Plan Review Details - Permit 10040714
Plan Review Stops For Permit 10040714
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-06-14 Cont ID  
Sent By jwitmer Date 2010-06-14 Time 15:25 Rev Time 0.55
Received By jwitmer Date 2010-06-14 Time 15:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-05-05 Cont ID  
Sent By jwitmer Date 2010-05-05 Time 11:02 Rev Time 0.77
Received By jwitmer Date 2010-05-05 Time 11:02 Sent To  
Notes
2010-05-05 11:14:26BUILDING PLAN REVIEW
 PERMIT: 10040714
 ADD: 2112 N JOG RD
 CONT: TEKTONICA IND. INC.
 TEL: (561)662-8352
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE INDICATE TYPE OF BUILDING TYPE EITHER A TYPE
 5A OR 5B. FBC-B TABLE 503.
  
 2) TENANT #3 PLEASE INDICATE WHAT TYPE OF ASSEMBLY THIS
 TENANT SPACE WILL BE? FBC-B 303.1
  
 3) SHEET A-1 THE OCCUPANCY LOAD FOR TTHE ASSEMBLY
 OCCUPANCY 1819 SQ FT / 15= 18 OCCUPANTS, SHOULD READ
 122 OCCUPANTS . TABLE 1004.1.1.
  
 4) SHEET A-1 INDICATES A 1HR RATED WALL BETWEEN THE
 BUSINESS OCUPANCY AND THE ASSEMBLY OCCUPANCY, PLEASE
 REVIEW TABLE 508.3.3 FOR A NON-SPRINKLED BUILDING, A
 TWO HOUR RATED WALL WILL BE REQUIRED.
  
 5) SHEET A-1 WIND DESIGN INFORMATION INDIATES A "B"
 EXPOSURE, THE ORIGINAL DESIGN UNDER PERMIT # 08110565
 WAS A "C" EXPOSURE.
  
 6) PLANS DO NOT PROVIDE A DOOR SCHEDULE, FBC-B
 1008.1.1.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2010-06-21 Time   Rev Time 0.00
Received By btrobaug Date 2010-06-21 Time 14:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-05-11 Cont ID  
Sent By btrobaug Date 2010-05-11 Time 11:15 Rev Time 0.00
Received By btrobaug Date 2010-05-11 Time 11:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-06-18 Cont ID  
Sent By mawillia Date 2010-06-18 Time 13:25 Rev Time 0.00
Received By mawillia Date 2010-06-18 Time 13:08 Sent To  
Notes
2010-06-18 13:22:35*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A-1 AND E-1 WERE STAMPED
 INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-05-12 Cont ID  
Sent By mawillia Date 2010-05-12 Time 15:52 Rev Time 0.00
Received By mawillia Date 2010-05-12 Time 14:55 Sent To  
Notes
2010-05-12 15:52:39*****DENIED*****
  
  
 1. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCE. ON SHEET 2, ELECTRICAL SPECS NOTE NUMBER 7
 INCORRECTLY REFERENCE THE 2003 EDITION.
  
 2. ON SHEET A-1, DESIGN OCCUPANCY LOAD INFORMATION
 INCORRECT.
  
 3. ON SHEET E-1, SMOKE DETECTOR ARE INDICTED IN THE
 BUILDING. IT IS ASSUME THAT THE BUILDING IS EQUIPPED
 WITH A FIRE ALARM SYSTEM
  
 4. SHOW THE LOCATION OF THE FIRE EXTINGUISHER WHICH
 SATISFIES THE 75 FOOT TRAVEL DISTANCE.
  
 5. PROVIDE A DOOR SCHEDULE AND RATINGS FOR ANY FIRE
 DOORS.
  
 6. PLEASE BE ADVISED FOR NEW ASSEMBLY OCCUPANCIES WHERE
 THE OCCUPANT LOAD EXCEED 100 THE OCCUPANCY SHALL BE
 PROTECTED THROUGHOUT BY AN APPROVED SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM. THEY ARE (1) DANCE HALL,
 (2) DISCOTHEQUES, (3) NIGHT CLUB OR ASSEMBLY USAGE, (4)
 ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING.
  
 7. IN ASSEMBLY OCCUPANCIES, ANY DOOR ANY REQUIRED MEANS
 OF EGRESS FROM AN AREA HAVING AN OCCUPANT LOAD OF 100
 OR MORE PERSONS SHALL BE PROVIDED WITH PANIC HARDWARE
 OR FIRE EXIT HARDWARE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-10 Cont ID  
Sent By vmolina Date 2010-06-10 Time 08:35 Rev Time 0.00
Received By vmolina Date 2010-06-10 Time 08:35 Sent To  
Notes
2010-06-10 08:41:20B-4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-17 Cont ID  
Sent By jwitmer Date 2010-05-17 Time 14:18 Rev Time  
Received By hmoser Date 2010-04-29 Time 07:48 Sent To  
Notes
2010-04-29 07:52:21INCOMING SENT TO B-7

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-06-29 Cont ID  
Sent By rregueir Date 2010-06-29 Time 13:50 Rev Time 0.00
Received By rregueir Date 2010-06-29 Time 13:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-05-17 Cont ID  
Sent By hmoser Date 2010-05-17 Time 13:57 Rev Time 0.00
Received By hmoser Date 2010-05-17 Time 13:29 Sent To  
Notes
2010-05-17 14:09:46PLAN DENIED
 1) PLEASE REFER TO SECTION 601.4 BALANCED RETURN AIR.
 2) PLEASE PROVIDE ON THE MECHANICAL PLANS THE BATH ROOM
 EXHAUST SHOWING CFM AND TERMINATION OF EXHAUST DUCT .
 3) PLEASE SHOW THE FRESH AIR REQUIREMENTS ON THE
 MECHANICAL PLANS .
 4) PLEASE SHOW A CURB TIE DOWN DETAIL ON THE PLANS .
 5) PLEASE REFER TO SECTION 301.12 WIND RESISTANCE 2007
 FBC (M) .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-06-17 Cont ID  
Sent By lwagner Date 2010-06-17 Time 14:06 Rev Time 0.00
Received By lwagner Date 2010-06-17 Time 11:26 Sent To  
Notes
2010-06-17 14:08:20****NOTE****
  
 BOTTOM OF LAV APRON TO BE 29" A.F.F. FBC 11-4.19.2

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-05-11 Cont ID  
Sent By lwagner Date 2010-05-11 Time 14:47 Rev Time 0.00
Received By lwagner Date 2010-05-11 Time 12:03 Sent To  
Notes
2010-05-11 14:17:32FBC 2007
 1ST REVIEW: DENIED
  
 1. PLEASE INDICATE OCCUPANCY TYPE.
  
 2. FBC PLUMBING 403.1 MINIMUN FIXTURES: MOP SINK
 REQUIRED FOR ASSEMBLY OCCUPANCY.
  
 3. WATER ISOMETRIC: 3/4" PIPE REQUIRED FOR MORE THAN 2
 FIXTURES. TABLE 603.1
  
 4. SAN ISOMETRIC: 2" SHOWN BETWEEN WC'S - 3" MINIMUM
 REQUIRED.
  
 5. FBC BUILDING 11-4.16.4 THE GRAB BAR BEHIND THE WATER
 CLOSET SHALL BE 36" MINIMUM.
  
 6. FBC BUILDING 11-4.19.2 THE LAV. SHALL HAVE A
 CLEARANCE OF 29" TO THE BOTTOM OF THE APRON.
  
 REVIEW BY LARRY WAGNER