Plan Review Details - Permit 10030264
Plan Review Stops For Permit 10030264
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-05-19 Cont ID  
Sent By jwitmer Date 2010-05-19 Time 14:19 Rev Time 0.77
Received By jwitmer Date 2010-05-19 Time 14:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-24 Cont ID  
Sent By jwitmer Date 2010-03-24 Time 11:31 Rev Time 1.33
Received By jwitmer Date 2010-03-24 Time 11:31 Sent To  
Notes
2010-03-24 12:56:36BUILDING PLAN REVIEW
 PERMIT: 10030264
 ADD: 1641 WORTHINGTON # 130
 CONT: DPR CONSTRUCTION
 TEL: (561)632-4028
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 GS&P
 GLIDDEN SPINA & PARTNERS
 PHONE: 561-684-5594
  
 PROJECT DOX
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET 1 INDICATES A NEW EXTERIOR DOOR, RULE 9B-72
 AND EXTERIOR METAL DOORS:EXTERIOR DOOR ASSEMBLIES NOT
 COVERED BY SECTION 1715.4.2 OR SECTION 1714.5.3.1 SHALL
 BE TESTED FOR STRUCTURAL INTEGRITY IN ACCORDANCE WITH
 ASTM E 330 PROCEDURE A, AT A LOAD OF 1.5 TIMES THE
 REQUIRED DESIGN PRESSURE LOAD. THE LOAD SHALL BE
 SUSTAINED FOR 10 SECONDS WITH NO PERMANENT DEFORMATION
 OF ANY MAIN FRAME OR PANEL MEMBER IN EXCESS OF 0.4
 PERCENT OF ITS SPAN AFTER THE LOAD IS REMOVED.
 HIGH-VELOCITY HURRICANE ZONES SHALL COMPLY WITH TAS
 202. AFTER EACH SPECIFIED LOADING, THERE SHALL BE NO
 GLASS BREAKAGE, PERMANENT DAMAGE TO FASTENERS, HARDWARE
 PARTS, OR ANY OTHER DAMAGE WHICH CAUSES THE DOOR TO BE
 INOPERABLE.
 THE MINIMUM TEST SIZES AND MINIMUM DESIGN PRESSURES
 SHALL BE AS INDICATED IN TABLE 1714.5.3 .
  
 2) 1609.6.2 WIND DESIGN PROCEDURES
 2.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 2.5) POSITIVE AND NEGATIVE PRESSURES FOR NEW OPENING
  
 2.6) HEIGHT OF BUILDING IN FEET.
  
 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 3.1PAIR OF EXTERIOR METAL DOORS
 3.2 MULLION
 3.3 TRANSOM ABOVE.
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) FLOOR PLAN INDICATES TTHE EXISTING EXIT PAASAGEWAY
 AS TWO HOUR IN DRAWING FORM BUT THE WRITTEN NOTE# 3
 INDICATES THIS WALL TO BE A 1 HR RATED WALL. A FOR
 STORY EXIXT ENCLOSURE WILL QUIRE A 2HR FIRE
 RATING.FBC-B 1020.1/ 1021.3.
  
 6) PLEASE PROVIDE ADDITIONAL INFORMATION FOR ROOM 108
 MRSE THIS ROOM APPEARS TO BE A IT ROOM, IF A TRUE IT
 ROOM THE NEC MAY REQUIRE A 1 HOUR FIRE RATING DEPENDING
 ON WIRING METHODS. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 7) SHEET A3 INDICATES THE USE OF TATE ACCESS FLOORS.
 THE AREA OF CONCERN IS THE FLOOR LOAD ON THE TATE FLOOR
 SYSTEM WITHIN THE COMPUTER ROOM.FBC-B TABLE 1607.1
 COMPUTER ROOMS SHALL BE DESISGNED FOR HEAVIER LOADS
 BASED ON THE ANTICIPATED OCCUPANCY. WILL THERE BE
 CONCENTRATED LOADS ON PANELS THAT MAY CREATE A FAILURE?
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-04-21 Cont ID  
Sent By dwise Date 2010-04-21 Time 21:14 Rev Time 0.00
Received By dwise Date 2010-04-21 Time 21:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-03-29 Cont ID  
Sent By dwise Date 2010-03-29 Time 20:16 Rev Time 0.00
Received By dwise Date 2010-03-29 Time 20:16 Sent To  
Notes
2010-03-29 20:22:18PLEASE PROVIDE SPECIFICATIONS AND INFORMATION ON THE
 PROPOSED PANEL HEATERS, INCLUDING EQUIPMENT
 SPECIFICATIONS, CONTROLS AND TIMING DEVICES REFERENCED
 ON THE PLANS. PLEASE PROVIDE DOCUMENTATION TO
 DEMONSTRATE THAT THESE DEVICES WERE INCLUDED IN THE
 BASE BUILDING ENERGY DESIGN.
  
