Plan Review Details - Permit 10030557
Plan Review Stops For Permit 10030557
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-05-18 Cont ID  
Sent By shill Date 2010-05-18 Time 07:30 Rev Time 0.00
Received By shill Date 2010-05-18 Time 07:30 Sent To  
Notes
2010-05-18 07:45:31****PROVISOS****
 ****ISSUED AT CONTRACTOR'S RISK****
 ****REVISION REQUIRED****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. PROVISO - SEPARATE ROOF PERMIT REQUIRED; NOAS 06
 0626.03, 06 0526.09 REVIEWED BY DOR
 NEED FOAM PRODUCT APPROVAL (CAN SUBMIT WITH ROOF PERMIT
 APPLICATION)
  
 WITH SUBMITTAL OF THE ROOF PERMIT, THE FOLLOWING
 INFORMATION IS REQUIRED:
 A. SELECT APPROVED ASSEMBLY; PER DOR, MOP DOWN SYSTEM
 WILL BE USED, SO NO ENHANCED FASTENING CALCULATIONS
 WILL BE REQUIRED.
 B. ON THE ROOF TILE PRODUCT APPROVAL, INDICATE METHOD
 OF ATTACHMENT TO SHOW COMPLIANCE WITH FBC1609. IF FOAM
 ADHESIVE IS USED, PROVIDE FOAM PRODUCT APPROVAL
 FAC9B72.
  
 2. PER CONTRACTOR, EXPOSURE CLASSIFICATION TO BE
 REVISED TO EXPOSURE C. ALL AFFECTED SHEETS, DESIGN
 PRESSURES, STRUCTURAL DESIGN AS APPLICABLE TO BE
 REVISED PRIOR TO CONSTRUCTION **OR** PROVIDE A LETTER
 FROM DESIGNER OF RECORD WHICH STATES THAT THE PROPOSED
 IMPROVEMENT COMPLIES WITH EXPOSURE C DESIGN PRESSURES.
 REVISION OR LETTER IS TO INCLUDE COMPONENT & CLADDING
 DESIGN PRESSURES. PERMIT ISSUED AT CONTRACTOR'S RISK.
  
 3. PER CONTRACTOR, WINDOWS AT XRAY ROOM EXTERIOR WALL
 TO BE RELOCATED ABOVE 7'. REVISE PLAN TO INCLUDE
 DETAIL.
  
 4. SHEET A2.0 WAS REVISED TO ADDRESS ACCESSIBLITY
 REQUIREMENTS. SHEET 3.0 (INTERIOR DIMENSION SHEET) AND
 OTHER SHEETS HAVE NOT INCORPORATED THE CHANGES. PLEASE
 REVISE SHEET 3.0 AND ANY OTHER SHEETS IF NECESSARY TO
 AVOID FIELD ISSUES.
  
 4. PROVISO ITEM, FBC435.5.1.3, PLANS TO BE SUBMITTED TO
 DOH PRIOR TO CONSTRUCTION.
  
 5. PROVISO, ACCESSIBLE ROUTE, ACCESSIBLE PARKING, SITE
 WORK SHOWN UNDER PERMIT 08080616.
  
 6. PROVIDE THE FOLLOWING INFORMATION FOR THE RAMPS:
  
 A. SLOPE FBC11-4.8.2
 B. WIDTH FBC11-4.8.3
 C. HANDRAIL HEIGHT FBC 11-4.8.5
 D. EDGE PROTECTION HEIGHT FBC11-4.8.7
  
 PLEASE ADVISE AS TO WHERE THIS INFORMATION IS LOCATED
 (PERMIT #, SHEET NUMBER AND WPB STAMP DATE) OR SUBMIT
 DETAIL UNDER EITHER PERMIT (SITEWORK OR THIS RENOVATION
 PERMIT).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-05-11 Cont ID  
Sent By shill Date 2010-05-11 Time 12:17 Rev Time 0.00
Received By shill Date 2010-05-11 Time 12:17 Sent To  
Notes
2010-05-11 12:17:54****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1-2. ADDRESSED.
  
