| Plan Review Stops For Permit 10030273 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2010-03-24 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2010-03-24 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2010-03-24 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2010-03-24 14:53:12 | *****PROVISO***** | | | | | | THE FIRE ALARM PLAN (FS-1, FS-5, FS-6) WAS FIRE-STAMPED | | | ACCORDINGLY; READY FOR PERMIT ISSUANCE. | | | | | | PLEASE BE ADVISED THAT THE FOLLOWING REVISIONS ARE | | | REQIRED PRIOR TO A FIRE ALARM FINAL (CODE #302) | | | INSPECTION: | | | 1. SHOW THE NECESSARY FIRE ALARM DEVICES IN THE WOMEN'S | | | BATH / WOMEN'S LOCKER AREA. AMEND APPROPIATE SHEET(S) | | | AS NECESSARY. | | | 2. AS PER LOCAL CODE, DUCT SMOKE DETECTORS SHALL | | | INITTIATE A GENERAL FIRE ALARM. MAKE NECESSARY | | | ADJUSTMENTS TO THE FIRE ALARM MATRIX AND SEQUENCE OF | | | OPERATIONS. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | 2. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2010-03-24 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-03-16 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2010-03-16 09:20:43 | TO FIRE |
|
|
|