 PLEASE PROVIDE CIRCUITING INFORMATION ON THE COUNTERTOP
 RECEPTACLES PROPOSED IN THE EMPLOYEE LOUNGE. PLEASE
 COORDINATE THIS INFORMATION WITH THE PANEL SCHEDULES.
  
 PLEASE REVIEW THE INTENDED USE OF THE COUNTERTOP
 RECEPTACLES PROPOSED IN THE EMPLOYEE LOUNGE. IF THE
 CUSTOMER INTENDS TO UTILIZE THESE FOR EITHER A
 MICROWAVE OVEN OR COFFEE MACHINE SEPERATE DEDICATED
 CIRCUITS MAY BE INDICATED DEPENDING ON THE EQUIPMENT
 PROPOSED TO PREVENT OVERLOADING THE PROPOSED WIRING.
  
 PLEASE FEEL FREE TO CONTACT ME DIRECTLY IF YOU HAVE ANY
 QUESTIONS OR CONCERNS ABOUT THESE ISSUES AT
 561-805-6650 DURING NORMAL BUSINESS HOURS. I MAY ALSO
 BE REACHED BY EMAIL AT [email protected].
  
 THANK YOU,
  
 DOUG WISE

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-05-03 Cont ID  
Sent By mcarsill Date 2010-05-03 Time 13:11 Rev Time 0.00
Received By mcarsill Date 2010-05-03 Time 13:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-19 Cont ID  
Sent By mcarsill Date 2010-03-19 Time 15:48 Rev Time 0.00
Received By mcarsill Date 2010-03-19 Time 15:33 Sent To  
Notes
2010-03-19 15:48:031641 WORTHINGTON ROAD, SUITE 130
 PERMIT NUMBER 10030264
  
 1. TACTILE SIGNAGE REQUIRED AT EXIT DOOR.
  
 2. ON PAGE A1.0 DASH SYMBOLS SHOW TWO HOUR RATINGS BUT
 NOTE # 3 SHOWS A ONE HOUR RATING.
  
 3. CARD READERS SHALL NOT INTERFERE WITH ANY EXITING.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 PRE-ACTION FIRE SPRINKLER SYSTEM AND THE FM 200
 SUPPRESSION SYSTEM.
  
 5. MORE INFORMATION NEEDED REGARDING THE MRSE ROOM. IS
 THE ROOM CONSIDERED A COMPUTER ROOM. NFPA 75, IS THE
 STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY
 EQUIPMENT. SEVERAL CODE REQUIREMENTS EXIST WITHIN THIS
 STANDARD. PLEASE REVIEW THE SCOPE OF THE STANDARD IN
 SECTION 1.1.
  
 6. IT APPEARS THAT ONLY ONE FIRE EXTINGUISHER EXISTS.
 TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75
 FEET OF TRAVEL DISTANCE.
  
