Plan Review Details - Permit 10050326
Plan Review Stops For Permit 10050326
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-06-03 Cont ID  
Sent By rmcdouga Date 2010-06-03 Time 07:50 Rev Time 0.00
Received By rmcdouga Date 2010-06-03 Time 07:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-05-18 Cont ID  
Sent By rmcdouga Date 2010-05-18 Time 13:44 Rev Time 0.00
Received By rmcdouga Date 2010-05-18 Time 13:43 Sent To  
Notes
2010-05-18 14:48:442007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE
 ACCORDION SHUTTERS AS REQUIRED BY FAC RULE 9B-72.
  
 2) SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE ACCORDION SHUTTERS. SPECIFY THE MOUNT,
 FASTENER TYPE AND SPACING, SPANS, ETC. FBC R301.1
  
 3) SUBMIT 2 COPIES OF A FLOOR PLAN INDICATING THE
 LOCATION, TYPE AND SIZE OF THE WINDOWS AND DOORS THAT
 WILL BE REPLACED. FBC 301.1
  
 4) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 EXTERIOR DOOR IS EXPIRED. SUBMIT CURRENT PRODUCT
 APPROVALS. RULE 9B-72
  
 5) PRODUCT APPROVALS WERE SUBMITTED FOR WINDOW
 MULLIONS. PLEASE SPECIFY THE WHICH WINDOWS WILL BE
 MULLED TOGETHER. SPECIFY THE SIZES AND CONFIGURATION.
 FBC R301.1
  
 6) ITEM # 8 UNDER EXTERIOR ON THE SCOPE OF WORK
 INDICATES THAT THE 2ND BATHROOM WINDOW IS TO BE
 REPLACED AND ACCORDION SHUTTER INSTALLED. THE WINDOW
 PRODUCT APPROVAL THAT WAS SUBMITTED IS FOR IMPACT
 WINDOWS. PLEASE CLARIFY.
  
 7) ITEM #16 UNDER MASTER BEDROOM AND ITEM #20 UNDER
 BATHROOM SPECIFIES REPLACING WINDOWS WITHOUT ANY
 MENTION OF IMPACT PROTECTION. ARE THESE GOING TO BE
 IMPACT WINDOWS? IF THEY ARE NOT LISTED UNDER EXTERIOR
 DOES THIS MEAN THEY ARE INTERIOR? PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-05-14 Cont ID  
Sent By btrobaug Date 2010-05-14 Time 07:50 Rev Time 0.00
Received By btrobaug Date 2010-05-14 Time 07:30 Sent To  
Notes
2010-05-14 08:21:51 
 PROVISO/REVISION REQUIRED
  
 R313.2.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A PERMIT
 OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR
 CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING
 UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS
 REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS SHALL BE
 INTERCONNECTED AND HARD WIRED.
  
 SUBMIT A FLOOR PLAN AND INDICATING THE LOCATION OF ALL
 EQUIPMENT AND DEVICES BEING INSTALLED UNDER THE SCOPE
 OF THIS APPLICATION.106.1.1 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-02 Cont ID  
Sent By vmolina Date 2010-06-02 Time 12:50 Rev Time 0.00
Received By vmolina Date 2010-06-02 Time 12:50 Sent To  
Notes
2010-06-02 12:50:23GAVE TO RM

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-20 Cont ID  
Sent By lmartine Date 2010-05-20 Time 08:58 Rev Time 0.00
Received By lmartine Date 2010-05-12 Time 08:57 Sent To  
Notes
2010-05-13 09:00:11R9

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-05-18 Cont ID  
Sent By rmcdouga Date 2010-05-18 Time 13:44 Rev Time 0.00
Received By rmcdouga Date 2010-05-18 Time 13:44 Sent To  
Notes
2010-05-18 13:45:41REPLACE FIXTURES IN SAME LOCATION.

Review Stop Z ZONING
Rev No 1 Status N Date 2010-05-20 Cont ID  
Sent By kdfreema Date 2010-05-20 Time 08:50 Rev Time 0.00
Received By kdfreema Date 2010-05-20 Time 08:50 Sent To  
Notes
2010-05-20 08:51:00PERMIT VALUE DOES NOT EXCEED 50% OF PAPA IMPROVEMENT
 VALUE.