| 2010-03-30 19:43:58 | PLANNING AND ZONING: *** FAILED **** |
| | |
| | 1. RESPOND TO COMMENTS IN WRITING. RE-SUBMITTAL MAY BE |
| | SUBJECT TO ADDITIONAL COMMENTS. |
| | |
| | 2. THE PERMIT'S PROJECT DETAIL INDICATES THAT NEW |
| | EQUIPMENT CABINET TO BE INSTALLED ON TOP O NEW BATTERY |
| | CABINET. HOWEVER THE SHEETS SUBMITTED DO NOT SHOW ANY |
| | NEW EQUIPMENT. PROVIDE LOCATION FOR NEW EQUIPMENT. |
| | ALSO, INDICATE TOTAL VERTICAL DIMENSION HIGHT IN |
| | RELATION WITH THE PLATFORM HIGHT FOR ALL EQUIPMENT, |
| | INCLUDING THE EXISTING. SHOW PROFILE OF THE EQUIPMENT, |
| | ONCE ALL EQUIPMENT IS MOUNTED TO THE RACK (INCLUDE |
| | DIMENSION FROM THE ROOF LEVEL TO THE TOP OF THE |
| | CABINET).. |
| | |
| | 3. PURSUANT TO SECTION 94-143 OF THE ZONING CODE, THE |
| | PROPERTY IS WITHIN AN OFFICE COMMERCIAL ("OC") ZONING |
| | DISTRICT , THE MAXIMUM BUILDING HEIGHT ADJACENT TO A |
| | RESIDENTIAL ZONING DISTRICT IS 30 FEET WITH EXCEPTIONS |
| | BASED ON ADDITIONAL SETBACKS AS PROVIDED IN SUBSECTION |
| | (6)B., PROVIDE A SITE PLAN ALONG WITH THIS PERMIT TO |
| | SHOW THE LOCATION OF BUILDING AND PROPERTY SETBACKS. |
| | PURSUANT TO SECTION 94-306, HEIGHT OF MECHANICAL |
| | EQUIPMENT MAY EXCEED DISTRICT HEIGHT REQUIREMENTS BY |
| | TEN (10) PERCENT. PROVIDE ELEVATIONS WITH A LINE OF |
| | SIGHT FROM THE GROUND LEVEL FROM ALL SIDES OF THE |
| | BUILDING DEPICTING PROPOSED CABINET (EQUIPMENT). IS THE |
| | "EXISTING WALL," SURROUNDING THE EQUIPMENT SCREENING |
| | FROM VIEW ALL THE MECHANICAL EQUIPMENT, INCLUDING THE |
| | PROPOSED WORK? |
| | |
| | 4. NOTE THAT REPLACEMENT OR ADDITION OF ANTENNAS |
| | REQUIRES A APPROVAL OF A WIRELESS COMMUNICATION |
| | FACILITY DEVELOPMENT APPLICATION AND BUILDING PERMIT |
| | WITH THE PLANNING AND ZONING DEPARTMENT. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME. |
| | |
| | LINDA MIA FRANCO |
| | SENIOR PLANNER |
| | PLANNING AND ZONING DEPARTMENT |
| | TEL: 822-1443 |
| | EMAIL: [email protected] |
| | |
| | |