Plan Review Details - Permit 10050628
Plan Review Stops For Permit 10050628
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-09-15 Cont ID  
Sent By jwitmer Date 2010-09-15 Time 14:21 Rev Time 0.67
Received By jwitmer Date 2010-09-15 Time 14:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-07-22 Cont ID  
Sent By jwitmer Date 2010-07-22 Time 09:03 Rev Time 0.00
Received By jwitmer Date 2010-07-22 Time 09:03 Sent To  
Notes
2010-07-22 09:05:00BUILDING PLAN REVIEW
 PERMIT:10050628
 ADD: 6505 S DIXIE HWY # 101
 CONT: R& K CONTRACTING
 TEL: (561)214-3682
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 JULY 22/ 2010
 2ND REVIEW
 ACTION: DENIED
  
 1) SHEET 1.1 INDICATES A MAXIMUM OF 75 FEET TRAVEL
 DISTANCE IN COMPLIANCE WITH 1019.2. IN ACTUALLITY THE
 TRAVEL DISTANCE IS APPROXIMATELY 88'-0". THE PLANS DO
 INDICATE A NEW REAR EXTERIOR DOOR, BUT THIS CAN NOT BE
 USED AS THE REQUIRED SECONDARY EXIT FOR THE PUBLIC
 SINCE TRAVEL WOULD BE THROUGH THE KITCHEN SERVICE AREA
 SEE 1014.2. 1014.3 COMMON PATH OF TRAVEL IS A LIMIT OF
 75' FROM THE MOST REMOTE POINT IN THE BUILDING AND
 MEASURED ALONG THE NATURAL AND UNOBSTRUCTED PATH TO THE
 EXIT, NOT IN A STRAIGHT LINE AS THE CROW FLIES..
  
 2)COMPLIED.
  
 3) COMPLIED.
  
 4)NOT REQUIRED, SPOKE WITH IMPACT FEE OFFICE! BEFORE A
 PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE
 PAID TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-09 Cont ID  
Sent By jwitmer Date 2010-06-09 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2010-06-09 Time 14:47 Sent To  
Notes
2010-06-09 15:07:26BUILDING PLAN REVIEW
 PERMIT:10050628
 ADD: 6505 S DIXIE HWY # 101
 CONT: R& K CONTRACTING
 TEL: (561)214-3682
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 JUNE 09/ 2010
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET 1.1 INDICATES A MAXIMUM OF 75 FEET TRAVEL
 DISTANCE IN COMPLIANCE WITH 1019.2. IN ACTUALLITY THE
 TRAVEL DISTANCE IS APPROXIMATELY 88'-0". THE PLANS DO
 INDICATE A NEW REAR EXTERIOR DOOR, BUT THIS CAN NOT BE
 USED AS THE REQUIRED SECONDARY EXIT FOR THE PUBLIC
 SINCE TRAVEL WOULD BE THROUGH THE KITCHEN SERVICE AREA
 SEE 1014.2.
  
 2) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 2A) KAWNEER 350 OUT-SWING DOOR- LARGE MISSILE NOT PART
 OF THE WINDOW NOA SEE NOTES ON PAGE 3 OF 9.
 2B) NEW SOLID CORE EXTERIOR DOOR NO PRODUCT APPROVAL
 SUBMITTED.
  
 3) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4)NOT REQUIRED, SPOKE WITH IMPACT FEE OFFICE! BEFORE A
 PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE
 PAID TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-08-10 Cont ID  
Sent By lmartine Date 2010-08-10 Time 17:19 Rev Time 0.00
Received By lmartine Date 2010-08-10 Time 17:19 Sent To  
Notes
2010-08-10 17:21:20SEE JAKE'S APPROVAL ON SHEETS 6.1 AND 6.2.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-06-09 Cont ID  
Sent By btrobaug Date 2010-06-09 Time 14:02 Rev Time 0.00
Received By btrobaug Date 2010-06-09 Time 13:02 Sent To  
Notes
2010-06-09 14:02:34 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE REFERENCED CODES ON SHEET 6.1 ARE INCORRECT, SEE
 CODES REFERENCED ABOVE AND IN THE 2007 FBC.
  
 2} THE LOAD CALCULATION USED IS FOR DWELLING UNITS, SEE
 ARTICLE 220.10, 220.14 AND ALL APPLICABLE SECTIONS OF
 THAT ARTICLE.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-09-21 Cont ID  
Sent By mcarsill Date 2010-09-21 Time 09:51 Rev Time 0.00
Received By mcarsill Date 2010-09-21 Time 09:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-07-26 Cont ID  
Sent By mcarsill Date 2010-07-26 Time 14:37 Rev Time 0.00
Received By mcarsill Date 2010-07-26 Time 14:28 Sent To  
Notes
2010-07-26 14:37:146405 SOUTH DIXIE HIGHWAY
 PERMIT NUMBER 10050628
  
  
 1. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 3. CARE IS TO BE TAKEN WHEN USING GASOLINE POWERED
 EQUIPMENT INDOORS TO CUT SLABS. CARBON MONOXIDE (CO) IS
 A COLORLESS, ODORLESS, AND TASTELESS GAS AND CAN BE
 FLAMMABLE IN CERTAIN CONCENTRATIONS. PLEASE ENSURE THAT
 PROPER VENTILATION IS PROVIDED WHEN USING THIS
 EQUIPMENT.
  
