Plan Review Details - Permit 10050262
Plan Review Stops For Permit 10050262
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-06-02 Cont ID  
Sent By wjolin Date 2010-06-02 Time 10:33 Rev Time 0.00
Received By wjolin Date 2010-06-02 Time 10:15 Sent To  
Notes
2010-06-02 10:18:29*****REVISION APPROVED*****
  
 AFTER DISCUSSIONS WITH THE BUILDING ENGINEER, SPRINKLER
 CONTRACTOR AND ARCHITECT, THE REVISED SPRINKLER DRAWING
 HAS BEEN ACCEPTED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-05-14 Cont ID  
Sent By mawillia Date 2010-05-14 Time 13:56 Rev Time 0.00
Received By mawillia Date 2010-05-14 Time 13:38 Sent To  
Notes
2010-05-14 13:53:11*****REVISION DENIED*****
  
  
  
 1) ORIGINAL HYDRAULIC CALCULATIONS SUBMITTED WERE FOR
 ORDINARY HAZARD GROUP II. NEW HYDRAULIC CALCULATIONS
 SUBMITTED WERE FOR LIGHT HAZARD. PLEASE EXPLAIN.
  
 2) STANDARD SPRAY SPRINKLERS SPACED 6 FEET APART TO WET
 SURFACE OF GLASS STOREFRONT CURTAINWALL (SUBSTITUTION
 FOR 1-HR RATED BARRIER) IS NOT PERMITTED. THIS
 EQUIVALENCY
 APPLIES TO ATRIUM SEPARATIONS. CONSIDER USE OF SPECIFIC
 APPLICATION WINDOW SPRINKLERS FOR EACH SECTION OF
 GLAZING. WINDOW SPRINKLER DEMAND WOULD NEED
 TO BE ADDED TO THE HYDRAULIC CALCULATIONS.
  
 3) GLASS DOOR CANNOT BE PROTECTED WITH SPRINKLERS. FIRE
 RATED DOORS ARE REQUIRED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-14 Cont ID  
Sent By mawillia Date 2010-05-14 Time 13:39 Rev Time 0.00
Received By mawillia Date 2010-05-11 Time 13:38 Sent To  
Notes
***NONE***