| Plan Review Stops For Permit 10030519 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2010-04-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-04-05 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-04-05 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2010-04-05 13:11:48 | ****PROVISOS**** | | | ****PROVIDE AT INSPECTION**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE | | | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER | | | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. | | | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET | | | AT | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | | INSTALLATION.PDF | | | | | | 2. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL | | | BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE | | | INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609, | | | FBC*106. | | | | | | 3. ON THE FLOOR PLAN, SHOW THE EMERGENCY MEANS OF | | | ESCAPE, FBC R310.4. | | | | | | 4. DESIGN PRESSURES ARE TO REFLECT EXPOSURE C | | | CONDITIONS. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-04-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-04-05 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-03-23 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2010-03-24 16:04:38 | UNDER 5 K, BLDG |
|
|
|