 3. PROVISO - SEPARATE ROOF PERMIT REQUIRED; NOAS 06
 0626.03, 06 0526.09 REVIEWED BY DOR
 NEED FOAM PRODUCT APPROVAL (CAN SUBMIT WITH ROOF PERMIT
 APPLICATION)
  
 WITH SUBMITTAL OF THE ROOF PERMIT, THE FOLLOWING
 INFORMATION IS REQUIRED:
 A. SELECT APPROVED ASSEMBLY; PER DOR, MOP DOWN SYSTEM
 WILL BE USED, SO NO ENHANCED FASTENING CALCULATIONS
 WILL BE REQUIRED.
 B. ON THE ROOF TILE PRODUCT APPROVAL, INDICATE METHOD
 OF ATTACHMENT TO SHOW COMPLIANCE WITH FBC1609. IF FOAM
 ADHESIVE IS USED, PROVIDE FOAM PRODUCT APPROVAL
 FAC9B72.
  
 4. FROM PREVIOUS LIST REGARDING EXPOSURE
 CLASSIFICATION:
  
 ARCHITECT'S AND ENGINEER'S RESPONSES REGARDING EXPOSURE
 B ARE NOTED. PLEASE SUBMIT A SITE PLAN SHOWING CURRENT
 CONDITIONS (MAY SUBMIT THIS ITEM VIA EMAIL, PRIOR TO
 RESUBMITTAL OR ISSUANCE). INCLUDE NEW BUILDINGS NOT
 SHOWN ON AERIALS, SIZE AND LOCATION OF NEW BUILDINGS ON
 ADJACENT LOTS, SIZE AND LOCATION OF PROPOSED NEW
 BUILDINGS, CONSTRUCTION SCHEDULE OF PROPOSED NEW
 BUILDINGS ALONG WITH ANY PERTINENT INFORMATION (PERMIT
 NUMBERS, DEVELOPMENT ORDERS, ETC.). INFORMATION
 PROVIDED SHOULD INCLUDE ALL CONDITIONS FOR 1500FT IN
 EACH DIRECTION, SEE FOLLOWING CODE REFERENCES:
  
 FBC1609.4.3, EXPOSURE C. EXPOSURE C SHALL APPLY FOR ALL
 CASES WHERE EXPOSURE B DOES NOT APPLY.
  
 FBC1609.4.3, EXPOSURE B. EXPOSURE B SHALL APPLY WHERE
 THE GROUND SURFACE ROUGHNESS CONDITION, AS DEFINED BY
 SURFACE ROUGHNESS B, PREVAILS IN THE UPWIND DIRECTION
 FOR A DISTANCE OF AT LEAST 2600 FEET, EXCEPTION REDUCES
 THIS REQUIREMENT TO 1500 FEET.
  
 FBC1609.4, EXPOSURE CATEGORY. FOR EACH WIND DIRECTION
 CONSIDERED, AN EXPOSURE CATEGORY THAT ADEQUATELY
 REFLECTS THE CHARACTERISTICS OF GROUND SURFACE
 IRREGULARITIES SHALL BE DETERMINED FOR THE SITE AT
 WHICH THE BUILDING OR STRUCTURE IS TO BE CONSTRUCTED.
 ACCOUNT SHALL BE TAKEN OF VARIATIONS IN GROUND SURFACE
 ROUGHNESS THAT ARISE FROM NATURAL TOPOGRAPHY AND
 VEGETATION AS WELL AS FROM CONSTRUCTED FEATURES. (ALSO
 SEE EXCEPTION).
  
 SEE ALSO FBC1609.4.1, WIND DIRECTIONS AND SECTORS. IN
 ORDER TO BE CONSIDERED EXPOSURE B, SHOW THAT THE
 SECTORS HAVE A SURFACE ROUGHNESS B. SEE FBC 1609.4.2,
 SURFACE ROUGHNESS B, URBAN AND SUBURBAN AREAS, WOODED
 AREAS OR OTHER TERRAIN WITH NUMEROUS CLOSELY SPACED
 OBSTRUCTIONS HAVING THE SIZE OF SINGLE FAMILY DWELLINGS
 OR LARGER. BASED ON AERIALS, WHICH ARE NOT CURRENT,
 THERE ARE MANY OPEN AREAS IN SEVERAL SECTORS. A CURRENT
 SITE PLAN WOULD BE REQUIRED FOR EVALUATION.
  
 REGARDING THE STRUCTURAL ENGINEER'S LETTER STATING THAT
 HE DESIGNED AN OFFICE BUILDING SEVERAL YEARS AGO AND
 USED EXPOSURE B IS NOTED. HOWEVER, PLEASE NOTE THAT THE
 CODE CHANGED MARCH 1, 2009, AND THE EXPOSURE
 CLASSIFICATIONS WERE CHANGED SIGNIFICANTLY. BUILDINGS
 APPLIED FOR PERMIT PRIOR TO MARCH 1, 2009 WOULD BE
 GOVERNED UNDER FBC2004.
  
