Plan Review Details - Permit 10040747
Plan Review Stops For Permit 10040747
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-05-14 Cont ID  
Sent By mawillia Date 2010-05-14 Time 13:32 Rev Time 0.00
Received By mawillia Date 2010-05-14 Time 13:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-05-07 Cont ID  
Sent By mawillia Date 2010-05-07 Time 12:44 Rev Time 0.00
Received By mawillia Date 2010-05-06 Time 15:40 Sent To  
Notes
2010-05-06 23:12:52*****DENIED*****
  
  
 1. THE TYPE OF FIRE INSPECTIONS NEEDED FOR THE SCOPE OF
 WORK (603 - SPRINKLER/STANDPIPE ROUGH, 311 - PRESSURE
 TEST, 302 - SPRINKLER/STANDPIPE FINAL) CAN NOT BE
 CONDUCTED UNDER THE APPLIED PLUMBING PERMIT. (FOR
 REFERENCE SEE CLOSED PERMIT # 08090748)
  
 2. THE PURPOSE OF THE PERMIT AS DESCRIBED (IN OUR
 SYSTEM) "INSTALL FIRE ALSRM FOR DOCK A & B IN SOUTH
 BASIN" DOES NOT CORRESPOND WITH THE SCOPE OF WORK
 DESCRIBED ON THE PERMIT APPLICATION.
  
 3. ADDRESS DISCREPANCY: PLEASE BE ADVISED THAT THE
 ADDRESS IN THE TITLE BLOCK OF EACH PLAN SHEET (4210
 NORTH FLAGLER DRIVE) DOES NOT CORRESPOND WITH THE
 ADDRESS ON THE PERMIT APPLICATION.
  
 4. PLAN DOES NOT SHOW THE LOCATION OF THE FIRE
 DEPARTMENT CONNECTION (FDC) TO SUPPLY/SUPPORT WATER TO
 THE SYSTEM FOR FIREFIGHTING OPERATIONS.
  
 5. KNOX LOCKING CAPS REQUIRED FOR THE FDC(S). DEVICE
 MAY BE OBTAINED AT WWW.KNOX.COM FOR YOUR ORDER.
  
 6. PLAN DOES NOT INDICATE LOCATION OF THE NEAREST FIRE
 HYDRANT(S).
  
 7. PLEASE EXPLAIN THE REDUCTION OF THE FIRE MAIN, FROM
 4" HDPE TO 3" HDPE, LOCATED AT THE EAST END OF DOCK A
 AS SHOWN ON SHEET P1 DRAWING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-05-13 Cont ID  
Sent By rmcdouga Date 2010-05-13 Time 08:17 Rev Time 0.00
Received By rmcdouga Date 2010-05-13 Time 08:17 Sent To  
Notes
2010-05-13 08:17:58TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-05-07 Time 11:44 Rev Time 0.00
Received By lmartine Date 2010-05-03 Time 17:32 Sent To  
Notes
2010-05-03 17:34:06IN FIRE BOX