Plan Review Details - Permit 10050327
Plan Review Stops For Permit 10050327
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-06-03 Cont ID  
Sent By rmcdouga Date 2010-06-03 Time 16:39 Rev Time 0.00
Received By rmcdouga Date 2010-06-03 Time 16:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-05-18 Cont ID  
Sent By rmcdouga Date 2010-05-18 Time 16:58 Rev Time 0.00
Received By rmcdouga Date 2010-05-18 Time 16:58 Sent To  
Notes
2010-05-18 17:01:392007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE
 ACCORDION SHUTTERS AS REQUIRED BY FAC RULE 9B-72.
  
 2) SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE ACCORDION SHUTTERS. SPECIFY THE MOUNT,
 FASTENER TYPE AND SPACING, SPANS, ETC. FBC R301.1
  
 3) SUBMIT 2 COPIES OF A FLOOR PLAN INDICATING THE
 LOCATION, TYPE AND SIZE OF THE WINDOWS AND DOORS THAT
 WILL BE REPLACED. FBC 301.1
  
 4) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 EXTERIOR DOOR IS EXPIRED. SUBMIT CURRENT PRODUCT
 APPROVALS. RULE 9B-72
  
 5) PRODUCT APPROVALS WERE SUBMITTED FOR WINDOW
 MULLIONS. PLEASE SPECIFY THE WHICH WINDOWS WILL BE
 MULLED TOGETHER. SPECIFY THE SIZES AND CONFIGURATION.
 FBC R301.1
  
 6) PRODUCT APPROVALS WERE SUBMITTED FOR IMPACT RATED
 WINDOWS, HOWEVER, THE SCOPE OF WORK SPECIFIES WINDOWS
 WITH ACCORDION SHUTTERS. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-05-14 Cont ID  
Sent By btrobaug Date 2010-05-14 Time 08:20 Rev Time 0.00
Received By btrobaug Date 2010-05-14 Time 07:51 Sent To  
Notes
2010-05-14 08:19:02 
 PROVISO/REVISION REQUIRED
  
 R313.2.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A PERMIT
 OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR
 CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING
 UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS
 REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS SHALL BE
 INTERCONNECTED AND HARD WIRED.
  
 SUBMIT A FLOOR PLAN AND INDICATING THE LOCATION OF ALL
 EQUIPMENT AND DEVICES BEING INSTALLED UNDER THE SCOPE
 OF THIS APPLICATION.106.1.1 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-03 Cont ID  
Sent By lmartine Date 2010-06-03 Time 10:41 Rev Time 0.00
Received By lmartine Date 2010-06-03 Time 10:41 Sent To  
Notes
2010-06-03 10:41:55GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-03 Cont ID  
Sent By lfranco Date 2010-06-02 Time 19:17 Rev Time 0.00
Received By lmartine Date 2010-05-12 Time 09:00 Sent To  
Notes
2010-05-13 09:00:54R10

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-05-19 Cont ID  
Sent By rmcdouga Date 2010-05-19 Time 07:03 Rev Time 0.00
Received By rmcdouga Date 2010-05-19 Time 07:03 Sent To  
Notes
2010-05-19 07:08:50FIXTURE CHANGE OUT IN SAME LOCATION.

Review Stop Z ZONING
Rev No 1 Status N Date 2010-06-02 Cont ID  
Sent By lfranco Date 2010-06-02 Time 19:14 Rev Time 0.00
Received By lfranco Date 2010-06-02 Time 19:14 Sent To I
Notes
2010-06-02 19:17:22PLANNING AND ZONING:
 *ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT,
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved