| Plan Review Stops For Permit 10030263 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2010-04-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-04-20 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-04-20 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2010-04-20 09:00:56 | PROVISO ITEM INCORPORATED INTO PLAN BY ARCHITECT | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2010-03-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-03-29 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-03-29 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2010-03-29 16:31:00 | PASSED WITH PROVISO | | | | | | SHEET A1, DOORS 100 & 118 TO BE 45 MIN. PER FBC | | | 708.1(7) (TENANT SEPARATION BETWEEN TENANT AND COMMON | | | AREA), FBC 715.4 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2010-04-21 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2010-04-21 |
Time |
20:39 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2010-04-21 |
Time |
20:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2010-03-29 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2010-03-29 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2010-03-29 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2010-03-29 18:50:25 | PLEASE PROVIDE INFORMATION / CLARIFICATION REGARDING | | | "PANEL HEATERS" BOTH PROPOSED AS PART OF THIS PROJECT | | | AND THOSE INDICATED AS "FUTURE". PLEASE PROVIDE | | | SPECIFICATIONS ON THESE HEATERS, THE ASSOCIATED | | | CONTROLS, AND TIMERS AND INFORMATION TO DEMONSTRATE | | | THAT THESE DEVICES ARE INCLUDED IN THE BASE BUILDING | | | ENERGY CALCUATIONS. | | | | | | PLEASE CLARIFY HOW ARE THESE HEATERS TO BE CONTROLLED | | | BY TIMERS? | | | | | | PLEASE CHECK INTENDED USE FOR RECEPTACLES / CIRCUIT | | | SERVING COUNTERTOP IN EMPLOYEE LOUNGE AREA. IF EITHER A | | | MICROWAVE OR COFFEE MACHINE IS DESIRED, DEDICATED | | | CIRCUITS MAY BE INDICATED TO AVOID OVERLOADING PROPOSED | | | CIRCUITS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY CONCERNS | | | OR QUESTIONS ABOUT THESE ISSUES AT 561-805-6650 OR BY | | | EMAIL AT [email protected]. | | | | | | THANK YOU, | | | | | | DOUG WISE |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2010-04-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-04-16 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-04-16 |
Time |
16:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2010-03-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-03-18 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-03-18 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2010-03-18 17:03:52 | 1641 WORTHINGTON ROAD, SUITE 410 | | | PERMIT # 10030263 | | | FIRST ELECTRONIC PLAN REVIEW FROM PROJECT DOX | | | | | | 1. THE TENANT DEMISING WALL SHALL BE PROPERLY | | | IDENTIFIED WITH "FIRE AND SMOKE BARRIER - PROTECT ALL | | | OPENINGS. SIGNS OR STENCILING WITH AT LEAST 4" HIGH | | | LETTERS, 1/2 " STROKE AND NOT MORE THAN 15 FEET ON | | | CENTER. | | | | | | 2. THE INSTALLATION OF CARD READERS SHALL NOT INTERFERE | | | WITH ANY EXITING. | | | | | | 3. THE PORTABLE FIRE EXTINGUISHERS ON SHEET A-1 SHALL | | | COMPLY WITH NFPA 10, THE STANDARD FOR PORTABLE FIRE | | | EXTINGUISHERS, 2002 EDITION. ALL EXTINGUISHERS SHALL BE | | | PROPERLY SERVICE TAGGED. | | | | | | 4. THE NEW FIRE DAMPER SHALL BE DROP TESTED TO ENSURE | | | PROPER OPERATION. | | | | | | 5. TACTILE SIGNAGE IS REQUIRED AT EXIT DOORS. | | | | | | 6. PLEASE ADVISED ALL UTILITIES THAT ARE PLANNED FOR | | | UNDERNEATH THE RAISED FLOOR. IS ANY FIRE ALARM | | | EQUIPMENT PLANNED OR ANY FIRE SUPPRESSION SYSTEMS | | | CONSIDERED. | | | | | | 7. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE | | | SPRINKLER OR FIRE ALARM SYSTEM REMODELING. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | (561) 804-4724 PHONE | | | (561) 804-4774 FAX | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2010-04-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2010-04-13 |
Time |
|
Sent To |
|
|
| Notes |
| 2010-04-15 07:59:00 | 1ST RESUB UPLOADED |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2010-03-31 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2010-03-15 |
Time |
|
Sent To |
|
|
| Notes |
| 2010-04-15 07:58:02 | ***DIGITAL PLAN REVIEW*** |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2010-03-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-03-29 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-03-29 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2010-03-29 13:30:53 | TENANT BUILDOUT | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2010-03-23 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2010-03-23 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2010-03-23 |
Time |
07:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2010-03-24 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2010-03-24 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2010-03-23 |
Time |
12:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2010-05-04 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2010-05-04 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2010-05-04 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2010-05-04 14:28:15 | ORIGINAL PADDS CERTIFICATION PAGES RECEIVED, SENT TO | | | RECORDS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2010-04-20 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2010-04-20 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2010-04-20 |
Time |
08:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2010-03-29 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2010-03-29 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2010-03-29 |
Time |
10:20 |
Sent To |
|
|
| Notes |
|
|