Plan Review Details - Permit 10040294
Plan Review Stops For Permit 10040294
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-05-27 Cont ID  
Sent By lmartine Date 2010-05-27 Time 15:57 Rev Time 0.00
Received By lmartine Date 2010-05-27 Time 15:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-19 Cont ID  
Sent By shill Date 2010-04-19 Time 13:47 Rev Time 0.00
Received By shill Date 2010-04-19 Time 13:47 Sent To  
Notes
2010-04-19 13:49:55****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE REVISED DEFINITION OF EXPOSURE C. PLEASE EITHER
 HAVE ENGINEER REVISE EXPOSURE CLASSIFICATION OR CONTACT
 ME PRIOR TO RESUBMITTAL TO DISCUSS. FBC R301.
  
 PLEASE NOTE THAT IN THE FUTURE, PERMIT APPLICATIONS
 SUBMITTED WITH AN INCORRECT EXPOSURE CLASSIFICATION MAY
 BE ISSUED WITH PROVISO THAT A REVISION BE SUBMITTED
 (WITH FEES). IN THE FUTURE PLEASE CONFIRM EXPOSURE
 CLASSIFICATION PRIOR TO SUBMITTAL IN ORDER TO AVOID
 REVISION FEES.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-05-20 Cont ID  
Sent By shill Date 2010-05-20 Time 09:12 Rev Time 0.00
Received By shill Date 2010-05-20 Time 09:12 Sent To  
Notes
2010-05-20 09:12:57TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-19 Cont ID  
Sent By shill Date 2010-04-19 Time 13:50 Rev Time 0.00
Received By shill Date 2010-04-13 Time 11:04 Sent To  
Notes
2010-04-13 11:04:23TO ZONING
  

Review Stop Z ZONING
Rev No 2 Status P Date 2010-05-26 Cont ID  
Sent By eschneid Date 2010-05-26 Time 11:05 Rev Time 0.25
Received By eschneid Date 2010-05-21 Time 15:30 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-04-15 Cont ID  
Sent By eschneid Date 2010-04-15 Time 16:14 Rev Time 0.66
Received By eschneid Date 2010-04-15 Time 16:14 Sent To B
Notes
2010-04-15 16:57:05FAILED
  
 1) PROVIDE A SURVEY LESS THAN ONE YEAR OLD SHOWING ALL
 BUILT FEATURES ON THE SITE. THE SURVEY PROVIDED DOES
 NOT MATCH THE 2009 AERIAL OF THE SITE.
  
 2) THE SETBACK FROM THE PORTION OF THE CARPORT CLOSEST
 TO THE EAST AND WEST PROPERTY LINES IS REQUIRED ON THE
 PLANS. THIS SETBACK SHALL BE PROVIDED FOR THE EXTERIOR
 OF THE POSTS AND THE FURTHEST POINT OF THE OVERHANG.
 NOTE: THE OVERHANG MAY NOT PROJECT MORE THAN 3 FEET
 INTO A REQUIRED SETBACK.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  