Plan Review Details - Permit 10040036
Plan Review Stops For Permit 10040036
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-05-04 Cont ID  
Sent By jwitmer Date 2010-05-04 Time 11:05 Rev Time 0.77
Received By jwitmer Date 2010-05-04 Time 11:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-14 Cont ID  
Sent By jwitmer Date 2010-04-14 Time 09:13 Rev Time 0.00
Received By jwitmer Date 2010-04-14 Time 08:00 Sent To  
Notes
2010-04-14 09:27:42BUILDING PLAN REVIEW
 PERMIT: 10040036
 ADD: 5716 S DIXIE HWY
 CONT: AFFORDABLE HOUSING REN DEV
 TEL: (561)644-0302
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) LS-1 MINIMUM OCCUPANT LOAD INDICATES THTTE 2004 FBC,
 PLEASE UPDATE CODES TO THE 2007 FBC WITH 2009
 SUPPLEMENTS.
  
 2) PLANS ALSO SHOULD BE DESIGNED TO THE 2007 EXISTING
 BUILDING CODE WITH 2009 SUPPLEMENTS. FBC EXISTING
 BUILDING CODE- 401.4 A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 3) SHEET LS-1 & 301, DOORWAY 150 EXISTING FRONT ENTRY,
 THE PLANS INDICATE AS EXISTING, PLEASE REVIEW SECTION
 11-4.8.4 (4) IF A DOORWAY IS LOCATED AT A LANDING, THEN
 THE AREA IN FRONT OF THE DOORWAY SHALL COMPLY WITH
 SECTION 11-4.13.6.
  
 1-4.13.6 MANEUVERING CLEARANCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIGURE 25. THE
 FLOOR OR GROUND AREA WITHIN THE REQUIRED CLEARANCES
 SHALL BE LEVEL AND CLEAR.
  
 PLEASE REVIEW FIGURE 25(C) THERE ARE TWO ISSUES :
 3.1 THE FIGURE INDICATES FOR A SIDE APPROACH FROM THE
 LEADING EDGE OF THE DOOR TO THE BEGINNING OF THE RAMP
 24 INCHES IS REQUIRED NOT THE 1'-6" INDICATED ON THE
 PLANS.
  
 3.2 PLEASE INDICATE IF THE EXISTING DOOR #150 HAS OR IS
 GOING TO HAVE A DOOR CLOSER INSTALLED IF SO PLEASE SEE
 NOTE AT THE BOTTOM OF FIGURE 25 (C) Y= 54 INCHES IF THE
 DOOR HA A CLOSER.
  
 4) PLANS ARE CORRECT IN NOT REQUIRING A HANDRAIL IF THE
 HEIGHT IS 6" OR LESS AND THE RUN IS 72 INCHES OR LESS.
 WHAT THE PLANS DO NOT PROVIDE IS EDGE PROTECTION.
 11-4.8.7 EDGE PROTECTION. RAMPS AND LANDINGS WITH
 DROP-OFFS SHALL HAVE CURBS, WALLS, RAILINGS, OR
 PROJECTING SURFACES THAT PREVENT PEOPLE FROM SLIPPING
 OFF THE RAMP. CURBS SHALL BE A MINIMUM OF 2 INCHES (50
 MM) HIGH (SEE FIGURE 17). WITH THE DOORWAY A DISSABLED
 PERSON IN A WHEEL CHAIR WOULD HAVE THE POSSIBILITY OF
 BACKING UP AND ROLLING OVER THE EDGE. THE OTHER ISSUE
 WITH THIS DESIGN IS THE EXISTING WALKWAY TO THE EAST,
 IF A PERSON WERE TO USE THIS WALKWAY THE REQUIRED EDGE
 PROTECTION REQUIRED BY 11-4.8.7 WILL CREATE A TRIPPING
 HAZARD, IT APPEARS MORE THOUGHT MAY BE REQUIRED FOR
 THIS AREA. NOTE THE SIDEWALK IS ALSO ONLY 2'-0" WIDE.
  
 5) SHEET 301 THE ACCESSIBLIE RAMP WILL HAVE NEW ISSUES
 SINCE IT WILL BE MOVED 6" CLOSER TO THE PROPERTY LINE
 TO ACCOMADATE THE 24 INCHES FROM THE DOOR TO THE EDGE
 OF THE RAMP AT THE UPPER LANDING. PLANS FAIL TO
 INDICATE THE LOCATION OF THE BOTTOM LANDING SECTION
 11-4.8.4(2) REQUIRES THE BOTTOM LANDING TO BE 72", THIS
 IS NOT SHOWN ON THE PLAN.
  
