Plan Review Details - Permit 10050317
Plan Review Stops For Permit 10050317
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-05-19 Cont ID  
Sent By shill Date 2010-05-19 Time 18:56 Rev Time 0.00
Received By shill Date 2010-05-19 Time 18:56 Sent To  
Notes
2010-05-19 19:05:00****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE PROVIDE TWO COMPLETE SETS OF THE INSTALLATION
 SCHEDULE.
  
 2. SEE INSTALLATION SCHEDULE. 1.5" EDGE DISTANCE
 REQUIRES A .35 FACTOR, SEE PAGE 11. PLEASE REVISE
 ANCHOR SPACING.
  
 3. ON THE INSTALLATION SCHEDULE, THE COLUMN SHUTTER
 MOUNTING CONNECTION TYPE SHOULD SPECIFY WHICH
 CONNECTION TYPE IS PROPOSED. THIS APPEARS TO BE FLOOR
 MOUNTING 7, WALL MOUNTING 1, AND WALL MOUNTING 3 (BASED
 ON HIGHLIGHTED PRODUCT APPROVAL). PLEASE INCORPORATE
 THIS INFORMATION INTO THE INSTALLATION SCHEDULE, WHICH
 IS OPENING SPECIFIC.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-13 Cont ID  
Sent By rmcdouga Date 2010-05-13 Time 08:12 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2010-05-13 08:12:25TO MISC 1