| 2010-06-08 12:29:02 | BUILDING PLAN REVIEW |
| | PERMIT:10050105/ |
| | REVISION: 10060054 |
| | ADD: 500 FERN ST |
| | CONT: MINUTEMAN CONSTRUCTION |
| | TEL: (561)644-9426 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | NOTE BUILDING TYPE: II-B, UNPROTECTED / SPRINKLED |
| | |
| | 1) COVERSHEET INDICATES THE LEVEL OF ALTERATION TO BE |
| | LEVEL 1. PLEASE REVIEW 2007 FBC EXIST BLDG CODE SECTION |
| | 404.1. |
| | 404.1 SCOPE. LEVEL 2 ALTERATIONS INCLUDE THE |
| | RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION |
| | OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION |
| | OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL |
| | EQUIPMENT. |
| | |
| | 2) SHEET A-1: |
| | 2A) IN THE UPPER RIGHT CORNER OF THE PLANS, THEY SHOW |
| | AN EXISTING VERTICAL EXIT ENCLOSURE WITH TWO ISSUES: |
| | |
| | 2A)(1) THE VERTICAL EXIT ENCLOSURE DOES NOT HAVE ?? |
| | HOUR FIRE RATED DOORS SEPARATING IT FROM THE REMAINDER |
| | OF THE EXIT ACCESS CORRIDORS. SINCE THERE IS NO |
| | SEPARATION THE HORIZONTAL EXTENSION OF THE VERTICAL |
| | EXIT ( 1 HR/ FBC- 1020.1) WOULD BE CONSIDERED A EXIT |
| | PASSAGEWAY REQUIRING THE CONTINUATION OF ONE HOUR RATED |
| | WALLS WITH ONE HOUR OPENING PROTECTIVE???S ( FBC-TABLE |
| | 715.4 SHAFTS/ EXIT ENCLOSURES & EXIT PASSAGE WAYS). |
| | |
| | 2A)(2) THE PLANS SHOW AN EXISTING ELEVATOR SHAFT WITH |
| | DOORS OPENING INTO THE VERTICAL EXIT. PERMIT # |
| | 91-B-02716 ON THE FIRST FLOOR INDICATED THE SHAFT TO BE |
| | WALLED UP AND THE PLANS ALSO INDICATE SHOP DRAWINGS |
| | WITH A NEW INFILL OF THE SECOND FLOOR WITHIN THE |
| | ELEVATOR SHAFT WITH STEEL SHOP DRAWINGS, ELIMINATING |
| | THE USE OF THE ELEVATOR. |
| | 2007 FBC 1020.1 ELEVATOR SHAFTS SHALL NOT OPEN INTO AN |
| | EXIT ENCLOSURE. |
| | |
| | 2B) THE CORRIDORS WITH WALL TAG #4 INDICATE A 1 HR |
| | RATING BUT THE PLANS DO NOT INDICATE THE CONSTRUCTION |
| | OF THE OTHER NEW WALL TYPES. NO OTHER WALL TAGS ARE |
| | INDICATED. PLANS WILL NEED TO IDENTIFY WALL |
| | CONSTRUCTION BY STUD TYPE MATERIAL, SIZE, SPACING AND |
| | WALL FINISH MATERIALS. FBC-B 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED, |
| | FBC-B 603.1 & FBC-B TABLE 1017.1. |
| | 2C) DOOR IDENTIFICATION INDICATES F.R. I TAKE THIS TO |
| | BE FIRE RATED DOORS BUT THERE IS NO LEGEND TO PROVIDE |
| | THE HOURLY RATING REQUIRED 2007 FBC-B TABLE 715.4 AND |
| | IF THERE IS TO BE ANY GLAZED OPENINGS WITHIN THE FIRE |
| | RATED DOORS (TABLE 715.5 & TABLE 715.5.3. |
| | |
| | 2D) THE BOX OFFICE INDICATES THE USE OF A SLIDING GLASS |
| | WINDOW WHICH AS SHOWN IS STILL LOCATED WITHIN A EXIT |
| | PASSAGE WAY REQUIRING A ONE HOUR WALL RATING AS WELL AS |
| | A ONE HOUR OPENING PROTECTIVE PER TABLE 715.4. THE |
| | OTHER ISSUE WITH THIS AREA THE WALL RATING IS |
| | ELIMINATED, PLEASE REVIEW 2007 FBC-B TABLE 1017.1 FOR |
| | ASSEMBLY OCCUPANCIES. |
| | |
| | 2E) THE PERFORMANCE SPACE WILL NEED TO INDICATE WHERE |
| | THE PUBLIC SEATING IS LOCATED AS WELL AS THE STAGE |
| | LOCATION, PLEASE PROVIDE A LIFE SAFETY PLAN FOR BOTH |
| | THE FIRST AND SECOND FLOORS. 2007 FBC-B 106.3.5.1.1 |
| | MINIMUM PLAN REVIEW REQUIREMENTS. |
| | |
| | 2F) COSTUME SHOP- IS THIS A MERCANTILE OR RETAIL AREA? |
| | |
| | 2G) SCENE SHOP PLEASE PROVIDE ADDITIONAL INFORMATION. |
| | WHAT IS THE PURPOSE OR USE OF THIS SPACE, WILL SCENES |
| | AND PROPS BE STORED THERE OR WILL THEY BE BUILT THERE. |
| | IF THE SCENES ARE BEING BUILT THERE WILL THERE BE |
