Plan Review Details - Permit 10040776
Plan Review Stops For Permit 10040776
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-06-16 Cont ID  
Sent By rmcdouga Date 2010-06-16 Time 11:05 Rev Time 0.00
Received By rmcdouga Date 2010-06-16 Time 11:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-05-25 Cont ID  
Sent By rmcdouga Date 2010-05-25 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2010-05-25 Time 11:20 Sent To  
Notes
2010-05-20 12:05:492007 FBC W/2009 REVISIONS
  
 1) SHEET 1 OF THE CARPORT ENCLOSURE SPECIFIES THAT IT
 IS EXPOSURE CATEGORY B. BECAUSE THE STRUCTURE IS
 LOCATED WITHIN 1500 FT OF THE INTRACOASTAL WATERWAY, IT
 IS EXPOSURE CATEGORY C. PLEASE CORRECT.
  
 2) FBC R704.1 REQUIRES CLEARANCE BETWEEN WALL COVERINGS
 AND FINAL EARTH GRADE TO BE A MINIMUM OF 6" FOR TERMITE
 INSPECTION. ALSO SEE R404.1.6 HEIGHT ABOVE FINISH
 GRADE.
  
 3) ASTM C 1063 REQUIRES FOUNDATION WEEP SCREEDS AT THE
 BOTTOM OF FRAMED EXTERIOR WALLS.
  
 4) SHOW COMPLIANCE WITH FBC R 303.3 FOR BATHROOM
 VENTILATION AFTER THE WINDOW IS ENCLOSED.
  
 5) FBC R 309.1 DOES NOT PERMIT OPENINGS FROM THE GARAGE
 TO SLEEPING ROOMS. SHOW COMPLIANCE.
  
 6) FBC R 309.2 REQUIRES THE GARAGE TO BE SEPARATED FROM
 THE RESIDENCE AND ITS ATTIC AREA BY NOT LESS THAN 1/2"
 GYPSUM BOARD APPLIED TO THE GARAGE SIDE. SHOW
 COMPLIANCE.
  
 7) THE DOOR FROM THE GARAGE TO THE RESIDENCE IS
 REQUIRED TO COMPLY WITH FBC R 309.2. SPECIFY DOOR TYPE
 ON PLANS.
  
 8) SPECIFY THE REQUIRED OPENING PRESSURES FOR THE
 EXTERIOR DOORS ON THE PLANS. FBC R 301.2.1
  
 9) THE PRODUCT APPROVAL SUBMITTED FOR THE SECTIONAL
 GARAGE DOOR, NOA 09-0128.01 IS MISSING PARTS OF THE
 DRAWINGS. IT APPEARS THAT THE DRAWING DID NOT FIT THE
 PAGE WHEN IT WAS DOWNLOADED. PLEASE CORRECT.
  
 10) SHOW COMPLIANCE WITH FBC R 313.2.1 FOR SMOKE ALARMS
 AND R 313.4 FOR CARBON MONOXIDE PROTECTION.
  
 11) PROVIDE DOOR BUCK DETAILS FOR THE OVERHEAD GARAGE
 DOOR ON THE PLANS. SEE SHEET 4 OF DRAWING 98-05 FOR NOA
 09-0128.01 AND FBC R 613.6.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-06-09 Cont ID  
Sent By btrobaug Date 2010-06-09 Time 16:25 Rev Time 0.00
Received By btrobaug Date 2010-06-09 Time 16:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-05-07 Cont ID  
Sent By btrobaug Date 2010-05-07 Time 12:41 Rev Time 0.00
Received By btrobaug Date 2010-05-07 Time 12:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-08 Cont ID  
Sent By vmolina Date 2010-06-08 Time 12:14 Rev Time 0.00
Received By vmolina Date 2010-06-08 Time 12:14 Sent To  
Notes
2010-06-08 12:17:50R-3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-25 Cont ID  
Sent By rmcdouga Date 2010-05-25 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2010-05-03 Time 17:26 Sent To  
Notes
2010-05-03 17:26:27R--2

Review Stop Z ZONING
Rev No 2 Status P Date 2010-06-25 Cont ID  
Sent By eschneid Date 2010-06-25 Time 16:47 Rev Time 0.25
Received By eschneid Date 2010-06-25 Time 16:47 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-05-19 Cont ID  
Sent By eschneid Date 2010-05-19 Time 11:02 Rev Time 0.50
Received By eschneid Date 2010-05-19 Time 11:02 Sent To  
Notes
2010-05-19 11:13:51FAILED
  
 1) PROVIDE THE DIMENSION FROM THE TRELLIS POSTS TO THE
 EAST AND NORTH PROPERTY LINES. CONTRACTOR MAY HAND DRAW
 DIMENSIONS ON THE SURVEY. PLEASE NOTE THAT THE TRELLIS
 OVERHANGS MAY NOT PROJECT MORE THAN THREE (3) FEET INTO
 A REQUIRED SETBACK - FIVE (5) FOOT NORTH SETBACK,
 TWENTY-FIVE (25) FOOT EAST SETBACK REQUIRED. IT APPEARS
 THAT THESE ARE MET, BUT THEY NEED TO BE SHOWN.
  
 2) AERIAL INDICATES THERE IS A STRUCTURE ADJACENT
 (NORTH) OF PROPOSED TRELLIS. PROVIDE PHOTOS TO SHOW
 THIS AREA. IF THERE ARE STRUCTURES NOT SHOWN ON THE
 SURVEY, THEN AN UPDATED SURVEY IS REQUIRED.
  
 3) PROVIDE THE PAVER WALK DIMENSIONS ON THE SURVEY.
  
 4) PROVIDE HOW THE PAVERS WILL BE INSTALLED.
  
 5) ZONING HAS NO ISSUES WITH THE CARPORT CONVERSION TO
 A GARAGE. NOTE THE NORTH ARROW ON SHEET A-2 FACES WRONG
 DIRECTION. RED-LINED BY STAFF.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  