Plan Review Details - Permit 10030499
Plan Review Stops For Permit 10030499
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-03-22 Cont ID  
Sent By jgomez Date 2010-03-22 Time 16:23 Rev Time 0.00
Received By jgomez Date 2010-03-22 Time 16:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-18 Cont ID  
Sent By jgomez Date 2010-03-18 Time 14:38 Rev Time 0.00
Received By jgomez Date 2010-03-18 Time 13:53 Sent To PC
Notes
2010-03-18 14:39:39REROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ACCORDING TO THE MIAMI-DADE COUNTY WEBSITE MODIFIED
 BITUMEN NOA 07-0111.03 FILE WAS SUPERSEDED. NEED TO
 PROVIDE CURRENT NOA.
  
 2- CLEARLY MARK WHICH APPROVED ASSEMBLY AND BASE SHEET
 FASTENING OPTION IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609 FBC
 2007.
  
 3- PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. IF RAS 117
 CALCULATIONS NEED TO BE SIGNED AND SEALED, THEN PROVIDE
 SIGNED AND SEALED CALCULATIONS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-18 Cont ID  
Sent By jgomez Date 2010-03-18 Time 14:58 Rev Time 0.00
Received By jgomez Date 2010-03-18 Time 13:54 Sent To  
Notes
***NONE***