| 2010-04-01 15:57:45 | |
| | |
| | 6501 NORTH JOG ROAD |
| | PERMIT NUMBER 10030591 |
| | "INTERIOR DEMO FOR UNIT 1 & 2 FOR SWA TEMPORARY ROOF |
| | HATCH WRITTEN SCOPE OF WORK. |
| | |
| | |
| | 1. DEMOLITION, RENOVATION AND CONSTRUCTION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 2. FIRE AND PARAMEDICAL ACCESS SHALL BE PROVIDED DURING |
| | THE CONSTRUCTION ACTIVITIES. |
| | |
| | 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY OR AS |
| | OFTEN AS NECESSARY. |
| | |
| | 4. ALL FIRE PROTECTION SYSTEMS AND DEVICES SHALL REMAIN |
| | CLEAR AND UNOBSTRUCTED. |
| | |
| | 5. ANY REQUIRED FIRE AND LIFE SAFETY SYSTEM THAT IS |
| | PLACED OUT OF SERVICE FOR MORE THAN FOUR HOURS IN A |
| | TWENTY FOUR HOUR PERIOD SHALL REQUIRE A FIRE WATCH OR |
| | THE BUILDING VACATED. ALL FIRE WATCHES MUST BE IN |
| | WRITING AND APPROVED BY THIS OFFICE. FIRE WATCH |
| | PERSONNEL SHALL HAVE NO OTHER DUTIES, MAINTAIN A LOG, |
| | AND BE RADIO OR CELLULAR TELEPHONE EQUIPPED TO REPORT |
| | EMERGENCIES. |
| | |
| | 6. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY |
| | MODIFICATIONS TO THE FIRE SPRINKLER OR FIRE ALARM |
| | SYSTEMS. |
| | |
| | 7. ALL EXIT DOORS ARE TO REMAIN CLEAR AND UNOBSTRUCTED. |
| | |
| | 8. ALL CUTTING AND WELDING OPERATIONS SHALL COMPLY WITH |
| | NFPA 51B. |
| | |
| | 9. THE OCCUPANCY PORTIONS OF THIS PROJECT WILL BE |
| | REVIEWED UNDER CHAPTER 40, INDUSTRIAL OCCUPANCIES. |
| | |
| | 10. ACCORDING TO SECTION 3.14. AREA DESCRIPTIONS, SOME |
| | NEW GAS PIPING INSTALLATIONS ARE EXPECTED TO OCCUR. GAS |
| | PIPING INSTALLATIONS SHALL BE REVIEWED, APPROVED, AND |
| | INSTALLED IN A SAFE MANNER IN ACCORDANCE WITH |
| | RECOGNIZED STANDARDS. |
| | |
| | 11. ACCORDING TO SECTION 3.2.1 ROADS FOR AREA |
| | DESCRIPTIONS, THE TEMPORARY ROADS SHALL BE INSTALLED |
| | AND MAINTAINED EVEN IN INCLEMENT FOR FIRE RESCUE USE. |
| | |
| | 12. IN SECTION 3.4.1 AREA DESCRIPTIONS, WHEN FIRE HOSE |
| | REELS ARE REMOVED, TEMPORARY MEASURES SHALL BE PROVIDED |
| | UNTIL SUCH TIME AS THEY CAN BE RE-INSTALLED. |
| | |
| | 13. ALL FIRE ALARM SYSTEMS SHALL COMPLY WITH NFPA 72, |
| | 2002 EDITION. |
| | |
| | 14. ALL FIRE SPRINKLER SYSTEM WORK SHALL COMPLY WITH |
| | NFPA 13, 2002 EDITION. |
| | |
| | 15. ALL PORTABLE FIRE EXTINGUISHERS SHALL BE PROPERLY |
| | SERVICE TAGGED. |
| | |
| | 16. PLEASE EXPLAIN WHY THE BOILER BUILDING IS NOT FIRE |
| | SPRINKLER PROTECTED AS DESCRIBED IN SECTION H OF THE |
| | SCOPE OF WORK. |
| | |
| | 17. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE |
