Plan Review Details - Permit 10050235
Plan Review Stops For Permit 10050235
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-07-06 Cont ID  
Sent By jgomez Date 2010-07-06 Time 11:06 Rev Time 0.00
Received By jgomez Date 2010-07-06 Time 11:54 Sent To  
Notes
2010-07-06 11:46:42BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 4- SHEET S2-1: ROOF SHEATHING TO BE MIN. 4" O.C. IN
 CORNER AREAS AND NAILS NEED TO BE MIN. 8D RING SHANK
 NAILS AS REQUIRED BY SEC. R803.2.3.1. REVISE
 SPECIFICATIONS FOR ROOF SHEATHING AS REQUIRED. OR
 PROVIDE ENGINEERING CALCULATIONS SHOWING THAT SPECIFIED
 FASTENING WILL MEET OR EXCEED REQUIREMENTS OF SEC.
 R803.2.3.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-01 Cont ID  
Sent By jgomez Date 2010-06-01 Time 14:30 Rev Time 0.00
Received By jgomez Date 2010-06-01 Time 14:30 Sent To PC
Notes
2010-06-01 14:56:46RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 AND BASE SHEET FASTENING OPTION IS GOING TO BE USED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.
 ***NOTE: CHECK GENERAL LIMITATION #7 ON LAST PAGE OF
 PRODUCT APPROVAL. IF PERIMETER AND CORNER AREAS NAIL
 ENHANCING RAS 117 CALCULATIONS NEED TO BE SIGNED AND
 SEALED, THEN THOSE CALCULATIONS NEED TO BE SIGNED AND
 SEALED. IF CALCULATIONS ARE NOT REQUIRED TO BE SIGNED
 AND SEALED, THEN, ROOFING CONTRACTOR MAY PROVIDE THE
 RAS 117 CALCULATIONS.
 APPROVED ROOF SYSTEMS THAT ARE LIMITED BY GENERAL
 LIMITATION #9 CAN'T BE USED IN THIS AREA BECAUSE THEY
 DON'T MEET THE DESIGN PRESSURES OF SEC. R301 AND NAIL
 ENHANCING CALCULATIONS ARE NOT ALLOWED.
  
 B) WINDOW ON LOGGIA AS SHOWN ON FLOOR PLAN ON SHEET
 A2-1. ( IF THIS IS NOT A WINDOW, THEN CLARIFY PROPOSED
 FLOOR PLAN DRAWING SHOWING WHAT IT IS.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 D) ROOF RAFTER CONNECTORS SPECIFIED ON PLANS/SECTIONS.
  
 3- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 4- SHEET S2-1:
 A) ROOF FRAMING PLAN DOESN'T SPECIFY ROOF RAFTERS SIZE
 AND SPACING. PROVIDE REQUIRED INFORMATION. TO VERIFY
 COMPLIANCE WITH THE DESIGN LOADS OF SEC. R301.
  
 B) ROOF SHEATHING TO BE MIN. 4" O.C. AND NAILS NEED TO
 BE MIN. 8D RING SHANK NAILS AS REQUIRED BY SEC.
 R803.2.3.1. REVISE SPECIFICATIONS FOR ROOF SHEATHING AS
 REQUIRED.
  
