Plan Review Details - Permit 10040586
Plan Review Stops For Permit 10040586
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-05-24 Cont ID  
Sent By jwitmer Date 2010-05-24 Time 10:25 Rev Time 0.77
Received By jwitmer Date 2010-05-19 Time 14:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-27 Cont ID  
Sent By jwitmer Date 2010-04-27 Time 15:53 Rev Time 2.22
Received By jwitmer Date 2010-04-27 Time 14:02 Sent To  
Notes
2010-04-27 16:18:58BUILDING PLAN REVIEW
 PERMIT: 10040586
 ADD: 515 N FLAGLER #1900
 CONT: ANDERSON & MOORE
 TEL: (561)662-1819
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) COMPLIED: 4/28/2010 SPOKE WITH JESSICA GOMES & DANNY
 BROWN ABOUT ELEVATOR LOBBY, SEE SHEET FA-1.01 NOTE FOR
 ELECTRIC LOCKS LOCATED IN THE ELEVATOR LOBBY TO BE FAIL
 SAFE WHEN FIRE ALARM IS ACTIVATED.
  
 SHEET A1.0 THE ELEVATOR LOBBY ROOM # 1900 IS INDICATED
 AS A ONE HOUR RATED WALL AS REQUIRED BY 708.1(5) AND
 708.3 FOR THE FIRE RESISTANCE RATING. THE ISSUE IS BOTH
 DOORS 1900A AND 1900B BOTH INDICATE ELECTRIC LOCKS WITH
 CARD READERS. IF THE FIRE ALARMS ARE ACTIVATED AND THE
 ELEVATORS ARE RECALLED DURING PHASE 1 ELEVATOR RECAL AS
 REQUIRED BY CHAPTER 30 ANY OCCUPANTS THAT WERE IN THE
 ELEVATOR LOBBY THAT DIDN'T HAVE CARD READERS WOULD BE
 STRANDED. FBC-B 707.14.1 ESTABLISHES THAT EVERY
 ELEVATOR LOBBY SHALL HAVE ACCESS TO AT LEAST ONE MEANS
 OF EGRESS; ENSURING THAT NO OCCUPANT IN A LOBBY IS LEFT
 ISOLATED FROM ESCAPE WHEN THE ELEVATORS ARE RECALLED
 DURING PHASE 1 ELEVATOR RECALL. ASME A17.1 SAFETY CODE
 FOR ELEVATOR
 DETAILS RECALL REQUIREMENTS, WHICH ARE ADOPTED BY
 REFRENCE IN CHAPTER 30.
  
 2) COMMONLY THE RESTROOMS ARE CONSIDERED COMMON AREA
 SINCE THEY ARE OUT OF THE LEASE LINE, IN THIS CASE THEY
 ARE LOCATED WITHIN THE TENANT SPACEDETAIL B/ A-2.1
 INDICATES AMBLATORY TYPE STALLS, (ALTERNATE STALL TYPE
 B), PLEASE REVIEW FIGURE 30-B IN REGARDS TO SIZE OF
 STALL, DOOR SWING AND DOOR CLEAR OPENING WIDTH. SINCE
 THTE RESTROOMS ARE NOW LOCATED WITHIN THE LEASE LINE,
 TECHNICALLY INFEASIBLE CAN NOT BE AN ISSUE AND
 11-4.1.6(2)(2)(A) DUTY TO PROVIDE ACCESSIBLE FEATURES.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
 MAY 12/ 2010 DISCUSSED 19TH FLOOR RESTROOMS WITH
 PLUMBING REVIEWER LARRY WAGNER THE E-MAIL ATTACHMENT
 RECEIVED YESTERDAY ONDICATING THE CHANGES TO BE MADE
 WITH DOORWAYS WILL ALLOW THE RESTROOMS TO BE CONSIDERED
 COMMON AREA RESTROOMS OUTSIDE OF THE TENANT SPACE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-05-04 Cont ID  
Sent By btrobaug Date 2010-04-28 Time 16:42 Rev Time 0.00
Received By btrobaug Date 2010-04-28 Time 16:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-05-24 Cont ID  
Sent By mawillia Date 2010-05-24 Time 11:17 Rev Time 0.00
Received By mawillia Date 2010-05-24 Time 10:55 Sent To  
Notes
2010-05-24 11:16:59****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS LS-1, A-1.1, A-1.5, E1.01,
 E2.01, AND FA1.01 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPTAIN MICHAEL A. WILLIAMS
 FIRE PLAN REVIEWER
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-04-30 Cont ID  
Sent By mawillia Date 2010-04-30 Time 14:15 Rev Time 0.00
Received By mawillia Date 2010-04-30 Time 13:16 Sent To  
Notes
2010-04-30 14:07:48*****UNSAT*****
  
 THE APPROPRIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER PLAN EXAMINERS' COMMENTS AS WELL AS THE
 FOLLOWING FIRE REVIEW COMMENTS HAVE BEEN ADDRESSED:
  
 1. DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS
 ACCESSED-CONTROLLED SYSTEM PROVIDED THAT ALL THE
 FOLLOWING CRITERIA ARE MET AS PER 7.2.1.6.2 OF NFPA 101
 LIFE SAFETY CODE, 2006 FLORIDA EDITION.
  
 2. PLANS DO NOT REFLECT THE LAYOUT OF THE FIRE
 SPRINKLERS AS PER PROPOSED SCOPE OF WORK. BE ADVISED
 THAT ANY REMODEL/ALTERATION OF THIS SYSTEM SHALL
 REQUIRE SEPARATE PLANS AND PERMIT.
  
  
 CAPTAIN MICHAEL A. WILLIAMS
 FIRE PLAN REVIEWER
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-05-19 Cont ID  
Sent By shill Date 2010-05-19 Time 14:14 Rev Time 0.00
Received By shill Date 2010-05-19 Time 14:12 Sent To  
Notes
2010-05-19 14:13:55****EXPEDITED****
  
 B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-14 Cont ID  
Sent By hmoser Date 2010-05-14 Time 14:54 Rev Time 0.00
Received By hmoser Date 2010-04-22 Time 12:03 Sent To  
Notes
2010-04-27 12:18:01*******************EXPEDITED********************
 B--3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-05-14 Cont ID  
Sent By hmoser Date 2010-05-14 Time 14:51 Rev Time 0.00
Received By hmoser Date 2010-05-14 Time 14:50 Sent To  
Notes
2010-05-14 14:53:51REFER TO SECTION 602.2.1 MATERIALS EXPOSER WITHIN
 PLENUMS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-05-24 Cont ID  
Sent By lwagner Date 2010-05-24 Time 09:17 Rev Time 0.00
Received By lwagner Date 2010-05-24 Time 09:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-04-28 Cont ID  
Sent By lwagner Date 2010-04-28 Time 08:57 Rev Time 0.00
Received By lwagner Date 2010-04-27 Time 14:00 Sent To  
Notes
2010-04-27 15:21:581. PLEASE SEE BUILDING REVIEW FOR COMMENTS ON
 RESTROOMS.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  