Plan Review Details - Permit 10040667
Plan Review Stops For Permit 10040667
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-04-27 Cont ID  
Sent By btrobaug Date 2010-04-27 Time 14:22 Rev Time 0.00
Received By btrobaug Date 2010-04-27 Time 12:47 Sent To I
Notes
2010-04-27 14:13:13 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.***CIRCUIT L42 SHOWN
 FEEDING NIGHT LIGHTS AND SOME EMERGENCY LIGHTS ON SHEET
 E-2, IS LISTED AS SPARE ON THE PANEL SCHEDULE. CHEK ALL
 PANEL SCHEDULES FOR ACCURACY.
  
 2} PER 700.12(F)(4)A RELAYING DEVICE ARRANGED TO
 ENERGIZE THE LAMPS AUTOMATICALLY UPON FAILURE OF THE
 SUPPLY TO THE UNIT EQUIPMENT
 THE BATTERIES SHALL BE OF SUITABLE RATING AND CAPACITY
 TO SUPPLY AND MAINTAIN AT NOT LESS THAN 871/2 PERCENT
 OF THE NOMINAL BATTERY VOLTAGE FOR THE TOTAL LAMP LOAD
 ASSOCIATED WITH THE UNIT FOR A PERIOD OF AT LEAST 11/2
 HOURS, OR THE UNIT EQUIPMENT SHALL SUPPLY AND MAINTAIN
 NOT LESS THAN 60 PERCENT OF THE INITIAL EMERGENCY
 ILLUMINATION FOR A PERIOD OF AT LEAST 11/2 HOURS.
 STORAGE BATTERIES, WHETHER OF THE ACID OR ALKALI TYPE,
 SHALL BE DESIGNED AND CONSTRUCTED TO MEET THE
 REQUIREMENTS OF EMERGENCY SERVICE.
 UNIT EQUIPMENT SHALL BE PERMANENTLY FIXED IN PLACE
 (I.E., NOT PORTABLE) AND SHALL HAVE ALL WIRING TO EACH
 UNIT INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF
 ANY OF THE WIRING METHODS IN CHAPTER 3. FLEXIBLE
 CORD-AND-PLUG CONNECTION SHALL BE PERMITTED, PROVIDED
 THAT THE CORD DOES NOT EXCEED 900 MM (3 FT) IN LENGTH.
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT
 EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL
 BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND
 BY ONE OF THE WIRING METHODS OF CHAPTER 3.
  
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-27 Cont ID  
Sent By btrobaug Date 2010-04-27 Time 14:23 Rev Time 0.00
Received By btrobaug Date 2010-04-27 Time 14:22 Sent To  
Notes
***NONE***