Plan Review Details - Permit 10030370
Plan Review Stops For Permit 10030370
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-16 Cont ID  
Sent By shill Date 2010-03-16 Time 16:01 Rev Time 0.00
Received By shill Date 2010-03-16 Time 16:01 Sent To  
Notes
2010-03-16 16:06:25****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE EXPLAIN HOW YOU HAVE DETERMINED DESIGN
 PRESSURES. SEE FBC TABLE R301.2(2) AND (3). 20SF, ZONE
 5, -44PSF WITH A COEFFICIENT OF 1.29 (BUILDING 20',
 EXPOSURE C) MINIMUM PRESSURES IS -56.76. PLEASE REVISE
 DESIGN PRESSURES AND ANCHORING SPECIFICATIONS AS
 NECESSARY.
  