Plan Review Details - Permit 10040038
Plan Review Stops For Permit 10040038
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-07-01 Cont ID  
Sent By jwitmer Date 2010-07-01 Time 09:22 Rev Time 0.77
Received By jwitmer Date 2010-07-01 Time 09:22 Sent To  
Notes
2010-07-02 14:46:111818 SOUTH AUSTRALIAN AVENUE, 2ND FLOOR
 PERMIT NUMBER 10040038
 REVISION
  
  
 1. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEM REMODEL. ONLY FAO.1 AND
 FAO.2 PROVIDED. NO FLOOR PLANS PROVIDED FOR FIRE ALARM
 DEVICES.
  
 2. ALL NEW FIRE RATED WALLS ARE TO BE PROPERLY
 IDENTIFIED.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 4. PAGE E2.1 DOES NOT MATCH A-4. ILLUMINATED EXIT SIGN
 MISSING FROM TRAINING ROOM ON PAGE E2.1
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-12 Cont ID  
Sent By jwitmer Date 2010-04-12 Time 14:57 Rev Time 3.77
Received By jwitmer Date 2010-04-12 Time 14:57 Sent To  
Notes
2010-04-12 14:57:51 
 BUILDING PLAN REVIEW
 PERMIT: 10040038
 ADD: 1818 S AUSTRALIAN AVE.
 CONT: IVY DEVELOPMENT
 TEL: (561)954-214-7574
  
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 DESIGNER OF RECORD: PETER CORRALES ARCHITECT
 TEL: (561)995-6700
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1) SHEET A-0 TENANT STATISTICS- TENANT STATISTICS THE
 ABBREVIATION F. O. B. OCCUPANCY IS FOUND, WHAT DOES
 THIS STAND FOR: 106.1.2 ADDITIONAL INFORMATION IS
 REQUIRED. THE OTHER ISSUE IS WITHIN THE SAME HEADING
 THE PLANS INDICATE CODE SECTIONS FBC 304.1.2 & 305.1.2.
 NEITHER OF THESE CODE SECTIONS ARE FOUND IN THE 2007
 FLORIDA BUILDING CODE NOR THE 2007 EXISTING BUILDING
 CODE? 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 2)SHEET A-2, PLANS INDICATE THIS PROJECT TO BE A
 BUSINESS OCCUPANCY BUT THERE ARE TWO AREAS THAT MAKE
 THIS A MIXED USE SEE TRAINING ROOM# 102 AND THE
 EXERCISE ROOM# 118 THE COMBINED AREAS ARE GREATER THAN
 10% OF THE FLOOR AREA CREATING A MIXED OCCUPANCY 508.3
 AND 508.3.1 ACCESSORY OCCUPANCIES. IN EACH CASE THEY
 ARE TO BE CONSIDERED ASSEMBLY OCCUPANCIES TABLE 508.3.3
 SPRINKLED BUILDINGS WILL REQUIRE A ONE HOUR FIRE
 RATING.
  
 3) SHEET A-2, THE TRAINING ROOM# 102 BEING AN ASSEMBLY
 OCCUPANCY WITH A OCCUPANT LOAD OF GREATER THAN 30 WILL
 REQUIRE FIRE RATED CORRIDORS PLEASE REVIEW DOOR# 2
 LEADS INTO A PORTION OF CORRIDOR THAT IS NOT RATED, SEE
 TABLE 1017.1.
  
 4) SHEET A-2 ROOM# 118 THE FITNESS CENTER IS > THAN 832
 SQ. FT./ 15( TABLE 1004.1.1) = 55 OCCUPANTS THIS ROOM
 WILL ALSO NEED TO BE ONE HOUR FIRE RATED PER TABLE
 508.3.3. THE SECOND CONCERN IS THIS ROOM ALSO ONLY HAS
 ONE MEANS OF EGRESS. PLEASE REVIEW TABLE 1019.2.
 DEPENDING ON WHERE THE RATED WALLS ARE PLACED PLEASE
 SEE 712.3.3 DUCTS AND AIR TRANSFER OPENINGS.
 PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS BY DUCTS
 THAT ARE NOT PROTECTED WITH DAMPERS SHALL COMPLY WITH
 SECTIONS 712.2 THROUGH 712.3.1. DUCTS AND AIR TRANSFER
 OPENINGS THAT ARE PROTECTED WITH DAMPERS SHALL COMPLY
 WITH SECTION 716.
  
 5) 106.1.2.ADDITIONAL INFORMATION IS REQUIRED, A-2
 BETWEEN DOOR 14 & DOOR # 19 THERE IS A SECTION OF
 CORRIDOR THAT DOES NOT PROVIDE A WALL TYPE TAG OR
 MATERIALS THIS WALL WILL BE CONSTRUCTED FROM. FBC
 708.1(7).
  