 REGARDING ARCHITECT'S LETTER, PLEASE SEE ABOVE CODE
 REFERENCES, AND PROVIDE A SITE PLAN WHICH SHOWS 1500
 FEET OF CLOSELY SPACED OBSTRUCTIONS HAVING THE SIZE OF
 SINGLE FAMILY DWELLINGS OR LARGER AS THE AERIALS WHICH
 ARE AVAILABLE ARE NOT CURRENT.
  
 5-11. ADDRESSED.
  
 12. A2.0, PLAN STATES THAT SHIELDING IS NOT REQUIRED.
 SEE FBC435.5.1.1 AND FBC435.5.1.2.
  
 PLEASE EXPLAIN, THE REPORT STATES "IF THE OUTSIDE WALLS
 ARE CONSTRUCTED OF AT LEAST THREE INCHES OF CONCRETE
 BLOCK, NO ADDITIONAL SHIELDING IS USUALLY RECOMMENDED."
 THE PLAN SHOWS TWO WINDOWS IN THE OUTSIDE WALL, IS THIS
 CORRECT? ARE THE WINDOWS HIGHER THAN 7FEET? WOULDN'T
 SHIELDING BE REQUIRED AT THE OPENINGS IN THE BLOCK?
  
 13. PROVISO ITEM, FBC435.5.1.3, PLANS TO BE SUBMITTED
 TO DOH PRIOR TO CONSTRUCTION. PLEASE ADVISE AS TO WHEN
 THIS WILL BE COMPLETED, MUST BE PRIOR TO CONSTRUCTION.
  
 14. ADDRESSED.
  
 15. PROVISO, ACCESSIBLE ROUTE SHOWN UNDER PERMIT
 08080616.
  
 16. PROVIDE THE FOLLOWING INFORMATION FOR THE RAMPS:
  
 A. SLOPE FBC11-4.8.2
 B. WIDTH FBC11-4.8.3
 C. HANDRAIL HEIGHT FBC 11-4.8.5
 D. EDGE PROTECTION HEIGHT FBC11-4.8.7
  
 ARCHITECT'S RESPONSE THAT THIS IS PERMITTED UNDER
 08080616 IS NOTED; HOWEVER, I WAS UNABLE TO LOCATE A
 DETAIL SHOWING THIS INFORMATION. PLEASE ADVISE AS TO
 WHERE THIS INFORMATION IS LOCATED (SHEET NUMBER AND WPB
 DATE) OR SUBMIT DETAIL UNDER EITHER PERMIT (SITEWORK OR
 THIS RENOVATION PERMIT).
  
 17. PROVISO, ACCESSIBLE PARKING SHOWN UNDER PERMIT
 08080616.
  
 18. ADDRESSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-29 Cont ID  
Sent By shill Date 2010-03-29 Time 11:05 Rev Time 0.00
Received By shill Date 2010-03-23 Time 17:32 Sent To  
Notes
2010-03-29 11:05:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SHEET CS, INCLUDE LEVEL OF ALTERATION FBC EB 401.4.
  
 2. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD FBC*106.3.3.
  
 3. SEPARATE ROOF PERMIT REQUIRED. FOR ISSUANCE OF A
 ROOF PERMIT, THE FOLLOWING INFORMATION IS REQUIRED:
 A. SELECT APPROVED ASSEMBLY
 B. IF THE SELECTED APPROVED ASSEMBLY REQUIRES ENHANCED
 FASTENING, CALCULATIONS PREPARED BY AN ARCHITECT,
 ENGINEER, OR REGISTERED ROOF CONSULTANT REQUIRED (SEE
 GENERAL LIMITATION 7 ON LAST PAGE OF NOA)
 C. PRODUCT APPROVALS FOR ROOF TILE
 D. ON THE ROOF TILE PRODUCT APPROVAL, INDICATE METHOD
 OF ATTACHMENT TO SHOW COMPLIANCE WITH FBC1609. IF FOAM
 ADHESIVE IS USED, PROVIDE FOAM PRODUCT APPROVAL
 FAC9B72.
  