 4. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 5. FIRE WALLS ARE TO BE PROPERLY IDENTIFIED.
  
 6. PLEASE ENSURE THAT TRAVEL DISTANCE TO REACH EXITS
 ARE CORRECT.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-06-08 Cont ID  
Sent By mawillia Date 2010-06-08 Time 16:50 Rev Time 0.00
Received By mawillia Date 2010-06-08 Time 15:53 Sent To  
Notes
2010-06-08 16:49:58*****DENIED*****
  
  
 1. THE ADDRESS NUMBER LISTED IN THE TITLE BLOCK OF THE
 PLANS (6405) DOES NOT CORRELATE WITH THE ADDRESS NUMBER
 (6505) LISTED ON THE PERMIT APPLICATION. THE ACTUAL
 PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.
  
 2. WHAT WAS THE PREVIOUS OCCUPANCY TYPE?
  
 3. THE PERMIT APPLICATION INDICATES THAT THE PROJECT
 SCOPE OF WORK WILL BE IN SUITE 101 WHICH ENTAILS THAT
 THERE ARE ADDITIONAL TENANT SPACES UNDER THE BUILDING
 ADDRESS OF 6505 SOUTH DIXIE HIGHWAY. PLEASE VERIFY AND
 ADVISE.
  
 4. SPECIFY THE INTERIOR FINISH FOR WALLS AND CEILING IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 5. ON SHEET 6.1, THE 2003 EDITION OF NFPA 101 IS
 INCORRECTLY REFERENCED. THIS SHOULD BE THE 2006 EDITION
 AS CORRECTLY LISTED ON 1.1 SHEET.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-13 Cont ID  
Sent By lmartine Date 2010-09-13 Time 16:27 Rev Time 0.00
Received By lmartine Date 2010-09-13 Time 16:26 Sent To  
Notes
2010-09-13 16:27:12B--3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-07 Cont ID  
Sent By hmoser Date 2010-07-07 Time 09:12 Rev Time 0.00
Received By hmoser Date 2010-05-20 Time 11:31 Sent To  
Notes
2010-05-24 11:34:09TO C8

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-06-24 Cont ID  
Sent By jwitmer Date 2010-06-24 Time 08:23 Rev Time 0.00
Received By jwitmer Date 2010-06-24 Time 08:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-09-15 Cont ID  
Sent By jwitmer Date 2010-09-15 Time 14:27 Rev Time 0.20
Received By jwitmer Date 2010-09-15 Time 14:27 Sent To  
Notes
2010-09-15 14:28:35COMPARE PLANS FROM PREVIOUS REVIEW AND STAMP

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-07-27 Cont ID  
Sent By hmoser Date 2010-07-27 Time 13:44 Rev Time 0.00
Received By hmoser Date 2010-07-27 Time 13:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-07-07 Cont ID  
Sent By hmoser Date 2010-07-07 Time 09:03 Rev Time 0.00
Received By hmoser Date 2010-07-07 Time 09:03 Sent To  
Notes
2010-07-07 09:12:01PLANS DENIED
 1) PLEASE SHOW THE MOTORIZED DAMPER IN THE RETURN AIR
 DUCT ON THE PLANS .
 2) PLEASE PROVIDE THE LOCATION OF THE PACKAGE UNIT ON
 THE ROOF OR GROUND ON THE PLANS.
 3) PLEASE REFER TO SECTION 606.2.1 FBC (M) 2007 SUPPLY
 AIR
 4) SEPARATE PERMITS ARE REQUIRED FOR THE WALK IN COOLER
 OR FREEZER
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-05-25 Cont ID  
Sent By lwagner Date 2010-05-25 Time 11:13 Rev Time 0.00
Received By lwagner Date 2010-05-24 Time 11:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-07-02 Cont ID  
Sent By lfranco Date 2010-07-02 Time 12:00 Rev Time 0.00
Received By lfranco Date 2010-07-02 Time 12:00 Sent To M
Notes
2010-07-02 12:03:43PLANNING AND ZONING: *** PASSED, ZONING REVIEW NOT
 REQUIRED: INTERIOR WORK ONLY AND THE VALUE OF PROPOSED
 WORK DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. ****
  
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]