  
  
 6) SHEET A-7 BOTH THE WOMEN???S RESTROOM# 117 AND THE
 MEN???S RESTROOM# 116 THE FINISH SCHEDULE INDICATES THE
 USE OF EPOXY PAINT AS THE WALL FINISH PLEASE REVIEW
 SECTION 1210.2 WALLS. WALLS WITHIN 2 FEET (610 MM) OF
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-07-21 Cont ID  
Sent By btrobaug Date 2010-07-21 Time 15:06 Rev Time 0.00
Received By btrobaug Date 2010-07-21 Time 14:26 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-05-12 Cont ID  
Sent By btrobaug Date 2010-05-12 Time 11:57 Rev Time 0.00
Received By btrobaug Date 2010-05-12 Time 08:29 Sent To  
Notes
2010-05-12 12:04:20TO LARGE PLAN HOLDING BIN UNDER "I"./WRT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-07-02 Cont ID  
Sent By mcarsill Date 2010-07-02 Time 14:46 Rev Time 0.00
Received By mcarsill Date 2010-07-02 Time 14:40 Sent To  
Notes
2010-07-02 14:53:011818 SOUTH AUSTRALIAN AVENUE
 PERMIT NUMBER 10040038
 REVISED PLANS
  
  
 1. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER AND FIRE ALARM SYSTEM REMODELING. ONLY
 FAO-.1AND FAO.2 PROVIDED. NO FLOOR PLANS PROVIDED
 ILLUSTRATING FIRE ALARM EQUIPMENT.
  
 2. ALL NEW FIRE RATED WALLS ARE TO BE PROPERLY
 IDENTIFIED.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 4. PAGE E2.1 DOES NOT MATCH A-4. ILLUMINATED EXIT SIGN
 MISSING FROM TRAINING ROOM PAGE E2.1.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-04-20 Cont ID  
Sent By mawillia Date 2010-04-20 Time 12:51 Rev Time 0.00
Received By mawillia Date 2010-04-20 Time 11:32 Sent To  
Notes
2010-04-20 12:50:05*****DENIED*****
  
  
 1. PROVIDE OCCUPANT LOAD FOR THE TRAINING ROOM (102)
 AND FITNESS CENTER (118) AS IT APPEARS THAT THESE TWO
 ROOMS ARE ASSEMBLY OCCUPANCIES.
  
 2. VERIFY/SHOW THAT THE OCCUPANCY SEPARATION (BUSINESS
 OCCUPANCY / ASSEMBLY OCCUPANCY) OF AT LEAST ONE HOUR AS
 REQUIRED IS PROVIDED IN THE BUILDING.
  
 3. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS. THEY
 MAY BE SHOWN ON THE REFECTED CEILING SHEET.
  
 4. ON SHEET FA0.1. AMEND FIRE ALARM NOTE #17 AND SYSTEM
 OPERATION MATRIX TO REFLECT AS PER LOCAL CODES: DUCT
 SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE ALARM.
  
 5. THE DRAWING INDEX ON SHEET A-0 INDICATES THAT THE
 FIRE ALARM RISER DIAGRAM SHOULD BE FA0.2, HOWEVER,
 THERE ARE TWO SHEETS INDICATED AS FA0.1 (FIRE ALARM
 NOTES) .
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-28 Cont ID  
Sent By lmartine Date 2010-06-28 Time 13:50 Rev Time 0.00
Received By lmartine Date 2010-06-28 Time 13:50 Sent To  
Notes
2010-06-28 14:11:42C--1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-12 Cont ID  
Sent By btrobaug Date 2010-05-12 Time 12:10 Rev Time 0.00
Received By btrobaug Date 2010-04-01 Time 12:12 Sent To  
Notes
2010-05-12 12:11:56TO LARGE PLAN HOLDING BIN UNDER "I"./WRT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hmoser Date 2010-07-13 Time 14:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-07-13 Cont ID  
Sent By hmoser Date 2010-07-13 Time 14:58 Rev Time 0.00
Received By hmoser Date 2010-07-13 Time 14:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-04-26 Cont ID  
Sent By hmoser Date 2010-04-26 Time 14:40 Rev Time 0.00
Received By hmoser Date 2010-04-26 Time 10:38 Sent To  
Notes
2010-04-26 14:50:37PLAN DENIED
 1) PLEASE PROVIDE OCCUPANT LOAD'S FOR OUTSIDE AIR
 CALCULATIONS ON THE PLANS.
 2) PLEASE PROVIDE RETURN AIR NECK SIZES ON THE PLANS .
 3) PLEASE PROVIDE DUCT DETECTORS ON SUPLY AND RETURN NO
 UNITS 1 &1 A , 13 & 13 A PER SECTION 606.2.2 FBC (M) .
 4) PLEASE PROVIDE DUCT SIZE ON THE PLANS FOR HP 1 HP 1A
 AFTER THE 20 X 16 DUCT .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-07-13 Cont ID  
Sent By lwagner Date 2010-07-13 Time 07:34 Rev Time 0.00
Received By lwagner Date 2010-07-13 Time 07:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-04-19 Cont ID  
Sent By lwagner Date 2010-04-19 Time 09:25 Rev Time 0.00
Received By lwagner Date 2010-04-14 Time 15:13 Sent To  
Notes
2010-04-14 15:19:42FBC 2007
 REVIEW ACTION: DENIED
  
 1. FROM BUILDING PLAN REVIEW- IF ASSEMBLY OCCUUPANCY IS
 ADDED, THEN ONE SERVICE SINK WILL BE REQUIRED TO BE
 ADDED TO THE PLUMBING PLANS.
  
 2. ADA SHOWERS DO NOT COMPLY WITH FBC 2007 11-4.21.2-
 FIG 35 FOR CLEAR SPACE AT HC SHOWER. 12" REQUIRED
 BEYOND SEAT, 5" SHOWN.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-05-12 Cont ID  
Sent By lfranco Date 2010-05-12 Time 09:44 Rev Time 0.50
Received By lfranco Date 2010-05-12 Time 09:44 Sent To  
Notes
2010-05-12 09:45:37PERMIT ORIGINALLY NOT IN BIN.