 4. SHEETS CS AND CN1.1 STATE THAT THIS PROJECT IS
 LOCATED IN EXPOSURE B. BASED ON AERIALS, THIS PROJECT
 IS LOCATED IN EXPOSURE C, SEE FBC1609.4.3 AND ASCE7 05.
 PLEASE REVISE.
  
 5. WIND DESIGN CRITERIA IS TO INCLUDE COMPONENT AND
 CLADDING PRESSURES, FBC1603.1.4.
  
 6. CN1.1 ROOF FRAMING NOTES 3 STATES THIS IS BUILDING
 IS ENCLOSED. THE CANOPY PORTION IS NOT ENCLOSED, PLEASE
 REVISE. FBC1609.
  
 7. ON THE SITE PLAN, PROVIDE THE DISTANCE OF PROPOSED
 IMPROVEMENT TO THE PROPERTY LINES FBC 106. ALSO INCLUDE
 OVERALL DIMENSIONS OF THE PROPOSED CANOPY.
  
 8. SHOW COMPLIANCE WITH FBC FIGURE 11-25, MANEUVERING
 CLEARANCE FOR DOORS. FOR INSTANCE, 18IN REQUIRED PULL
 SIDE FOR DOORS 12, 20, 34, DOOR BETWEEN CORR 8 AND
 WAITING 3. EXAM 32, EXAM 33, BACK ENTRANCE, DOOR AT PT,
 SHOW 12IN PUSH SIDE AS REQUIRED. CHECK ALL DOORS AND
 NOTE DIMENSION ON PLAN FOR DOORS WHICH DO NOT CLEARLY
 COMPLY.
  
 9. SHOW COMPLIANCE WITH FBC1503.4, ROOF DRAINAGE. IT
 APPEARS THAT A PORTION OF THE NEW CANOPY ROOF DRAINS
 ONTO THE EXISTING FLAT ROOF.
  
 10. SHOW PROVISIONS FOR OVERFLOW, FBC1503.4.3. THERE IS
 A NOTE ON THE PLAN STATING THAT THIS IS NOT REQUIRED
 DUE TO THE LIVE LOAD DESIGN OF THE ROOF DECK. THIS DOES
 NOT ADDRESS OTHER ISSUES RELATED TO STANDING WATER; FOR
 INSTANCE (ONE EXAMPLE), HAS THE ROOF ASSEMBLY BEEN
 DESIGNED TO HOLD STANDING WATER FOR A PROLONGED PERIOD
 OF TIME? HOW DOES STANDING WATER AFFECT THE MECHANICAL
 EQUIPMENT CURBS? THERE IS NO EXCEPTION IN THE FBC
 REGARDING OVERFLOW DRAINS OR SCUPPERS.
  
 11. SEE FBC435 AND SHOW COMPLIANCE WITH ALL
 REQUIREMENTS.
  
 12. A2.0, PLAN STATES THAT SHIELDING IS NOT REQUIRED.
 SEE FBC435.5.1.1 AND FBC435.5.1.2.
  
 13. SEE FBC435.5.1.3, PLANS TO BE SUBMITTED TO DOH
 PRIOR TO CONSTRUCTION, AND ADVISE AS TO WHEN THIS WILL
 BE DONE.
  
 14. STAFF TOILET, PROVIDE A DETAIL FOR THE SHOWER WHICH
 COMPLIES WITH FBC11-4.21.
  
 15. SHOW ACCESSIBLE ROUTE FROM THE PUBLIC WAY, AS1.0,
 FBC 11-4.1.1(1)(A), 11-4.1.2(1) AND (2).
  
 16. PROVIDE THE FOLLOWING INFORMATION FOR THE RAMPS:
  
 A. SLOPE FBC11-4.8.2
 B. WIDTH FBC11-4.8.3
 C. HANDRAIL HEIGHT FBC 11-4.8.5
 D. EDGE PROTECTION HEIGHT FBC11-4.8.7
  
 17. ACCESSIBLE PARKING IS TO BE DISPERSED, FBC11 4.6.2.
 LOCATION; IN BUILDINGS WITH MULTIPLE ACCESSIBLE
 ENTRANCES WITH ADJACENT PARKING, ACCESSIBLE PARKING
 SPACES SHALL BE DISPERSED AND LOCATED CLOSEST TO THE
 ACCESSIBLE ENTRANCES.
  
