Plan Review Details - Permit 10050340
Plan Review Stops For Permit 10050340
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-09-22 Cont ID  
Sent By jwitmer Date 2010-09-22 Time 12:31 Rev Time 0.55
Received By jwitmer Date 2010-09-22 Time 12:31 Sent To  
Notes
2010-09-22 12:32:45REVIEW & STAMP PLANS DATED 6/15/10

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-06-17 Cont ID  
Sent By jwitmer Date 2010-05-20 Time 08:11 Rev Time 0.50
Received By jwitmer Date 2010-05-20 Time 08:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-09-22 Cont ID  
Sent By jleahy Date 2010-09-22 Time 09:11 Rev Time 0.00
Received By jleahy Date 2010-09-22 Time 09:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-05-18 Cont ID  
Sent By btrobaug Date 2010-05-18 Time 16:01 Rev Time 0.00
Received By btrobaug Date 2010-05-18 Time 15:20 Sent To  
Notes
2010-05-18 16:02:52REDLINED 210.63 & 210.8(B) FOR RTU UNITS #3 &4./WRT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-07-02 Cont ID  
Sent By mcarsill Date 2010-07-02 Time 09:54 Rev Time 0.00
Received By mcarsill Date 2010-07-02 Time 09:50 Sent To  
Notes
2010-07-02 09:53:272100-45TH STREET
 UNITS A 2A & A3
 PERMIT NUMBER 10050340
 REVISED PLANS
  
 1. ADDRESS HAS BEEN PROVIDED IN THE TITLE BLOCK AS
 REQUESTED BY RETIRED CAPTAIN MIKE WILLIAMS.
  
 2. ALL NEW FIRE RATED WALLS ARE TO BE PROPERLY
 IDENTIFIED.
  
 3. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOORS.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-06-03 Cont ID  
Sent By mawillia Date 2010-06-03 Time 12:00 Rev Time 0.00
Received By mawillia Date 2010-06-03 Time 11:21 Sent To  
Notes
2010-06-03 12:00:11*****UNSAT*****
  
 THE APPROPITE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 FOLLOWINIG COMMENT HAS BEEN ADDRESSED:
  
 1. THE VERBAGE IN THE TITLE BLOCK OF THE PLAN SHEETS -
 AN INTERIOR RENOVATION TO: PARK PLAZA , SECTIONS "A &
 B" OF THE VILLAGE PROMENADE - IS UNCLEAR. THE ACTUAL
 PROJECT SITE ADDRESS, INCLUDING THE SUITE NUMBER(S),
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-22 Cont ID  
Sent By vmolina Date 2010-06-22 Time 08:38 Rev Time 0.00
Received By vmolina Date 2010-06-17 Time 08:38 Sent To  
Notes
2010-06-22 08:38:47IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-22 Cont ID  
Sent By vmolina Date 2010-06-03 Time 08:37 Rev Time 0.00
Received By vmolina Date 2010-05-18 Time 08:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-09-21 Cont ID  
Sent By rregueir Date 2010-09-21 Time 15:51 Rev Time 0.00
Received By rregueir Date 2010-09-21 Time 15:51 Sent To  
Notes
2010-09-21 15:51:54RE-STAMPED NEW COPIES OF PREVIOUSLY PASSED PLANS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-06-01 Cont ID  
Sent By rregueir Date 2010-06-01 Time 11:40 Rev Time 0.00
Received By rregueir Date 2010-06-01 Time 10:47 Sent To  
Notes
2010-06-01 11:40:28**PROVISO**
  
 PROVIDE PRODUCT APPROVALS FOR LOUVERS AND CONDENSER
 STAND PER FAC RULE 9B-72.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-05-19 Cont ID  
Sent By lwagner Date 2010-05-19 Time 11:40 Rev Time 0.00
Received By lwagner Date 2010-05-19 Time 11:09 Sent To  
Notes
2010-05-19 11:46:24****PROVISO*****
  
 1. AIR CHAMBERS ARE NO LONGER PART OF THE PLUMBING CODE
 THEREFORE NOT TO BE INSTALLED.
  
 2. CONDENSATE IS NOT TO BE CONNECTED TO SANITARY PER
 UTILITIES CITY ORDINANCE 90-125 (5)
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2010-09-21 Cont ID  
Sent By ajones Date 2010-09-21 Time 14:45 Rev Time 0.00
Received By ajones Date 2010-09-21 Time 14:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2010-06-28 Cont ID  
Sent By jroach Date 2010-06-28 Time 10:54 Rev Time 0.00
Received By lmartine Date 2010-06-23 Time 11:14 Sent To FIRE
Notes
2010-06-28 10:54:34ZONING PLAN REVIEW
  
 PERMIT NO.: 10050340
 ADDRESS: 2100 45TH STREET
 CONTRACTOR/CONTACT: GARY FOSTER
 TELEPHONE NO.: 954.467.9694
 SCOPE OF REVIEW: BUILDOUT
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) AS PART OF THE CONVERSION OF THIS SPACE FROM A
 DRIVE-THROUGH TO AN ENCLOSED RETAIL BAY, IT WAS
 REQUIRED THAT THE LANDSCAPING THROUGHOUT THE SITE BE
 UPGRADED TO COMPLY WITH THE CITY???S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS). THIS WORK WAS NEVER
 COMPLETED AND DID NOT PASS FINAL INSPECTION. NO PERMITS
 FOR THE BUILD-OUT OF THIS SPACE WILL BE ISSUED UNTIL
 THIS OUTSTANDING ISSUE HAS BEEN RESOLVED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-06-02 Cont ID  
Sent By jroach Date 2010-06-02 Time 13:22 Rev Time 0.00
Received By jroach Date 2010-06-02 Time 13:22 Sent To  
Notes
2010-06-02 13:22:51ZONING PLAN REVIEW
  
 PERMIT NO.: 10050340
 ADDRESS: 2100 45TH STREET
 CONTRACTOR/CONTACT: GARY FOSTER
 TELEPHONE NO.: 954.467.9694
 SCOPE OF REVIEW: BUILDOUT
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) AS PART OF THE CONVERSION OF THIS SPACE FROM A
 DRIVE-THROUGH TO AN ENCLOSED RETAIL BAY, IT WAS
 REQUIRED THAT THE LANDSCAPING THROUGHOUT THE SITE BE
 UPGRADED TO COMPLY WITH THE CITY???S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS). THIS WORK WAS NEVER
 COMPLETED AND DID NOT PASS FINAL INSPECTION. NO PERMITS
 FOR THE BUILD-OUT OF THIS SPACE WILL BE ISSUED UNTIL
 THIS OUTSTANDING ISSUE HAS BEEN RESOLVED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  