Plan Review Details - Permit 10030273
Plan Review Stops For Permit 10030273
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-03-24 Cont ID  
Sent By mawillia Date 2010-03-24 Time 15:33 Rev Time 0.00
Received By mawillia Date 2010-03-24 Time 14:39 Sent To  
Notes
2010-03-24 14:53:12*****PROVISO*****
  
 THE FIRE ALARM PLAN (FS-1, FS-5, FS-6) WAS FIRE-STAMPED
 ACCORDINGLY; READY FOR PERMIT ISSUANCE.
  
 PLEASE BE ADVISED THAT THE FOLLOWING REVISIONS ARE
 REQIRED PRIOR TO A FIRE ALARM FINAL (CODE #302)
 INSPECTION:
 1. SHOW THE NECESSARY FIRE ALARM DEVICES IN THE WOMEN'S
 BATH / WOMEN'S LOCKER AREA. AMEND APPROPIATE SHEET(S)
 AS NECESSARY.
 2. AS PER LOCAL CODE, DUCT SMOKE DETECTORS SHALL
 INITTIATE A GENERAL FIRE ALARM. MAKE NECESSARY
 ADJUSTMENTS TO THE FIRE ALARM MATRIX AND SEQUENCE OF
 OPERATIONS.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
 2.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-03-24 Time 14:40 Rev Time 0.00
Received By shill Date 2010-03-16 Time 09:20 Sent To  
Notes
2010-03-16 09:20:43TO FIRE