Plan Review Details - Permit 10050223
Plan Review Stops For Permit 10050223
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-09-23 Cont ID  
Sent By jwitmer Date 2011-09-23 Time 07:51 Rev Time 0.55
Received By jwitmer Date 2011-09-23 Time 07:51 Sent To  
Notes
2011-09-23 08:00:28BUILDING PLAN REVIEW
 PERMIT: 10050223
 ADD: 104 S CLEMATIS ST
 CONT: ATLANTIC GENERAL CONTRACTING
 TEL: (561)723-2401
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW REVIEW
 ACTION: DENIED
 COMMENTS FROM 2ND REVIEW:
 1) THIS PERMIT IS OWNED BY ATLANTIC GENERAL CONTRACTING
 NOT SPEEDY ROOTER, INC. SPEEDY ROOTER INC HAS A U (PBC
 LICENSE FOR SEPTIC TANKS) SCOPE OF WORK IS OUTSIDE OF
 YOUR LICESSURE.
  
 2) PERMIT APPLICATION IS EXPIRED OVER 6 MONTHS. IT WILL
 BE CONSIDERED A REISSUE IF THE OWNER OF THE PERMIT
 WISHES TO RE-APPLY IT WILL BE CONSIDERED A NEW PERMIT.
 THERE ARE NO VESTED RIGHTS AFTER A PERMIT EXPIRES AND
 IS ONLY A PERMIT APPLICATION.
  
 NO FURTHER REVIEW OF PRODUCT APPROVAL SUBMITTED WILL BE
 COMPLETED UNDER A EXPIRED PERMIT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
 COMMENTS FROM 1ST REVIEW:
 1) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 2) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 2A) WINDOWS
 2B) DOOR
 2C) TRANSOM
 2D) MULLION
 2E) STORM PANELS IF GLAZED OPENINGS DO NOT HAVE LARGE
 MISSILE TESTING.
  
 3) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) THE PRESSURES NEGATIVE APPEAR TO BE A LITTLE LOW FOR
 THE DOOR AND TRANSOM WITH THE COASTAL EXPOSURE FACTOR
 OF 1.21 ASCE 7-05 FIGURE 6-2.
  
 5) THE PLANS DO NOT PROVIDE THTE HEIGTH DIFFERENCE
 BETWEEN THE INTERIOR FLOOR FINISH AND EXTERIOR DECK
 HEIGTH, 11-4-3.8 CHANGES IN LEVEL.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-05-19 Cont ID  
Sent By jwitmer Date 2010-05-19 Time 11:12 Rev Time 0.77
Received By jwitmer Date 2010-05-19 Time 11:12 Sent To  
Notes
2010-05-19 11:25:41BUILDING PLAN REVIEW
 PERMIT: 10050223
 ADD: 104 S CLEMATIS ST
 CONT: ATLANTIC GENERAL CONTRACTING
 TEL: (561)723-2401
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 2) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 2A) WINDOWS
 2B) DOOR
 2C) TRANSOM
 2D) MULLION
 2E) STORM PANELS IF GLAZED OPENINGS DO NOT HAVE LARGE
 MISSILE TESTING.
  
 3) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) THE PRESSURES NEGATIVE APPEAR TO BE A LITTLE LOW FOR
 THE DOOR AND TRANSOM WITH THE COASTAL EXPOSURE FACTOR
 OF 1.21 ASCE 7-05 FIGURE 6-2.
  
 5) THE PLANS DO NOT PROVIDE THTE HEIGTH DIFFERENCE
 BETWEEN THE INTERIOR FLOOR FINISH AND EXTERIOR DECK
 HEIGTH, 11-4-3.8 CHANGES IN LEVEL.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-05-25 Cont ID  
Sent By mawillia Date 2010-05-25 Time 11:32 Rev Time 0.00
Received By mawillia Date 2010-05-25 Time 11:05 Sent To  
Notes
2010-05-25 11:32:20******UNSAT*****
  
 1. PLEASE INDICATE THE USE OF THE DOOR AS EITHER A
 MEANS OF EGRESS (MARKED EXIT) OR AS AN CONVENIENCE.
  
 2. FIRE DOORS, IF APPLICABLE, SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA 80 - 1999 EDITION.
  
 3. ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PREOVIDED WITH PANIC HARDWARE OF FIRE EXIT HARDWARE.
 SEE REFERENCE 13.2.2.2.3 OF NFPA 101, LIFE SAFETY CODE,
 FLORIDA 2007 EDITION.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2011-09-23 Cont ID  
Sent By jwitmer Date 2011-09-23 Time 08:00 Rev Time 0.00
Received By jwitmer Date 2011-09-22 Time 07:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-23 Cont ID  
Sent By jwitmer Date 2011-07-14 Time 07:46 Rev Time 0.00
Received By jwitmer Date 2010-05-13 Time 08:07 Sent To  
Notes
2010-05-13 08:10:01C5

Review Stop Z ZONING
Rev No 1 Status P Date 2010-07-14 Cont ID  
Sent By astelly Date 2010-07-14 Time 09:15 Rev Time 0.00
Received By astelly Date 2010-07-14 Time 09:15 Sent To  
Notes
***NONE***