| 2010-06-10 11:46:04 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ROOF TILE ADHESIVE. TILE NOA NOA SUBMITTED CAN'T BE |
| | USED BECAUSE IT DOESN'T MEET THE DESIGN PRESSURES. SEE |
| | DESIGN PRESSURES ON TILE NOA. PROVIDE PRODUCT APPROVAL |
| | FOR ADHESIVE THAT WILL MEET OR EXCEED THE DESIGN |
| | PRESSURES REQUIRED FOR THIS BUILDING LOCATED ON |
| | EXPOSURE "C". |
| | |
| | B) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | C) SEALOFLEX WATERPROOFING NOA 05-0901.04: CLEARLY |
| | IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE USED. |
| | AND, PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA. |
| | |
| | 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS. SEC. 105.3.3 CITY AMENDMENTS TO |
| | FBC. |
| | |
| | 4- ARCHITECTURAL PLANS ARE MISSING DETAILS AND |
| | SPECIFICATIONS FOR ATTIC VENTILATION AS REQUIRED BY |
| | SEC. R806. |
| | |
| | 5- SPECIFY ATTIC ACCESS, SIZE AND LOCATION AS REQUIRED |
| | BY SEC. R807. |
| | |
| | 6- ARCHITECT TO COORDINATE INSULATION INFORMATION. |
| | SHEET A0 AND SHEET A2 SPECIFY DIFFERENT TYPE AND |
| | INSULATION R-VALUE. REVISE AS REQUIRED TO MATCH. ALSO, |
| | COORDINATE WITH THE ENERGY CALCULATIONS. |
| | |
| | 7- ARCHITECT TO SPECIFY CARBON MONOXIDE ALARMS ON PLANS |
| | AS REQUIRED BY SEC. R313.4. |
| | |
| | 8- ARCHITECT TO REVISE WALL LEGEND ON PLANS TO MATCH |
| | FLOOR PLANS. EG: MISSING CONCRETE BLOCK CONSTRUCTION ON |
| | NEW STAIRWAY. REVISE AS REQUIRED. CHECK ALL SHEETS |
| | WHERE-WALL LEGEND IS SHOWN. |
| | |
| | 9- OWES $3919.14 FOR PERMIT FEE BALANCE. |
| | |
| | 10- SHEET A0: REVISE PROJECT INFORMATION. SPECIFY |
| | CURRENT CODE AND REVISE LEVEL OF ALTERATION. THIS IS |
| | NOT LEVEL ONE. |
| | |
| | 11- SHEET A1: A) SPECIFY OPENING WIDTH AT BOTTOM OF |
| | STAIRS TO VERIFY COMPLIANCE WITH THE EGRESS |
| | REQUIREMENTS OF SEC. R311. |
| | |
| | B) BOTTOM LANDING NEEDS TO COMPLY WITH SEC. R311.5.4. |
| | THE WIDTH OF EACH LANDING SHALL NOT BE LESS THAN THE |
| | STAIRWAY SERVED. |
| | |
| | 12- SHEET A2: SPECIFY DIMENSIONS FOR STAIRS TO VERIFY |
| | COMPLIANCE OF LANDINGS WITH SEC. R311.5.4. TH3 WIDTH OF |
| | EACH LANDING SHALL NOT BE LESS THAN THE STAIRWAY |
| | SERVED. |
| | |
| | 13- EXTERIOR ELEVATIONS AND ALL TYPICAL WALL SECTIONS. |
| | REVISE STUCCO THICKNESS FOR FRAMED WALL. 7/8" MIN. |
| | REQUIRED BY TABLE R702.1(1). |
| | |
| | 14- SHEET A8: A) REVISE WINDOW AND DOOR BUCK DETAILS. |
| | BUCK SIZE SPECIFIED NEED TO PROVIDE FULL SUPPORT TO THE |
| | WINDOW/DOOR FRAMES AS REQUIRED BY SEC. R613.6. |
| | |
| | B) CLEARLY SPECIFY ANCHORING OF STRUCTURAL BUCKS. |
| | COORDINATE WITH INFORMATION GIVEN ON STRUCTURAL |
| | DRAWINGS. |
| | |
| | 15- SHEET S1: REVISE DESIGN PRESSURES FOR WALL |
| | OPENINGS. DESIGN PRESSURES SHOWN DON'T REFLECT DESIGN |
| | PRESSURES FOR A BUILDING OF EXPOSURE "C" AND THE HEIGHT |
| | OF THIS STRUCTURE. REVISE AS REQUIRED. |
| | |
| | 16- SHEET S2: CLEARLY SPECIFY SIZE OF STAIRWAY FOOTING. |
| | NONE IDENTIFIED ON FOUNDATION PLAN. |
| | |
| | 17- SHEET S3: CLEARLY IDENTIFY ON FLOOR FRAMING PLAN |
| | WHICH CONNECTORS FROM THE CONNECTOR SCHEDULE ARE GOING |
| | TO BE USED. NONE IDENTIFIED ON FRAMING PLANS. |
| | |
| | 18- SHEET S4: |
| | A) PROVIDE ROOF FRAMING DETAILS FOR WOOD FRAMED |
| | CONSTRUCTION. ONLY MASONRY CONSTRUCTION DETAILS WERE |
| | PROVIDED. |
| | |
| | B) CLEARLY MARK ON ROOF FRAMING PLANS ROOF TRUSS |
| | CONNECTORS TO BE USED. NONE KEYED ON PLANS. KEEP INTO |
| | CONSIDERATION MASONRY OR WOOD TO WOOD CONNECTORS. EG: |
| | HGAM10 IS A MASONRY CONNECTOR NOT WOOD TO WOOD |
| | CONNECTOR. REVISE AS REQUIRED. |
| | |
| | 19- SPECIFY MATERIAL AND LOCATION OF DRAFSTOPPING ON |
| | SECOND FLOOR FRAMING PLAN AS REQUIRED BY SEC. R502.1.2. |
| | |
| | 20- PROVIDE COMPLETE SPECIFICATIONS FOR FLOOR ASSEMBLY |
| | AT NEW BALCONY. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |