Plan Review Details - Permit 10030717
Plan Review Stops For Permit 10030717
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-07-27 Cont ID  
Sent By jgomez Date 2010-07-27 Time 08:26 Rev Time 0.00
Received By jgomez Date 2010-07-27 Time 08:26 Sent To PC
Notes
2010-07-27 08:30:52BUILDING REVIEW APPROVED WITH PROVISO:
 -1- PROVIDE PRODUCT APPROVALS FOR: (A) GARAGE DOOR THAT
 MEETS THE DESIGN PRESSURES CALCULATED ON SHEET A-2.0.
 (B) EXTERIOR INSWING AND OUTSWING DOORS. (C) WINDOW
 MULLIONS. (D)STRUCTURAL CONNECTORS. (E) CURRENT ROOF
 TILE AND POLYFOAM ADHESIVE. NOA 07-1023.11 WAS CLOSED
 BY MIAMI-DADE. (F) FLAT ROOF. PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS.
 -2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS.
 -3- ARCHITECT TO COORDINATE WINDOW MATERIAL SPECIFIED
 ON PLANS AND PRODUCT APPROVAL SUBMITTED TO MATCH.
 -4- ENERGY CALCULATIONS: (A) PROVIDE COMPLETE
 INFORMATION ON TOP OF FORM. (B) ENGINEER TO PROVIDE ALL
 HIS INFORMATION AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES. (C) REVISE TYPE OF ROOF SHOWN ON PAGE 2 OF
 ENERGY CALCULATIONS TO MATCH PLANS. (D) COORDINATE
 WINDOW MATERIAL WITH REVISED WINDOW MATERIAL REQUESTED
 ON ITEM #3 ABOVE.
 -5- OUTDOOR FIREPLACE: (A) PROVIDE COMPLETE FRAMING
 DETAILS FOR FIREPLACE AND CHIMNEY. SPECIFY ALL FRAMING
 MEMBERS AND CONNECTORS TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301. (B) DESIGNER OF RECORD
 TO REVIEW AND APPROVE IN WRITING OUTDOOR FIREPLACE
 COMPLETE PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE.
 -6- GUARDRAILS AND HANDRAILS: (A) MISSING GUARDRAILS
 AND HANDRAILS ON WEST STAIRS. SEE SHEET A-1. (B) REVISE
 DETAIL #12 ON SHEET A-1.1. REVISE PICKET SPACING. A 4"
 SPHERE SHALL NOT PASS TRU. SEC. R312.
 -7- PROVIDE COPY OF RECORDED UNITY OF TITLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-27 Cont ID  
Sent By jgomez Date 2010-04-27 Time 15:58 Rev Time 0.00
Received By jgomez Date 2010-04-27 Time 15:58 Sent To PC
Notes
2010-04-27 16:19:10RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) GARAGE DOOR TO BE REPLACED AS SHOWN ON PLANS.
 B) WINDOWS TO BE REPLACED AS SHOWN ON PLANS.
 C) EXTERIOR INSWING AND EXTERIOR OUTSWING DOORS AS
 SHOWN ON PLANS.
 D) WINDOW MULLIONS AS SHOWN ON PLANS.
 E) STRUCTURAL CONNECTORS AS SHOWN ON PLANS FOR NEW
 COVERED PATIO.
 F) ROOF TILE. AND, SPECIFIC ADHESIVE TO BE USED. SEE
 PRODUCT APPROVAL FOR LISTED ADHESIVES.
 G) IF RE-ROOFING ANY FLAT ROOF, THEN PROVIDE PRODUCT
 APPROVAL AND REQUIRED RAS 117 CALCULATIONS. CHECK
 PRODUCT APPROVAL TO VERIFY IF SIGNED AND SEALED
 CALCULATIONS ARE REQUIRED.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 4- APPLY FOR DRIVEWAY UNDER A SEPARATE PERMIT.
  
 5- CLARIFY ISSUE WITH THE UNITY OF TITLE. SEE ZONING
 COMMENTS. THE ADDRESS ON PERMIT APPLICATION AND PLANS
 NEED TO MATCH.
  
 6- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM (AND
 COORDINATE CORRECT ADDRESS WITH ITEM #5 ABOVE).
 B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
 C) ENGINEER DOING THE CALCULATIONS TO PROVIDE ALL HIS
 INFORMATION AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES
 WHEN SUBMITTING INFORMATION FOR PUBLIC RECORDS.
 D) CLARIFY HOW ACHIEVING THE R13 INSULATION ON CONCRETE
 BLOCK WALL ON ITEM #9(B).
 E) REVISE TYPE OF ROOF SHOWN ON PAGE 2 OF ENERGY
 CALCULATIONS. THERE ARE NOT COMPOSITION SHINGLES. SEE
 PLANS AND REVISE AS REQUIRED.
 F) REVISE FRAME MATERIAL FOR WINDOWS. PLANS CALL FOR
 ALUM/ WOOD WINDOWS. SEE PLANS AND REVISE AS REQUIRED.
  
