| Plan Review Stops For Permit 10030547 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2010-04-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-04-07 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-04-07 |
Time |
10:08 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-03-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-03-22 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-03-22 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2010-03-22 14:23:08 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- NEED TO PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC. R301 | | | OF 2007 FLORIDA RESIDENTIAL CODE. SEE LIMITATION 5.6 OF | | | FLORIDA PRODUCT APPROVAL FL1654-R5 SUBMITTED. | | | | | | 2- DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS | | | TO HAVE INTO CONSIDERATION THAT THIS BUILDING IS | | | LOCATED ON EXPOSURE "C". SEC. R301.2.1.4.3 OF 2009 | | | REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE. | | | | | | 3- OWES $51.67 FOR UPDATED VALUATION. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-03-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-03-22 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-03-22 |
Time |
14:10 |
Sent To |
|
|
| Notes |
|
|
|