 5- OWES $18.56 FOR RADON FEES AND FOR ADDITIONAL
 LANDSCAPE REVIEW ($15.00).
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-07-21 Cont ID  
Sent By btrobaug Date 2010-07-21 Time 06:42 Rev Time 0.00
Received By btrobaug Date 2010-07-21 Time 06:32 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-05-13 Cont ID  
Sent By btrobaug Date 2010-05-13 Time 14:19 Rev Time 0.00
Received By btrobaug Date 2010-05-13 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-29 Cont ID  
Sent By vmolina Date 2010-06-29 Time 09:43 Rev Time 0.00
Received By vmolina Date 2010-06-29 Time 09:43 Sent To  
Notes
2010-06-29 09:45:36R-8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-01 Cont ID  
Sent By jgomez Date 2010-06-01 Time 14:19 Rev Time 0.00
Received By jgomez Date 2010-05-12 Time 11:56 Sent To  
Notes
2010-05-12 13:04:31SENT TO R-6.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-06-01 Cont ID  
Sent By jgomez Date 2010-06-01 Time 14:15 Rev Time 0.00
Received By jgomez Date 2010-06-01 Time 14:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-07-06 Cont ID  
Sent By jgomez Date 2010-06-01 Time 14:15 Rev Time 0.00
Received By jgomez Date 2010-06-01 Time 14:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-07-06 Cont ID  
Sent By jgomez Date 2010-07-06 Time 12:52 Rev Time 0.00
Received By jgomez Date 2010-07-06 Time 11:54 Sent To  
Notes
2010-07-06 13:00:14PLUMBING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE PLUMBING RISER DIAGRAM. WATER HEATER CAN'T BE
 DIRECTLY CONNECTED TO THE DRAINAGE SYSTEM.

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-06-01 Cont ID  
Sent By jgomez Date 2010-06-01 Time 14:14 Rev Time 0.00
Received By jgomez Date 2010-06-01 Time 14:14 Sent To  
Notes
2010-06-01 14:29:56RESIDENTIAL (R3) ADDITION, PLUMBING PLAN REVIEW.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE PLUMBING RISER DIAGRAM AS REQUIRED BY SEC.
 106.3.5.4(9) OF CITY AMENDMENTS TO FBC.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 2 Status P Date 2010-07-19 Cont ID  
Sent By eschneid Date 2010-07-19 Time 15:15 Rev Time 1.00
Received By eschneid Date 2010-07-19 Time 15:15 Sent To  
Notes
2010-07-19 16:02:31PASSED W/PROVISO
  
 1) THIS PERMIT ESTABLISHES THE WEST PROPERTY LINE AS
 THE FIVE (5) FOOT SIDE FOR SETBACK PURPOSES. ANY NEW
 CONSTRUCTION ON THE EAST PROPERTY LINE SHALL ADHERE TO
 A TEN (10) FOOT SIDE SETBACK.
  
 2) INSTALL ONE (1) PALM TREE ON SITE TO REPLACE DEAD
 PALM. NEW PALM SHALL HAVE A MINIMUM OF EIGHT (8) FEET
 OVERALL HEIGHT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-05-24 Cont ID  
Sent By eschneid Date 2010-05-24 Time 10:38 Rev Time 0.50
Received By eschneid Date 2010-05-24 Time 10:38 Sent To  
Notes
2010-05-24 11:01:14FAILED
  
 1) A SURVEY, LESS THAN ONE YEAR OLD, IS REQUIRED. THE
 SURVEY SHALL INCLUDE ALL EXISTING STRUCTURES AND THEIR
 SETBACK DIMENSION TO THE PROPERTY EAST, NORTH AND WEST
 PROPERTY LINES.
  
 2) PLEASE NOTE THAT THE PROPERTY IS LOCATED WITHIN THE
 SF14 ZONING DISTRICT. THIS ZONING DISTRICT REQUIRES A
 TOTAL SIDE SETBACK OF A MINIMUM OF 15 FEET. THE
 SUBMITTED PLANS SEEM TO SHOW LESS THAN THE 15 FOOT
 REQUIRED.
  
 3) IT APPEARS FROM THE 2009 AERIAL THAT THERE WILL BE
 LANDSCAPE REMOVED AS PART OF THE ADDITION. WHAT
 LANDSCAPE MATERIAL IS BEING AFFECTED BY THE ADDITION?
  
 4) PLEASE NOTE THAT THE CITY HAS MINIMUM TREE AND SHRUB
 REQUIREMENTS FOR SINGLE FAMILY LOTS AS LISTED IN
 SECTION 94-442(2)A. THIS MAY REQUIRE THE REPLACEMENT OF
 ANY REMOVED LANDSCAPE. A TREE ALTERATION PERMIT IS
 REQUIRED PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREE
 OR PALM.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  