Plan Review Details - Permit 10050533
Plan Review Stops For Permit 10050533
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-05-24 Cont ID  
Sent By jwitmer Date 2010-05-24 Time 10:58 Rev Time 0.00
Received By jwitmer Date 2010-05-24 Time 10:49 Sent To  
Notes
2010-05-24 14:48:20BUILDING PLAN REVIEW
 PERMIT: 10050533
 ADD: 900 S OLIVE LASSITER STUDENT CENTER
 CONT: RYCON CONSTRUCTION
 TEL: (412)392-2525
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). A REVISION SHALL BE
 REQUIRED WITH ADDITIONAL REVIEW AND ASSOCIATED FEES.
  
 1) ON BOTH SHEET # A100 & A101 IT APPEARS DIFFERENT
 NOTE LAYERS WERE TURNED OFF. ON BOTH SHEETS THE PLANS
 REFERENCE VARIOUS FEATURES WITH NUMBERED SQUARES,
 DIAMONDS AND HEXAGON WITH NO ASSOCIATED NOTES.
 FBC-B* 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 2) SHEET A100 DIAMOND 1& 2 BOTH INDICATE GLASS WALL
 PANELS WITH WALKING SURFACES WITHIN 3'-0" OF THE GLAZED
 PANELS BUT SHEET A600 DOES NOT INDICATE GLAZING TYPES
 LEFT BLANK. THIS LOCATION IS CONSIDERED A HAZARDOUS
 LOCATION. 2406.3 HAZARDOUS LOCATIONS. THE FOLLOWING
 SHALL BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS
 REQUIRING SAFETY GLAZING MATERIALS:
 7. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL,
 OTHER THAN IN THOSE LOCATIONS DESCRIBED IN PRECEDING
 ITEMS 5 AND 6, WHICH MEETS ALL OF THE FOLLOWING
 CONDITIONS:
  
 7.1. EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9
 SQUARE FEET (0.84 M2);
  
 7.2. EXPOSED BOTTOM EDGE LESS THAN 18 INCHES (457 MM)
 ABOVE THE FLOOR;
  
 7.3. EXPOSED TOP EDGE GREATER THAN 36 INCHES (914 MM)
 ABOVE THE FLOOR; AND
  
 7.4. ONE OR MORE WALKING SURFACE(S) WITHIN 36 INCHES
 (914 MM) HORIZONTALLY OF THE PLANE OF THE GLAZING.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-05-20 Cont ID  
Sent By btrobaug Date 2010-05-20 Time 15:36 Rev Time 0.00
Received By btrobaug Date 2010-05-20 Time 12:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-05-27 Cont ID  
Sent By mawillia Date 2010-05-27 Time 15:02 Rev Time 0.00
Received By mawillia Date 2010-05-27 Time 14:26 Sent To  
Notes
2010-05-27 15:02:29*****APPROVED*****
  
  
 PLAN SHEETS G100, A100, E100, E201, FP100, AND FP101
 WERE STAMPED, INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-08 Cont ID  
Sent By vmolina Date 2010-06-08 Time 08:15 Rev Time 0.00
Received By vmolina Date 2010-06-08 Time 08:14 Sent To  
Notes
2010-06-08 08:15:47GAVE TO LWAGNER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-08 Cont ID  
Sent By vmolina Date 2010-06-02 Time 08:14 Rev Time 0.00
Received By vmolina Date 2010-05-19 Time 10:55 Sent To  
Notes
2010-05-19 11:07:44SENT TO C-26.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-05-26 Cont ID  
Sent By rregueir Date 2010-05-26 Time 16:51 Rev Time 0.00
Received By rregueir Date 2010-05-26 Time 15:40 Sent To  
Notes
2010-05-26 16:51:41PRIMARY MECHANICAL SCOPE OF WORK IS THE KITCHEN HOOD
 VENTILATION SYSTEM. A MECHHOOD PERMIT TYPE IS REQUIRED
 FOR THIS SCOPE. A SEPARATE MECH PERMIT IS REQUIRED FOR
 THE MODIFICATIONS TO THE EXISTING HVAC SYSTEM. A
 SEPARATE HOODSUPP PERMIT WITH SEPARATE PLANS IS
 REQUIRED FOR THE HOOD FIRE SUPPRESSION SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-06-08 Cont ID  
Sent By lwagner Date 2010-06-08 Time 13:58 Rev Time 0.00
Received By lwagner Date 2010-06-08 Time 13:57 Sent To  
Notes
2010-06-08 13:59:02PLUMBING PERMIT REQUIRED
 GAS PERMIT REQUIRED WITH DRAWING AND ALL REQUIRED
 INFORMATION

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-05-25 Cont ID  
Sent By lwagner Date 2010-05-25 Time 13:10 Rev Time 0.00
Received By lwagner Date 2010-05-25 Time 11:28 Sent To  
Notes
2010-05-25 13:06:26FBC PLUMBING 2007
 REVIEW #1 DENIED
  
 1. FBC 106.3.5.1.3 - SANITARY AND WATER PIPE RISER
 DIAGRAMS REQUIRED.
  
 2. GAS PIPE CAN NOT BE APPROVED WITHOUT THE REQUIRED
 INFORMATION.
 THIS INFORMATION MAY BE SUBMITTED WITH THE GAS
 CONTRACTORS APPLICATION FOR PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2007 FUEL GAS.
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL).
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2007 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ???
 USE OF CAPACITY SECTION A.3.1(4)
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2007 FUEL GAS CODE SEC. 304
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2007
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2007 FUEL GAS CODE
 SEC. 502 THRU 505.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2007 FUEL GAS SEC. 402.2
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW
 CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO
 BE DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2010-06-02 Cont ID  
Sent By jroach Date 2010-06-02 Time 11:38 Rev Time 0.00
Received By jroach Date 2010-06-02 Time 11:38 Sent To  
Notes
***NONE***