Plan Review Details - Permit 10030263
Plan Review Stops For Permit 10030263
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-04-20 Cont ID  
Sent By shill Date 2010-04-20 Time 09:00 Rev Time 0.00
Received By shill Date 2010-04-20 Time 08:43 Sent To  
Notes
2010-04-20 09:00:56PROVISO ITEM INCORPORATED INTO PLAN BY ARCHITECT
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-03-29 Cont ID  
Sent By shill Date 2010-03-29 Time 16:29 Rev Time 0.00
Received By shill Date 2010-03-29 Time 13:30 Sent To  
Notes
2010-03-29 16:31:00PASSED WITH PROVISO
  
 SHEET A1, DOORS 100 & 118 TO BE 45 MIN. PER FBC
 708.1(7) (TENANT SEPARATION BETWEEN TENANT AND COMMON
 AREA), FBC 715.4
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-04-21 Cont ID  
Sent By dwise Date 2010-04-21 Time 20:39 Rev Time 0.00
Received By dwise Date 2010-04-21 Time 20:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-03-29 Cont ID  
Sent By dwise Date 2010-03-29 Time 17:10 Rev Time 0.00
Received By dwise Date 2010-03-29 Time 17:10 Sent To  
Notes
2010-03-29 18:50:25PLEASE PROVIDE INFORMATION / CLARIFICATION REGARDING
 "PANEL HEATERS" BOTH PROPOSED AS PART OF THIS PROJECT
 AND THOSE INDICATED AS "FUTURE". PLEASE PROVIDE
 SPECIFICATIONS ON THESE HEATERS, THE ASSOCIATED
 CONTROLS, AND TIMERS AND INFORMATION TO DEMONSTRATE
 THAT THESE DEVICES ARE INCLUDED IN THE BASE BUILDING
 ENERGY CALCUATIONS.
  
 PLEASE CLARIFY HOW ARE THESE HEATERS TO BE CONTROLLED
 BY TIMERS?
  
 PLEASE CHECK INTENDED USE FOR RECEPTACLES / CIRCUIT
 SERVING COUNTERTOP IN EMPLOYEE LOUNGE AREA. IF EITHER A
 MICROWAVE OR COFFEE MACHINE IS DESIRED, DEDICATED
 CIRCUITS MAY BE INDICATED TO AVOID OVERLOADING PROPOSED
 CIRCUITS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY CONCERNS
 OR QUESTIONS ABOUT THESE ISSUES AT 561-805-6650 OR BY
 EMAIL AT [email protected].
  
 THANK YOU,
  
 DOUG WISE

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-04-16 Cont ID  
Sent By mcarsill Date 2010-04-16 Time 16:17 Rev Time 0.00
Received By mcarsill Date 2010-04-16 Time 16:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-18 Cont ID  
Sent By mcarsill Date 2010-03-18 Time 17:03 Rev Time 0.00
Received By mcarsill Date 2010-03-18 Time 16:52 Sent To  
Notes
2010-03-18 17:03:521641 WORTHINGTON ROAD, SUITE 410
 PERMIT # 10030263
 FIRST ELECTRONIC PLAN REVIEW FROM PROJECT DOX
  
 1. THE TENANT DEMISING WALL SHALL BE PROPERLY
 IDENTIFIED WITH "FIRE AND SMOKE BARRIER - PROTECT ALL
 OPENINGS. SIGNS OR STENCILING WITH AT LEAST 4" HIGH
 LETTERS, 1/2 " STROKE AND NOT MORE THAN 15 FEET ON
 CENTER.
  
 2. THE INSTALLATION OF CARD READERS SHALL NOT INTERFERE
 WITH ANY EXITING.
  
 3. THE PORTABLE FIRE EXTINGUISHERS ON SHEET A-1 SHALL
 COMPLY WITH NFPA 10, THE STANDARD FOR PORTABLE FIRE
 EXTINGUISHERS, 2002 EDITION. ALL EXTINGUISHERS SHALL BE
 PROPERLY SERVICE TAGGED.
  
 4. THE NEW FIRE DAMPER SHALL BE DROP TESTED TO ENSURE
 PROPER OPERATION.
  
 5. TACTILE SIGNAGE IS REQUIRED AT EXIT DOORS.
  
 6. PLEASE ADVISED ALL UTILITIES THAT ARE PLANNED FOR
 UNDERNEATH THE RAISED FLOOR. IS ANY FIRE ALARM
 EQUIPMENT PLANNED OR ANY FIRE SUPPRESSION SYSTEMS
 CONSIDERED.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER OR FIRE ALARM SYSTEM REMODELING.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2010-04-13 Time   Rev Time 0.00
Received By   Date 2010-04-13 Time   Sent To  
Notes
2010-04-15 07:59:001ST RESUB UPLOADED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-03-31 Time   Rev Time  
Received By   Date 2010-03-15 Time   Sent To  
Notes
2010-04-15 07:58:02***DIGITAL PLAN REVIEW***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-03-29 Cont ID  
Sent By shill Date 2010-03-29 Time 13:30 Rev Time 0.00
Received By shill Date 2010-03-29 Time 13:30 Sent To  
Notes
2010-03-29 13:30:53TENANT BUILDOUT
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-03-23 Cont ID  
Sent By rregueir Date 2010-03-23 Time 07:56 Rev Time 0.00
Received By rregueir Date 2010-03-23 Time 07:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-03-24 Cont ID  
Sent By lwagner Date 2010-03-24 Time 09:54 Rev Time 0.00
Received By lwagner Date 2010-03-23 Time 12:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2010-05-04 Cont ID  
Sent By rregueir Date 2010-05-04 Time 14:28 Rev Time 0.00
Received By rregueir Date 2010-05-04 Time 14:27 Sent To  
Notes
2010-05-04 14:28:15ORIGINAL PADDS CERTIFICATION PAGES RECEIVED, SENT TO
 RECORDS.

Review Stop Z ZONING
Rev No 2 Status P Date 2010-04-20 Cont ID  
Sent By jroach Date 2010-04-20 Time 08:41 Rev Time 0.00
Received By jroach Date 2010-04-20 Time 08:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-03-29 Cont ID  
Sent By jroach Date 2010-03-29 Time 10:21 Rev Time 0.00
Received By jroach Date 2010-03-29 Time 10:20 Sent To  
Notes
***NONE***