Plan Review Details - Permit 10030231
Plan Review Stops For Permit 10030231
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-06-08 Cont ID  
Sent By jwitmer Date 2010-06-08 Time 12:44 Rev Time 0.33
Received By jwitmer Date 2010-06-08 Time 12:44 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-18 Cont ID  
Sent By jwitmer Date 2010-03-18 Time 14:05 Rev Time 0.77
Received By jwitmer Date 2010-03-18 Time 14:05 Sent To  
Notes
2010-03-18 14:58:58BUILDING PLAN REVIEW
 PERMIT: 10030231
 ADD: 1400 CENTREPARK SUITE# 310
 CONT: METRO RENOVATIONS
 TEL: (407)234-2269
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE REVIEW THE SIZE LIMITATIONS IN FBC-B
 715.5.7.2 THE TOTAL AREA OF WINDOWS, THIS WOULD ALSO
 INCLUDE THE GLAZING WITHIN THE 45 MINUTE RATED DOOR.
  
 2) PLEASE ALSO REVIEW 715.4.6.4 FOR SAFETY GLAZING
 REQUIREMENTS.
  
 3) THE PLANS FAIL TO IDENTIFY FRAME TYPE FOR BOTH THE
 WINDOW AND DOOR. 715.4.5.1.
  
 4) RATED FIRE DOORS WILL ALSO NEED CLOSEERS. 715.4.7.
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 5) PLANS DO NOT INDICATE THE MINIMUM FLAME SPREAD AND
 SMOKE DEVELOPMENT FBC-B 803.1/ TABLE 803.5.
  
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-06-07 Cont ID  
Sent By mawillia Date 2010-06-07 Time 14:00 Rev Time 0.00
Received By mawillia Date 2010-06-07 Time 13:48 Sent To B1
Notes
2010-06-07 13:57:08*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; SINGLE SHEET S1 STAMPED, INITLALED, AND
 APPROVED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-18 Cont ID  
Sent By mawillia Date 2010-03-18 Time 15:58 Rev Time 0.00
Received By mawillia Date 2010-03-18 Time 15:36 Sent To  
Notes
2010-03-18 15:58:06*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS TO COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. SPECIFY THE INTERIOR FINISH MATERIAL NEW WALL IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 4. DOORS WHICH LEAD INTO THE EXIT ACCESS CORRIDOR SHALL
 BE SELF CLOSING AND SELF LATCHING UPON RELEASE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-04 Cont ID  
Sent By lmartine Date 2010-06-04 Time 11:03 Rev Time 0.00
Received By lmartine Date 2010-06-04 Time 11:02 Sent To  
Notes
2010-06-04 11:03:22PUT IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-02 Cont ID  
Sent By lmartine Date 2010-03-22 Time 09:39 Rev Time 0.00
Received By lmartine Date 2010-03-15 Time 16:04 Sent To  
Notes
2010-03-15 16:06:40B8

Review Stop Z ZONING
Rev No 2 Status P Date 2010-06-16 Cont ID  
Sent By jroach Date 2010-06-16 Time 08:54 Rev Time 0.00
Received By jroach Date 2010-06-11 Time 11:56 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-03-22 Cont ID  
Sent By jroach Date 2010-03-22 Time 15:57 Rev Time 0.00
Received By jroach Date 2010-03-22 Time 15:57 Sent To  
Notes
***NONE***