| | NATIONAL ELECTRICAL CODE. |
| | |
| | 18. ALL NEW STRUCTURES AND BUILDINGS SHALL BE PROPERLY |
| | PERMITTED PRIOR TO COMMENCING WORK. |
| | |
| | 19. THE NEW ADDITION DESCRIBED IN 3.10.2 SCOPE OF WORK |
| | SHALL BE REVIEWED BY THE CITY TO DETERMINE CODE |
| | COMPLIANCE. |
| | |
| | 20. PLEASE DEFINE ANY FIRE RATED WALLS AND FIRESTOPPING |
| | METHODS PLANNED FOR THE PROJECT. |
| | |
| | 22. ADEQUATE SAFETY MEASURES AND SIGNAGE SHALL BE |
| | INSTALLED TO PREVENT INJURIES OR DEATH AFTER THE HOLES |
| | ARE INSTALLED IN THE ROOF AS DESCRIBED IN SECTION |
| | 3.15.3 IN THE SCOPE OF WORK. |
| | |
| | 23. TEMPORARY BARRICADES OR OTHER MEASURES SHALL BE |
| | UTILIZED TO PREVENT ACCESS INTO UNSAFE OR UNAUTHORIZED |
| | AREAS DURING DEMOLITION . |
| | |
| | 24. TEMPORARY EXIT ROUTES MAY NEED TO BE CONSIDERED AND |
| | UTILIZED DURING WORK ACTIVITIES. |
| | |
| | 25. SHEET 182 MO 023 DOES NOT APPEAR TO PROVIDE ENOUGH |
| | CLARITY FOR REVIEW. |
| | |
| | 26. ALL STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS |
| | SHALL COMPLY WITH NFPA 30. |
| | |
| | 27. CARE MUST BE TAKEN WHEN USING GASOLINE POWERED |
| | EQUIPMENT IN CONFINED SPACES TO PREVENT THE |
| | ACCUMULATION OF CARBON MONOXIDE (CO). CARBON MONOXIDE |
| | IS A COLORLESS, ODORLESS GAS WHICH IS FLAMMABLE IN THE |
| | PROPER CONCENTRATION. ADEQUATE VENTILATION SHALL BE |
| | PROVIDED. |
| | |
| | 28. A COMPREHENSIVE FIRE SAFETY PROGRAM SHALL BE |
| | DEVELOPED AND MAINTAINED DURING THE COURSE OF THIS |
| | PROJECT. THIS PROGRAM SHALL BE SUBMITTED TO THIS OFFICE |
| | AS SOON AS POSSIBLE. PLEASE SEE NFPA 241. |
| | |
| | 29. THESE PLANS PRIMARILY DEMONSTRATE ITEMS AND |
| | MATERIALS THAT WILL BE DEMOLISHED. PLEASE DESCRIBE |
| | METHODS OF DEMOLITION, STORAGE CONFIGURATIONS, ETC. |
| | |
| | 30. THE KEY PLAN IS NOT VERY ILLUSTRATIVE OR |
| | INFORMATIONAL ON SOME SHEETS. |
| | |
| | 31. PLEASE DESCRIBE OVERFIRE AIR PIPING SYSTEMS. |
| | |
| | 32. IN SECTION 4.1.1 CODES, PLEASE THE FLORIDA FIRE |
| | PREVENTION CODE 2007 EDITION, NFPA 101 2006 AND NFPA 1, |
| | 2006 EDITION. |
| | |
| | 33. LIGHTING PROTECTION NFPA 780 THE STANDARD FOR THE |
| | INSTALLATION OF LIGHTNING PROTECTION SYSTEMS TO BE |
| | ADDED TO SECTION 4.2.15. |
| | |
| | 34. PLEASE PROVIDE PROCEDURE FOR LOCKING AND TAGGING |
| | OUT SYSTEMS THAT INVOLVE ALL SYSTEMS. |
| | |
| | 35. OVERALL SITE PLAN DOES NOT ILLUSTRATE ANY FIRE |
| | HYDRANTS, HOSE HOUSES, PROPOSED CRANE LOCATIONS, |
| | STORAGE OR STAGING AREAS. |
| | |
| | |
| | DENIED |
| | |
| | |