Plan Review Details - Permit 10030515
Plan Review Stops For Permit 10030515
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-07-08 Cont ID  
Sent By shill Date 2010-07-08 Time 11:49 Rev Time 0.00
Received By shill Date 2010-07-08 Time 11:49 Sent To Z
Notes
2010-07-08 11:51:54****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE SHED PROPOSED IS DESIGNED FOR EXPOSURE B, BUT
 YOUR PARCEL IS LOCATED IN EXPOSURE C (ADJACENT TO
 CARDINAL NEWMAN PARKING LOT AND SPORTS FIELDS), AND
 PLEASE ALSO NOTE THAT IMPORTANCE FACTOR HAS ALREADY
 BEEN REDUCED TO .77. SEE FBC R301.2.1.4, REVISE PLAN TO
 EXPOSURE C WIND DESIGN.
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE DOOR, FAC9B72.
  
 FROM PREVIOUS LIST:
  
 3. CONTRACTOR HAS REQUESTED AN ELECTRIC PERMIT (SEE
 APPLICATION, SIGNED ON "ELECTRICAL CONTRACTOR" LINE).
 NO ELECTRIC WORK SHOWN.
  
 4. ROOF PERMIT REQUIRED.
  
 5. SITE PLAN IS TO INCLUDE PROPOSED DIMENSIONS TO
 PROPERTY LINES AND STRUCTURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-21 Cont ID  
Sent By shill Date 2010-04-21 Time 08:31 Rev Time 0.00
Received By shill Date 2010-04-21 Time 08:31 Sent To  
Notes
2010-04-21 08:51:09****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLANS ARE TO BE ARCHITECTURAL QUALITY, TO SCALE,
 FBC106. PLANS SUBMITTED DO NOT INCLUDE ENOUGH
 INFORMATION TO DETERMINE CODE COMPLIANCE. IT IS UNCLEAR
 HOW THIS STRUCTURE HAS BEEN DESIGNED TO COMPLY WITH
 REQUIRED LOADS FBCR301.1, SEE FBC R301.2.1.1.
  
 FOR INSTANCE: PLAN STATES "8" DIA CONC PAD", NO
 REINFORCEMENT, NO ANCHORS TO TIE THE FOUNDATION TO THE
 STRUCTURE.
 FOUNDATION PLAN SHOWS "CONC PAD INTO GROUND" WITH NO
 REINFORCEMENT, NO SIZE.\
 HOW HAS IT BEEN DETERMINED THAT THE ROUND FOOTINGS WILL
 BE ADEQUATE TO SUPPORT AND HOLD DOWN THIS STRUCTURE?
 THE WALL SECTION DOES NOT INCLUDE ALL CONNECTORS TO
 SHOW HOW PROPOSED CONSTRUCTION WILL BE STRUCTURALLY
 CONTINUOUS.
 PLANS STATE THERE WILL BE "HAND FRAMED WOOD TRUSSES,"
 HOW WILL THIS BE ACCOMPLISHED? NO DETAILS PROVIDED.
 STUCCO INSTALLATION DOES NOT COMPLY WITH FBC R703.6.3,
 BOND BREAK. NO MINIMUM STUCCO THICKNESS SPECIFIED.
 STATE WIND DESIGN CRITERIA ON THE PLAN - DESIGN MUST
 COMPLY WITH 140MPH EXPOSURE C.
 WALL FRAMING DETAIL FOR OPENING (DOOR)
  
 PLEASE BE ADVISED THAT CONSTRUCTION METHODS WHICH DO
 NOT COMPLY WITH A PRESCRIPTIVE DESIGN METHOD MAY
 REQUIRE CALCULATIONS.
  
 2. CONTRACTOR HAS REQUESTED AN ELECTRIC PERMIT (SEE
 APPLICATION, SIGNED ON "ELECTRICAL CONTRACTOR" LINE).
 NO ELECTRIC WORK SHOWN.
  
 3. PLAN STATES "HAND FRAME" FOR THE DOOR, NO DETAILS
 PROVIDED. CONTRACTOR WILL BE REQUIRED TO DEMONSTRATE
 THAT THE DOOR MEETS THE WIND REQUIREMENTS, BUT THERE IS
 NO PRESCRIPTIVE CODE FOR DOOR CONSTRUCTION. THIS IS
 USUALLY DONE THROUGH A PRODUCT APPROVAL.
  
 4. ROOF PERMIT REQUIRED.
  
 5. SITE PLAN IS TO INCLUDE PROPOSED DIMENSIONS TO
 PROPERTY LINES AND STRUCTURE.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-23 Cont ID  
Sent By vmolina Date 2010-06-23 Time 10:14 Rev Time 0.00
Received By vmolina Date 2010-06-23 Time 10:14 Sent To  
Notes
2010-06-23 10:15:09GAVE TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-21 Cont ID  
Sent By shill Date 2010-04-21 Time 08:54 Rev Time 0.00
Received By shill Date 2010-03-18 Time 14:10 Sent To  
Notes
2010-03-22 14:13:28IN ZONING BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2010-04-06 Cont ID  
Sent By astelly Date 2010-04-06 Time 10:07 Rev Time 0.00
Received By astelly Date 2010-04-06 Time 10:06 Sent To B
Notes
2010-04-06 10:11:32AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
  
 SIDE AND REAR SETBACKS MUST BE SHOWN ON PLANS. THE
 SETBACKS ARE AS FOLLOWS FOR ACCESSORY STRUCTURES IN SF7
 ZONING DISTRICTS:
  
 ACCESSORY STRUCTURES IN RESIDENTIAL DISTRICTS.
 (1)
 MAXIMUM SQUARE FOOTAGE. THE TOTAL FLOOR AREA OF ALL
 ROOFED ACCESSORY BUILDINGS ON A PROPERTY SHALL NOT
 EXCEED 75 PERCENT OF THE GROSS FLOOR AREA OF THE
 PRIMARY STRUCTURE WITH A MAXIMUM FLOOR AREA OF 1,000
 SQUARE FEET.
 (2)
 SETBACKS.
 FRONT: 25 FEET.
  
 SIDE: FIVE FEET FROM THE LOT LINES.
  
 CORNER: SAME AS REQUIRED FOR PRINCIPAL STRUCTURE.
  
 REAR: FIVE FEET MINIMUM OR 15 FEET FROM THE CENTERLINE
 OF THE ALLEY TO A GARAGE DOOR FACING THE ALLEY,
 WHICHEVER IS GREATER.
  
 (3)
 BUILDING SEPARATION. ACCESSORY STRUCTURES COVERED WITH
 A SOLID ROOF SHALL BE LOCATED NO CLOSER THAN SIX FEET
 TO THE PRINCIPAL STRUCTURE. ACCESSORY STRUCTURES LESS
 THAN SIX FEET FROM THE PRIMARY STRUCTURE MUST MEET THE
 PRIMARY STRUCTURE SETBACKS. ACCESSORY STRUCTURES MAY BE
 CONNECTED TO THE PRINCIPAL STRUCTURE WITH A CANVAS
 COVERED OPEN BREEZEWAY.
 (4)
 HEIGHT. ACCESSORY STRUCTURES SHALL NOT EXCEED 25 FEET.
  