 18. FBC1210.2, WALLS TO HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE AT URINALS AND WATER CLOSETS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-05-06 Cont ID  
Sent By btrobaug Date 2010-05-06 Time 16:39 Rev Time 0.00
Received By btrobaug Date 2010-05-06 Time 16:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-04-14 Cont ID  
Sent By jleahy Date 2010-04-14 Time 07:12 Rev Time 0.00
Received By jleahy Date 2010-04-13 Time 07:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-05-17 Cont ID  
Sent By mawillia Date 2010-05-17 Time 16:11 Rev Time 0.00
Received By mawillia Date 2010-05-17 Time 15:20 Sent To  
Notes
2010-05-17 15:48:15*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS LS-1.0, A-2.0, CN-2.0, E-1.4,
 AND E-1.5 WERE STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-04-06 Cont ID  
Sent By mawillia Date 2010-04-06 Time 14:49 Rev Time 0.00
Received By mawillia Date 2010-04-06 Time 12:05 Sent To  
Notes
2010-04-06 14:49:50*****DENIED*****
  
  
 01. STRUCTURES UNDERGOOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 02. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION
 CODE BASED ON NFPA 1, UNIFORM FIRE CODE, 2006 EDITION
 AND NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 03. THE DEFINITION OF "COMMON PATH OF TRAVEL" AS LISTED
 ON SHEET LS-1.0 IS NOT CONSISTENT AS DEFINED IN NFPA 1
 AND/OR NFPA 101. PLEASE EXPLAIN.
  
 04. INCORRECT REFERENCES SUCH AS 36.2.5.2.1, 12.6.6 AND
 12..5.1.2 ARE LISTED ON THE LS-1.0 SHEET. BE ADVISED
 THAT CHAPTER 36 OF NFPA 101 IS FOR NEW MERCANTILE
 OCCUPANCIES AND CHAPTER 12 OF NFPA 101 IS FOR NEW
 ASSEMBLY OCCUPANCIES.
  
 05. ON SHEET LS-1.0, SOME DOORS (I.E. PATIENT TOIL. 2,
 STOR. 4, TOIL 4, PT. TOIL. 3) OPEN INTO THE MEANS OF
 EGRESS. BE ADVISED: DURING ITS SWING, ANY DOOR IN A
 MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF
 THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A
 PASSAGEWAY, OF A LANDING UNOBSTRUCTED AND SHALL NOT
 PROJECT MORE THAN 7 INCHES INTO THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING WHEN
 FULLY OPENED.
  
 06. ON THE APPROPIATE PLAN SHEET, DISPLAY/SHOW THE
 ADDRESS NUMBER ON THE EXTERIOR ELEVATION WHICH FRONTS
 OKEECHOBEE BOULEVARD.
  
 07. ON SHEET E-1.4, THERE IS A MATCHLINE REFERENCED TO
 SEE SHEET E-1.4 ; PLEASE EXPLAIN.
  
 08. THERE DOESN'T APPEAR TO BE ENOUGH EXIT LIGHTS AND
 EMERGENCY LIGHTS AS SHOWN IN THE LIGHTING PLAN. PLEASE
 SHOW.
  
 09. SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS AS. CLASS B, OR CLASS C.
  
 10. CLASSIFY THE CONTENTS OF THIS BUILDING AS LOW,
 ORDINARY, OR HIGH HAZARD.
  
 11. PROVIDE VERTICAL CLEARANCE FOR THE NEW ENTRANCE
 CANOPY. SUCH CLEARANCE, (IDEALLY 13' 6") SHALL NOT
 OBSTRUCT, IMPEDE, OR IMPAIR ACCESS BY FIRE APPARATUS.
  
