Plan Review Details - Permit 10030553
Plan Review Stops For Permit 10030553
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-04-14 Cont ID  
Sent By shill Date 2010-04-14 Time 14:15 Rev Time 0.00
Received By shill Date 2010-04-14 Time 14:15 Sent To  
Notes
2010-04-14 14:17:28ISSUED AT CONTRACTOR'S RISK
  
 PROVISO : RESPONSE FROM ARCHITECT VIA EMAIL, INSPECTOR
 TO CONFIRM IN FIELD:
  
  
 REGARDING THE APPLICATION FOR A RAMP AT THE EXISTING
 SIDE ENTRANCE TO TEMPLE BETH EL (PERMIT NO. 10030553, I
 HAVE THE FOLLOWING COMMENT:
  
 THE DOOR WIDTH ADJACENT TO THE PROPOSED RAMP IS 3'-6".
 2 ADDITIONAL DOORS(A MAIN ENTRY/EGRESS FOR THE SAME
 AREA) WHICH ARE 4' WIDE EACH(A TOTAL EGRESS WIDTH OF
 8') ARE LOCATED 12' AWAY.
  
 THE PROPOSED RAMP IS 5' WIDE, WHICH DOES NOT MAKE THE
 EXIT NARROWER.
  
 BOTH THESE EXITS SERVE ONLY A SMALL AREA CONSISTING OF
 3 SMALL OFFICES, AND TWO REST ROOMS, AS WELL A
 CONFERENCE ROOM.
  
 THE ASSEMBLY HALL NEXT TO THIS AREA HAS ITS OWN DIRECT
 EXIST, INCLUDING 3-6' WIDE DOORS WITH PANIC HARDWARE
 AND WOULD NOT BE COUNTED IN THE SECONDARY OFFICE EXIT
 AT WHICH THE PROPOSED RAMP IS TO BE INSTALLED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-06 Cont ID  
Sent By shill Date 2010-04-06 Time 14:39 Rev Time 0.00
Received By shill Date 2010-04-06 Time 14:39 Sent To Z
Notes
2010-04-06 14:40:59****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE FBC1005.2 AND REVISE PLAN TO SHOW COMPLIANCE
 (CANNOT REDUCE EGRESS WIDTH TO LESS THAN HALF).
  
 2. FBC11-4.8.4(2), SHOW LANDING SIZE AT TOP AND BOTTOM.
  
 3. FBC11-4.8.5, PROVIDE A HANDRAIL DETAIL AND SHOW
 HANDRAILS ON THE PLAN WITH ALL REQUIRED DIMENSIONS.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-07 Cont ID  
Sent By shill Date 2010-04-07 Time 11:42 Rev Time 0.00
Received By shill Date 2010-03-22 Time 10:23 Sent To  
Notes
2010-03-24 10:24:14UNDER 5 K, BLDG

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2010-03-22 15:21:15ANGELA VAUGHN-JONES LOOKED AT PLAN & SAID NO ZONING
 REVIEW APPLICABLE