  
 NOR IS A HANDICAPPED
 PARKING SPACE? PLEASE REVIEW 11-4.1.6(2)(2)(A) DUTY TO
 PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 6) SHEET 301 DETAIL # 4 THE BREAKROOM 107 CABINET
 DETAIL AT THE SINK PLANS DO INDICATE A SINK HEIGHT OF
 2'-10" BUT THE PLANS ALSO INDICATE THE USE OF SHELVING
 UNDER THE SINK BEHIND CLOSED DOORS. SECTION 11-4.24.5
 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT LEAST 30
 INCHES BY 48 INCHES (760 MM BY 1219 MM) COMPLYING WITH
 SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK
 TO ALLOW FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF
 19 INCHES (485 MM) UNDERNEATH THE SINK (SEE FIGURE 32).
 REQUIRES BOTH THE DOORS AND SHELVING BENEATH THE SINK
 BE REMOVED FOR A FORWARD APPROACH.
  
 1-4.24.6 EXPOSED PIPES AND SURFACES. HOT WATER AND
 DRAIN PIPES EXPOSED UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT AGAINST CONTACT.
 THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
 11-4.24.7 FAUCETS. FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS ARE ACCEPTABLE
 DESIGNS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-04-12 Cont ID  
Sent By btrobaug Date 2010-04-12 Time 11:07 Rev Time 0.00
Received By btrobaug Date 2010-04-12 Time 10:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-05-03 Cont ID  
Sent By mawillia Date 2010-05-03 Time 14:51 Rev Time 0.00
Received By mawillia Date 2010-05-03 Time 14:33 Sent To  
Notes
2010-05-03 14:51:41*****APPROVED*****
  
 THE COMMENTS FROM THEW PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS LS-1, 301,302, 303, AND 802 WERE
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-04-16 Cont ID  
Sent By mawillia Date 2010-04-16 Time 13:50 Rev Time 0.00
Received By mawillia Date 2010-04-16 Time 12:15 Sent To  
Notes
2010-04-16 12:53:33*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. THE COMBO EXIT/EMERGENCY LIGHT SHOWN IN THE VICINITY
 OF THE INTERIOR DOOR APPEARS TO BE ON THE WRONG SIDE
 WHICH MAY DIRECT PATRONS TO THE ALTENATE MEANS OF
 EGRESS (INDICATED ON SHEET LS-1 AS NO EXIT LIGHT
 REQUIRED).
  
 3. IF THE RAMP IS PART OF A CURB THAT SEPARATES A
 SIDEWALK FROM VEHICULAR TRAFFIC WAY, IT SHALL NOT BE
 REQUIRED TO HAVE A HANDRAIL. OTHERWISE THE RAMP SHALL
 HAVE HANDRAILS ON BOTH SIDES.
  
 4. IF HANDRAILS ARE REQUIRED, PROVIDE THE PRESCRIPTIVE
 STRENGHTS FOR THOSE HANDRAILS
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-04-26 Cont ID  
Sent By jgomez Date 2010-04-26 Time 08:58 Rev Time 0.00
Received By jgomez Date 2010-04-26 Time 08:58 Sent To  
Notes
2010-04-26 09:03:17SENT TO B-2.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-16 Cont ID  
Sent By jwitmer Date 2010-04-16 Time 11:30 Rev Time 0.00
Received By jwitmer Date 2010-04-01 Time 09:22 Sent To  
Notes
2010-04-08 09:27:06B--3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-05-06 Cont ID  
Sent By jwitmer Date 2010-05-06 Time 11:31 Rev Time 0.55
Received By jwitmer Date 2010-05-06 Time 11:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-04-15 Cont ID  
Sent By hmoser Date 2010-04-15 Time 14:21 Rev Time 0.00
Received By hmoser Date 2010-04-15 Time 14:21 Sent To  
Notes
2010-04-15 14:43:10PLANS DENIED
 1) PER NOTE #14 PLEASE REFER TO SECTION 504.4 EXHAUST
 INSTALLATION . SCREENS SHALL NOT BE INSTALLED AT THE
 DUCT TERMINATION .
 2) PLEASE REFER TO SECTION 504.6.1 MAXIMUM LENGTH .
 3) ROOM 106 PLEASE REFER TO TABLE 403.3 NAIL SALON SEE
 FOOT NOTE D & I
 4) PLEASE SHOW THE LOCATION OF THE RETURN AIR INTAKE ON
 THE PLANS REFER TO SECTION 407 FBC(M)
 5) PLEASE PROVIDE FRESH AIR CALCULATIONS ON THE PLANS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-04-26 Cont ID  
Sent By lwagner Date 2010-04-26 Time 13:28 Rev Time 0.00
Received By lwagner Date 2010-04-26 Time 13:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-04-14 Cont ID  
Sent By lwagner Date 2010-04-14 Time 13:52 Rev Time 0.00
Received By lwagner Date 2010-04-14 Time 13:28 Sent To  
Notes
2010-04-14 13:51:34FBC 2007
 ACTION: DENIED
  
 1. PAGE 301- 18" FROM SIDE WALL IS AN ABSOLUTE
 MEASURMENT FOR HC WATER CLOSETS FBC 11-4.16 FIGURE 28.
  
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-10-26 Cont ID  
Sent By ajones Date 2010-05-06 Time 10:24 Rev Time 0.00
Received By ajones Date 2010-04-20 Time 12:48 Sent To  
Notes
***NONE***