| Plan Review Stops For Permit 10040402 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-04-16 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2010-04-16 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2010-04-16 |
Time |
16:21 |
Sent To |
PC |
|
| Notes |
| 2010-04-16 16:08:32 | APPROVED WITH THE FOLLOWING EXCEPTION: | | | | | | IT IS NOT PERMISSABLE TO INSTALL A GFCI RECEPTACLE ON | | | THE WASHING MACHINE CIRCUIT PER 210.11(C)(2) OF THE | | | 2008 NEC. | | | IT IS PERMISSIBLE TO INSTALL A GFCI RECEPTACLE ON | | | ANOTHER BRANCH CIRCUIT SERVING THE LAUNDRY AREA IN | | | CONFORMANCE WITH ALL APPLICABLE REQUIREMENTS OF THE | | | GOVERNING CODES. |
|
|
|