Plan Review Details - Permit 10040509
Plan Review Stops For Permit 10040509
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-04-27 Cont ID  
Sent By jwitmer Date 2010-04-27 Time 08:02 Rev Time 0.77
Received By jwitmer Date 2010-04-27 Time 08:02 Sent To  
Notes
2010-04-27 08:25:25BUILDING PLAN REVIEW
 PERMIT: 10040509
 ADD: 2250-2260 PALM BEACH LAKES BLVD
 CONT: LTL BUILDERS, INC LEONARD TYLKA JR.
 TEL: (561)628-9753
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 DESIGN PROFESSIONAL: LEONARD TYLKA JR.- ARCHITECT
  
 DATE: 4-27-2010
  
 I SPOKE WITH MR TYLKA IN REGARDS TO THE EXISTING TENANT
 SEPARATION WALLS ALSO BEING OCCUPANCY SEPARATION
 (EXISTING BUILDING 912.5.3) THIS SPACE BEING A A-3
 OCCUPANCY AND MR TYLKA VERIFYING A BUSINESS OCCUPANCIES
 ON BOTH SIDES. WE AGREED A (2) HR WALL WOULD BE
 REQUIRED (FBC-B TABLE 508.3.3) SINCE THERE IS NO FIRE
 SPRINKLERS WITHIN THE BUILDING. A REVISION WILL BE
 COMING IN BEFORE THE FRAMING INSPECTION INDICATING HOW
 THE 2 HR WALL WILL BE BUILT.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS WILL
 REQUIRE ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-05-04 Cont ID  
Sent By btrobaug Date 2010-05-04 Time 15:15 Rev Time 0.00
Received By btrobaug Date 2010-05-04 Time 15:01 Sent To  
Notes
2010-05-04 15:15:06THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES. INDICATE IF NEW OR EXISTING. 106.3.5 FBC.
  
 2} 13-415.1.AB.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING.
 A. A CONTROL DEVICE SHALL BE INSTALLED THAT
 AUTOMATICALLY TURNS LIGHTING OFF WITHIN 30 MINUTES OF
 ALL OCCUPANTS LEAVING A SPACE, EXCEPT SPACES WITH
 MULTISCENE CONTROL, IN THE FOLLOWING:
 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS,
 LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE
 CLASSROOMS).
 2. CONFERENCE/MEETING ROOMS.
 3. EMPLOYEE LUNCH AND BREAK ROOMS.
  
 3} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1*** SHOW COMPLIANCE ON THE PLAN. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATING THE
 WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT
 CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES
 ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-05-10 Cont ID  
Sent By mawillia Date 2010-05-10 Time 16:43 Rev Time 0.00
Received By mawillia Date 2010-05-10 Time 15:33 Sent To  
Notes
2010-05-10 16:43:27*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. THE ACTUAL PROJECT SITE ADDRESS, INCLUDING SUITE
 NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 3. SHOW LOCATION OF EXIT LIGHTS, EMERGENCY LIGHTS, AND
 FIRE EXTINGUISHERS.
  
 4. SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS
 FOR THIS NEW ASSEMBLY OCCUPANCY IN TERMS OF CLASS A,
 CLASS B, OR CLASS C.
  
 5. NO DOOR DETAIL INCLUDED IN PLAN. BE ADVISED - ANY
 DOOR IN AN REQUIRED MEANS OF EGRESS FROM AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE SHALL BE PERMITTED TO
 BE PROVIDED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE.
 ONLY APPROVED PANIC HARDWARE SHALL BE USED ON DOORS
 THAT ARE NOT FIRE DOORS; ONLY APPROVED FIRE EXIT
 HARDWARE SHALL BE USED ON FIRE DOORS.
  
 6. FOR NEW ASSEMBLY OCCUPANCIES, (AS PER 12.3.5.1 OF
 NFPA 101 - LIFE SAFETY CODE - FLORIDA 2007 EDITION),
 WHERE THE OCCUPANT LOAD EXCEEDS 100, THE FOLLOWING
 ASSEMBLY OCCUPANCIES SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED SUPERVISED AUTOMATIC SPRINKLER SYSTEM: (1)
 DANCE HALLS, (2) DISCOTHEQUES, (3) NIGHTCLUBS OR
 SIMILAR USAGE, (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL
 SEATING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW THE ABOVE ITEMS ARE
 ADDRESSED
  
  
 MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-21 Cont ID  
Sent By hmoser Date 2010-05-21 Time 08:00 Rev Time 0.00
Received By hmoser Date 2010-04-20 Time 16:31 Sent To  
Notes
2010-04-26 16:37:49C--8

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-04-27 Cont ID  
Sent By jwitmer Date 2010-04-27 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2010-04-27 Time 08:25 Sent To  
Notes
2010-04-27 08:26:30CHANGE OF OCCUPANCY:
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-05-21 Cont ID  
Sent By hmoser Date 2010-05-21 Time 07:55 Rev Time 0.00
Received By hmoser Date 2010-05-21 Time 07:40 Sent To  
Notes
2010-05-21 07:59:59PASS PROVISO
 PLEASE PROVIDE DUCT SIZE AND CFM ON THE BATHROOM DUCT
 BE FOR 1ST INSPECTION .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-05-18 Cont ID  
Sent By lwagner Date 2010-05-18 Time 13:45 Rev Time 0.00
Received By lwagner Date 2010-05-17 Time 08:59 Sent To  
Notes
2010-05-17 09:25:511. PLUMBING PERMIT REQUIRED.
 2. NO PLUMBING ON DRAWING AT THIS TIME.
 3. FBC 2007 11-4.16.2 FIGURE 28 - WC 18" ABSOLUTE
 MEASUREMENT

Review Stop Z ZONING
Rev No 1 Status P Date 2010-05-19 Cont ID  
Sent By astelly Date 2010-05-19 Time 11:32 Rev Time 0.00
Received By astelly Date 2010-05-19 Time 11:32 Sent To  
Notes
***NONE***