 7- OUTDOOR FIREPLACE:
 A) PROVIDE COMPLETE FRAMING DETAILS FOR FIREPLACE AND
 CHIMNEY. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301 AND WITH THE REQUIREMENTS OF CHAPTER 10 OF 2007
 FLORIDA RESIDENTIAL CODE (INCLUDING UL LISTINGS AND
 CHIMNEY ROOF CLEARANCES).
  
 B) PROVIDE COMPLETE SPECIFICATIONS FOR OUTDOOR
 FIREPLACE AND CHIMNEY.
  
 C) PROVIDE MANUFACTURER'S SPECS SHOWING THAT THE
 CHIMNEY CAP AS SHOWN ON PLANS IS APPROVED BY THEM.
  
 8- SPECIFY ON PLANS THE ROOF TO WALL CONNECTIONS AS
 REQUIRED BY SEC. 611.8 OF THE 2007 EXISTING BUILDING
 CODE.
  
 9- OWES $1978.78 BALANCE OF THE PERMIT FEES.
  
 10- SHEET SP-1: REVISE THE CONSTRUCTION TYPE AND FLOOD
 ZONE SHOWN ON THE BUILDING DATA INFORMATION. THIS IS A
 TYPE VB CONSTRUCTION. AND, THIS BUILDING IS LOCATED ON
 FLOOD ZONE "B".
  
 11- SHEET A-1 (GUARDRAILS, HANDRAILS AND RISERS AND
 TREADS):
 A) SPECIFY GUARDRAILS AND HANDRAILS ON NEW PATIOS AS
 REQUIRED BY SEC. R312.
 B) PROVIDE COMPLETE DETAILS AND SPECS TO SHOW
 COMPLIANCE WITH TABLE R301.5, SEC. R311.5.3 AND SEC.
 R312.
  
 12- SHEET S-1: PROVIDE CALCULATED DESIGN PRESSURES FOR
 EXTERIOR DOORS AND WINDOWS OPENINGS. SEC. R301.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-07-22 Cont ID  
Sent By btrobaug Date 2010-07-22 Time 15:30 Rev Time 0.00
Received By btrobaug Date 2010-07-22 Time 15:00 Sent To  
Notes
2010-07-22 15:31:27PUT IN R-20./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-04-22 Cont ID  
Sent By btrobaug Date 2010-04-22 Time 11:20 Rev Time 0.00
Received By btrobaug Date 2010-04-22 Time 08:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-01 Cont ID  
Sent By vmolina Date 2010-06-01 Time 13:29 Rev Time 0.00
Received By vmolina Date 2010-06-01 Time 13:29 Sent To  
Notes
2010-06-01 13:29:47IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-27 Cont ID  
Sent By jgomez Date 2010-04-27 Time 16:19 Rev Time 0.00
Received By jgomez Date 2010-03-30 Time 14:05 Sent To  
Notes
2010-03-30 14:05:32R 19
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-04-27 Cont ID  
Sent By jgomez Date 2010-04-27 Time 15:58 Rev Time 0.00
Received By jgomez Date 2010-04-22 Time 10:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-04-27 Cont ID  
Sent By jgomez Date 2010-04-27 Time 16:19 Rev Time 0.00
Received By jgomez Date 2010-04-27 Time 16:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-04-27 Cont ID  
Sent By jgomez Date 2010-04-27 Time 16:19 Rev Time 0.00
Received By jgomez Date 2010-04-27 Time 16:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2010-07-03 Cont ID  
Sent By astelly Date 2010-07-03 Time 16:53 Rev Time 0.00
Received By astelly Date 2010-06-15 Time 16:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-04-16 Cont ID  
Sent By astelly Date 2010-04-16 Time 12:27 Rev Time 0.00
Received By astelly Date 2010-04-08 Time 16:30 Sent To  
Notes
2010-04-16 12:39:03AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 THE SURVEY INDICATES THAT THE PROPERTY AT 216 MURRAY
 ROAD HAS BEEN UNIFIED WITH THE PROPERTY AT 213 E.
 LAKEWOOD ROAD. THE COMBINED PROPERTIES HAVE THREE (3)
 DWELLING UNITS WHICH EXCEEDS THE ALLOWABLE NUMBER OF
 UNITS FOR THE ZONING DISTRICT. PROPERTIES MUST BE
 SUBDIVIDED BEFORE APPROVAL CAN BE GIVEN.