 12. PROVIDE FLAME PROPOGATION PERFOMANCE CRITERIA
 AND/OR SPECIFICATIONS, AS PER NFPA 701, IF ANY
 TEXTILES/FABRICS/FILMS ARE USED IN THE NEW ENTRANCE
 CANOPY.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-04-28 Cont ID  
Sent By jwitmer Date 2010-04-28 Time 14:51 Rev Time 0.00
Received By jwitmer Date 2010-04-28 Time 14:47 Sent To  
Notes
2010-04-28 14:51:48INCOMING SENT TO C-2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-14 Cont ID  
Sent By btrobaug Date 2010-04-14 Time 10:56 Rev Time 0.00
Received By btrobaug Date 2010-03-22 Time 16:33 Sent To  
Notes
2010-03-23 16:33:53*****************EXPEDITED*******************
 C--28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-03-29 Cont ID  
Sent By shill Date 2010-03-29 Time 11:19 Rev Time 0.00
Received By shill Date 2010-03-29 Time 11:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-05-11 Cont ID  
Sent By rregueir Date 2010-05-11 Time 16:12 Rev Time 0.00
Received By rregueir Date 2010-05-11 Time 16:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-03-25 Cont ID  
Sent By rregueir Date 2010-03-25 Time 10:22 Rev Time 0.00
Received By rregueir Date 2010-03-25 Time 10:08 Sent To  
Notes
2010-03-25 10:22:44REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-1.4: FLEX DUCT CONNECTION DETAIL CALLS FOR
 TWO DRAWBANDS, WITH NO SEALER AT DUCT CONNECTION. SHOW
 HOW FLEX CONNECTION IS STO BE SEALED, IN ADDITION TO
 THE MECHANICAL ATTACHMENT PER FBC-M 603.1. ALSO, DO NOT
 INSTALL OUTER DRAWBAND ON INSULATION JACKET AS THAT
 WILL COMPRESS THE INSULATION PER FBC-M 604.7.
  
 2. THIS IS, AT A MINIMUM, A LEVEL 2 ALTERATION PER
 FBC-EB SECTION 202. SHOW VENTILATION CALCULATIONS FOR
 ALL RECONFIGURED SPACES IN ACCORDANCE WITH FBC-EB
 709.1. EXAMPLE: STAFF TOILET ROOM HAS A NEW SHOWER.
 WHAT IS THE EXHAUST RATE PROVIDED FOR THIS ROOM. SHOW
 COMPLIANCE WITH FBC-M 403.3 OR 403.4.
  
 3. PAGE M-1.4 SHOWS A 100% OUTSIDE AIR PLAN. HOWEVER,
 THE UNIT SHOWN ON THE SCHEDULE IS RATED AT 6000 CFM
 WITH 2500 CFM OF OUTSIDE AIR. PLEASE CLARIFY.
  
 4. PAGE M-1.4. SOME DROPS ON THE 100% OUTSIDE AIR PLAN
 ARE MISSING CFM DESIGNATION. PROVIDE MISSING
 INFORMATION IN ACCORDANCE WITH FBC-M 603.1.
  
 5. PAGE M-1.3: SEVERAL DUCTS ON THIS PLAN ARE MISSING
 SIZES. PROVIDE ALL MISSING INFORMATION. ALSO, WAITING
 ROOM #3 SHOWS A FLEX DUCT WITH NO SIZE AND NO GRILL OR
 DIFFUSER. PLEASE CLARIFY.
  
 6. PLAN DOES NOT SHOW ANY NEW OR EXISTING DUCT SMOKE
 DETECTORS. SHOW COMPLIANCE WITH FBC-M 606.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-05-13 Cont ID  
Sent By lwagner Date 2010-05-13 Time 15:11 Rev Time 0.00
Received By lwagner Date 2010-05-12 Time 14:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-04-05 Cont ID  
Sent By lwagner Date 2010-04-05 Time 10:34 Rev Time 0.00
Received By lwagner Date 2010-04-05 Time 09:39 Sent To  
Notes
2010-04-05 10:31:09FBC 2007
 FBC PLUMBING 2007
  
 1ST REVIEW
 *****CORRECTIONS*****
  
 1. LOUNGE SINK SHALL COMPLY WITH FBC CHAPTER 11
 ACCESSIBILITY CODE 11-4.24.1
 2. SANITARY ISO IS MISSING PIPE SIZES, STACK VENTS, AND
 CLEANOUTS.
 3. A WATER PIPE ISO IS REQUIRED 106.3.5.1.3
 3. WASHING MACHINE REQUIRES A VENT-901.2.1.
 A CLEANOUT AT 48" AFF 708.3.4.
 A 3" STACK IS REQUIRED- 406.3
 4. SINKS ARE NOT PERMITTED ON THE WET VENT FOR TOILET
 ROOM #1, AND #3 / #4. 909.1- ONLY THE FIXTURES WITHIN
 THE BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2010-03-24 Cont ID  
Sent By eschneid Date 2010-03-24 Time 15:58 Rev Time 0.25
Received By eschneid Date 2010-03-24 Time 15:58 Sent To  
Notes
2010-03-24 15:59:27SIGNS REQUIRE SEPARATE PERMIT.