 7. NEW FIRE DAMPERS ARE TO BE DROP TESTED TO ENSURE
 PROPER OPERATION.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-30 Cont ID  
Sent By rregueir Date 2010-03-17 Time 15:45 Rev Time 0.00
Received By rregueir Date 2010-03-17 Time 15:45 Sent To  
Notes
2010-04-21 15:47:34DIGITAL PLAN REVIEW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-04-21 Cont ID  
Sent By rregueir Date 2010-04-21 Time 15:44 Rev Time 0.00
Received By rregueir Date 2010-04-21 Time 15:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-03-23 Cont ID  
Sent By rregueir Date 2010-03-23 Time 11:18 Rev Time 0.00
Received By rregueir Date 2010-03-23 Time 11:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-03-30 Cont ID  
Sent By lwagner Date 2010-03-30 Time 14:23 Rev Time 0.00
Received By lwagner Date 2010-03-30 Time 14:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2010-07-01 Cont ID  
Sent By jroach Date 2010-07-01 Time 14:19 Rev Time 0.00
Received By jroach Date 2010-07-01 Time 14:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2010-04-21 Cont ID  
Sent By jroach Date 2010-04-21 Time 09:41 Rev Time 0.00
Received By jroach Date 2010-04-21 Time 09:41 Sent To  
Notes
2010-04-21 11:21:52ZONING PLAN REVIEW
  
 PERMIT NO.: 10030264
 ADDRESS: 1640 WORTHINGTON ROAD
 CONTRACTOR/CONTACT: DPR CONSTRUCTION
 TELEPHONE NO.: 561.632.4028
 SCOPE OF REVIEW: INTERIOR BUILD-OUT
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 THE FOLLOWING IS A REPEAT COMMENTS....ADDITIONAL
 INFORMATION HAS BEEN PROVIDED IN ALL CAPS...
  
 1) A MINOR AMENDMENT TO THE CENTREPARK WEST COMMERCIAL
 PLANNED DEVELOPMENT (CPD) SHALL BE SUBMITTED TO AND
 APPROVED BY THE PLANNING AND ZONING DEPARTMENT FOR
 EXTERIOR ALTERATIONS TO THE SITE. ALL OUTDOOR
 MECHANICAL EQUIPMENT SHALL BE SCREENED FROM VIEW. WHILE
 A DRAFT COPY OF THE PROPOSED LANDSCAPE REVISIONS WAS
 PRESENTED TO ME FOR CURSORY REVIEW, NO APPLICATION OR
 PLANS HAVE BEEN SUBMITTED TO THE PLANNING AND ZONING
 DEPARTMENT FOR FINAL APPROVAL OF A MINOR AMENDMENT TO
 THE CPD. PLEASE SUBMIT A COMPLETE APPLICATION WITH
 REVISED PLANS AS SOON AS POSSIBLE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-03-29 Cont ID  
Sent By jroach Date 2010-03-29 Time 11:17 Rev Time 0.00
Received By jroach Date 2010-03-29 Time 11:17 Sent To  
Notes
2010-03-29 11:19:40ZONING PLAN REVIEW
  
 PERMIT NO.: 10030264
 ADDRESS: 1640 WORTHINGTON ROAD
 CONTRACTOR/CONTACT: DPR CONSTRUCTION
 TELEPHONE NO.: 561.632.4028
 SCOPE OF REVIEW: INTERIOR BUILD-OUT
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) A MINOR AMENDMENT TO THE CENTREPARK WEST COMMERCIAL
 PLANNED DEVELOPMENT (CPD) SHALL BE SUBMITTED TO AND
 APPROVED BY THE PLANNING AND ZONING DEPARTMENT FOR
 EXTERIOR ALTERATIONS TO THE SITE. ALL OUTDOOR
 MECHANICAL EQUIPMENT SHALL BE SCREENED FROM VIEW.
  
 2) ELEVATION SHOWN DOES NOT MATCH THAT WHICH WAS
 APPROVED THROUGH A PREVIOUS MINOR AMENDMENT. IF
 MODIFICATIONS ARE BEING MADE, A NEW MINOR AMENDMENT
 SHALL BE SUBMITTED TO AND APPROVED BY THE PLANNING AND
 ZONING DEPARTMENT. OTHERWISE, THE PLANS SHALL BE
 MODIFIED TO MATCH THOSE THAT WERE APPROVED THROUGH THE
 PREVIOUS MINOR AMENDMENT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  