| | CONSTRUCTION DUST AS SAW DUST? |
| | COMBUSTIBLE DUST. FINELY DIVIDED SOLID MATERIAL THAT IS |
| | 420 MICRONS OR LESS IN DIAMETER AND WHICH, WHEN |
| | DISPERSED IN AIR IN THE PROPER PROPORTIONS, COULD BE |
| | IGNITED BY A FLAME, SPARK OR OTHER SOURCE OF IGNITION. |
| | COMBUSTIBLE DUST WILL PASS THROUGH A U.S. NO. 40 |
| | STANDARD SIEVE. |
| | DEFLAGRATION. AN EXOTHERMIC REACTION, SUCH AS THE |
| | EXTREMELY RAPID OXIDATION OF A FLAMMABLE DUST OR VAPOR |
| | IN AIR, IN WHICH THE REACTION PROGRESSES THROUGH THE |
| | UNBURNED MATERIAL AT A RATE LESS THAN THE VELOCITY OF |
| | SOUND. A DEFLAGRATION CAN HAVE AN EXPLOSIVE EFFECT. |
| | |
| | PLEASE REVIEW FBC-B TABLE 414.5.1 EXPLOSION CONTROL |
| | REQUIREMENTS- COMBUSTIBLE DUST. |
| | |
| | 2H) SCENE SHOP DOOR TYPE # 2, IS MISSING THE 12??? ON |
| | THE CORRIDOR SIDE ON THE LATCH SIDE OF DOOR. 2007 FBC-B |
| | 11-4.13.6 MANEUVERING CLEARANCES AT DOORS. |
| | |
| | 2I) THE TYPICAL STAIR DETAIL PROVIDED HAS ALL |
| | REFERENCES AND DIMENSIONS TO THE 2007 FBC-RESIDENTIAL |
| | CODE PLEASE UPDATE TO THE CORRECT CODE REFERENCES. THE |
| | DETAIL INDICATES THE USE OF ????? T & G FLOORING, NOTE |
| | TYPE I / TYPE II CONSTRUCTION FBC-B 1009.5 STAIRS ARE |
| | TO BE BUILT OF THE SAME MATERIALS WITH THE TYPE |
| | PERMITTED FOR THE TYPE OF CONSTRUCTION AS THE BUILDING |
| | TYPE. |
| | |
| | 2J) PLEASE PROVIDE FLOOR AND FRAMING DETAILS FOR THE |
| | DJ???S RAISED FLOOR. FBC-B 603.1, FBC-B 1009.5 & FBC-B |
| | 1009.1 HANDRAILS. |
| | |
| | 2K) BOTH EXIT ACCESS CORRIDORS AND EXIT PASSAGE WAYS |
| | INDICATE THE USE OF CARPETED FLOORS, PLEASE COMPLY WITH |
| | FBC-B 804.4.1 MINIMUM CRITICAL RADIANT FLUX. INTERIOR |
| | FLOOR FINISH AND FLOOR COVERING MATERIALS IN EXIT |
| | ENCLOSURES, EXIT PASSAGEWAYS AND CORRIDORS SHALL NOT BE |
| | LESS THAN CLASS I IN GROUPS I-2 AND I-3 AND NOT LESS |
| | THAN CLASS II IN GROUPS A, B, E, H, I-4, M, R-1, R-2 |
| | AND S. IN ALL AREAS, FLOOR COVERING MATERIALS SHALL |
| | COMPLY WITH THE DOC FF-1 "PILL TEST" (CPSC 16 CFR, PART |
| | 1630). |
| | |
| | 2L) PLANS WILL ALSO NEED TO SHOW COMPLIANCE WITH |
| | INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY |
| | OCCUPANCY FBC-B TABLE 803.5. |
| | |
| | 3) SHEET A-2: |
| | 3A) THE REHEARSAL STUDIO DOORS LABELED # 2 BOTH ARE |
| | MISSING THE REQUIRED 18??? PULL SIDE OF DOORS FBC-B |
| | 11-4.13.6. |
| | |
| | 3B) DRESSING ROOM DOORS LABELED # 2 BOTH ARE MISSING |
| | THE REQUIRED 18??? PULL SIDE OF DOORS FBC-B 11-4.13.6. |
| | |
| | 3C) THE DESIGN CLASSROOM OUT SWING DOOR # 2 SWINGS OVER |
| | 50% OF THE REQUIRED CORRIDOR WIDTH. FBC-B 1008.1.8.8. |
| | |
| | 3D) THE PLANS INDICATE THE CORRIDORS TO BE RATED, |
| | PARTIALLY SEE STUDENT WORK ROOM? |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 3E) THE STUDENT WORK ROOM IS PART OF THE CORRIDOR AND |
| | ALSO INDICATES THE USE OF CARPET, PLEASE SHOW |
| | COMPLIANCE WITH 804.4.1 MINIMUM CRITICAL RADIANT FLUX. |
| | INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS IN |
| | EXIT ENCLOSURES, EXIT PASSAGEWAYS AND CORRIDORS SHALL |
| | NOT BE LESS THAN CLASS I IN GROUPS I-2 AND I-3 AND NOT |
| | LESS THAN CLASS II IN GROUPS A, B, E, H, I-4, M, R-1, |
| | R-2 AND S. IN ALL AREAS, FLOOR COVERING MATERIALS SHALL |
| | COMPLY WITH THE DOC FF-1 "PILL TEST" (CPSC 16 CFR, PART |
| | 1630). |
| | |
| | 3F) THE PLANS INDICATE ELEVATOR DOORS BUT NO RATING, |
| | FBC-B TABLE 715.4. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |