Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-06-09 Cont ID  
Sent By shill Date 2010-06-09 Time 14:22 Rev Time 0.00
Received By shill Date 2010-06-09 Time 14:22 Sent To  
Notes
2010-06-09 14:22:34PROVISO - SEPARATE PERMIT FOR ROOF (W/ENHANCED
 FASTENING CALCS)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-06-07 Cont ID  
Sent By shill Date 2010-06-07 Time 10:38 Rev Time 0.00
Received By shill Date 2010-06-07 Time 10:38 Sent To  
Notes
2010-06-07 10:43:11****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 (NEW NOA AND CALCULATIONS SUBMITTED)
  
 1. PLEASE SEE THE RAS117 CALCULATIONS, SHEET 1. ZONE 2
 STATES THAT SPACING WILL BE:
  
 9.3"O.C. FOR ROWS 12" APART (3 ROWS)
  
 PLEASE EXPLAIN; FOUR ROWS TOTAL (3 FIELD ROWS, 1 LAP
 ROW) PLUS A 4" LAP WOULD EQUAL A 52" SHEET, BUT THE
 BASE SHEET WIDTH IS 39.37".
  
 2. CALCULATIONS STATE THAT THE SF/FASTENER IS 1.02';
 PLEASE EXPLAIN HOW THIS NUMBER HAS BEEN DERIVED AS I
 BELIEVE THIS SHOULD BE .88'.
  
 3. FASTENING PATTERN IS NOT CLEAR. THE APPROVED
 ASSEMBLY INCLUDES A 9" LAP ROW, TWO 12" FIELD ROWS. FOR
 ZONES 2 AND 3, LAP ROW WAS NOT SPECIFIED. IS IT THE
 INTENT TO HAVE THE LAP ROWS AT 9" OR 12"? WITHOUT THIS
 INFORMATION, COMPLIANCE WITH RAS117 CANNOT BE
 DETERMINED.
  
 4. SEE RAS117, SPACING IS TO BE ROUNDED DOWN TO THE
 NEAREST INCH.
  
 PLEASE CONTACT ME TO DISCUSS A PROVISO FOR THIS PERMIT.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-05-11 Cont ID  
Sent By shill Date 2010-05-11 Time 18:13 Rev Time 0.00
Received By shill Date 2010-05-11 Time 18:13 Sent To  
Notes
2010-05-11 18:18:16****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLANS PREPARED BY AN ARCHITECT AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS481.
  
 2. PLEASE CLARIFY THE ROOF DETAIL, SHOWS DRIP EDGE AT
 EDGE OF RAFTER, 1X CUT INTO THE RAFTER END, PLEASE SHOW
 HOW THE DESIGN WILL DIRECT WATER AWAY FROM STRUCTURAL
 MEMBERS. THIS COMMENT CAN BE ADDRESSED BY GRAPHICALLY
 DEPICTING THE 1X AT THE OUTSIDE OF THE RAFTER (HOLDING
 DRIP EDGE AWAY FROM RAFTER).
  
 3. CBS HOUSE WALL SHOWN WITH DASHED LINES. HOW DOES
 THIS RELATE TO THE PROPOSED IMPROVEMENT?
  
 4. THE ROOF ASSEMBLY SELECTED REFERS TO GENERAL
 LIMITATION #9, NO ENHANCED FASTENING PERMITTED, SEE
 NOA. PLEASE SELECT AN APPROVED ASSEMBLY WHICH REFERS TO
 GENERAL LIMITATION #7 AND SPECIFY ENHANCED FASTENING
 FOR THAT ASSEMBLY.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-05-20 Cont ID  
Sent By jgomez Date 2010-05-20 Time 15:46 Rev Time 0.00
Received By jgomez Date 2010-05-20 Time 15:46 Sent To B
Notes
2010-05-20 15:46:27SENT TO S. HILL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-11 Cont ID  
Sent By shill Date 2010-05-11 Time 18:18 Rev Time 0.00
Received By shill Date 2010-05-10 Time 10:05 Sent To  
Notes
2010-05-10 10:05:515/10 RETURNED FROM ZONING, SENT TO MISC 2
  
  
2010-05-04 11:05:12SENT TO ZONING BOX.

Review Stop Z ZONING
Rev No 1 Status N Date 2010-05-07 Cont ID  
Sent By astelly Date 2010-05-07 Time 11:00 Rev Time 0.00
Received By astelly Date 2010-05-07 Time 11:00 Sent To E
Notes
***NONE***