| 2010-03-31 08:47:06 | BUILDING PLAN REVIEW |
| | PERMIT: 10030543 |
| | ADD: 5013 @ GARDEN AVE. |
| | CONT: C. R. DUNN |
| | TEL: (561)585-2155 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | |
| | 1) SHEET E-20 LIGHT POLE NOTES: CONTRACTOR TO SUBMIT |
| | POLE WIND LOADING CALCULATIONS FOR THE POLE AND |
| | EMBEDMENT SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | STRUCTURAL ENGINEER ILLUSTRATING THAT THE PROPOSED |
| | INSTALLATION SHALL MEET THE GIVEN LOADING REQUIREMENTS. |
| | |
| | 2) ENGINEER OF RECORD HASN'T DECLARED WHAT THE EXPOSURE |
| | IS FOR THIS LOCATION, WILL GREATLY EFFECT THE WIND LOAD |
| | CALCULATIONS. 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| | BUILDING: |
| | 2.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | |
| | 2.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | |
| | 2.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |