF ANY SOIL OR WASTE.
  
 4. A URINAL ON THE 2ND FLOOR IS LABELED AS SINK.
  
 5. THE SOIL STACK SERVING THE 2ND FLOOR REQUIRES A
 CLEANOUT.
  
 6. 911.3 THE WASTE FROM THE 2ND FLOOR IS NOT PERMITTED
 TO FLOW THROUGH THE 1ST FLOOR CURCUIT VENT. ATTACH THE
 2ND FLOOR DOWNSTREAM OF THE 1ST WATER CLOSET ON THE 1ST
 FLOOR.
  
 7. A DRY VERTICAL CURCUIT VENT IS REQUIERED BETWEEN THE
 TWO MOST UPSTREAM WATER CLOSETS ON THE FIRST FLOOR.
  
 8. 20 FIXTURE UNITS ARE MAXIMUM FOR A 3" BRANCH. 4"
 PIPE IS REQUIRED UP TO THE BRANCHES BEFORE THE WATER
 CLOSETS ON THE SECOND FLOOR.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  