| Plan Review Stops For Permit 10030114 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2010-08-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-08-30 |
Time |
14:28 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2010-08-30 |
Time |
14:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-03-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-03-18 |
Time |
12:50 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2010-03-18 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2010-03-18 12:55:28 | BUILDING PLAN REVIEW | | | PERMIT: 10030114 | | | ADD: 1700 PALM BEACH LAKES 11TH FLOOR RESTROOMS | | | CONT: HOLT LEE CONSTRUCTION | | | TEL: (954)270-1894 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) SHEET D3 WOMENS RESTROOM INDICATES A PRIVATE | | | RESTROOM MISSING THE LAV FROM WITHIN THE STALL. REVIEW | | | 11-4.17 FIGURE 30E. | | | | | | 2) SHEET D3 MENS RESTROOM MENS LAV PLEASE INDICATE THE | | | CLEAR FLOOR SPACE FOR THE LAV. IT APPEARS THAT THE DOOR | | | MAY ENCROACH ON THE REQUIRED CLEAR FLOOR SPACE.PLEASE | | | REVIEW | | | 11-4.19.3 30"X48". | | | | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE | | | CUSTOMER SERVICE SURVEY AT: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-04-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2010-04-05 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2010-04-01 |
Time |
08:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2010-09-07 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-09-07 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-09-07 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2010-09-07 16:00:42 | *****APPROVED***** | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | WPB FIRE PLAN REVIEW | | | 561-805-6730 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2010-03-18 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2010-03-18 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2010-03-18 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2010-03-18 14:47:10 | *****PARTIAL APPROVAL****** | | | | | | THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN ALL | | | OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-08-30 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-08-30 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-08-30 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2010-08-30 12:40:43 | *******************EXPEDITED****************** | | | B--6 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-04-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2010-04-01 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2010-03-03 |
Time |
10:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2010-09-17 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2010-09-10 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2010-09-17 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2010-09-17 08:21:31 | PLAN PASS WITH PROVISO | | | PLEASE REFER TO SECTION 607.5.5 2007 FBC (M) SHAFT | | | INCLOSURE'S SHAFTS SHALL BE PROTECTED WITH LISTED FIRE | | | SMOKE DAMPERS. IF THERE ARE EXCEPTIONS PLEASE SUBMIT | | | THEM TO THE INSPECTOR AT THE FIRST INSPECTION. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | 2010-09-10 13:15:01 | PUT BACK ON BOB BOARD FOR HM TO REVIEW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2010-03-23 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2010-03-23 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2010-03-23 |
Time |
08:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2010-09-09 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2010-09-09 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2010-09-09 |
Time |
13:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2010-03-17 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2010-03-17 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2010-03-17 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2010-03-17 10:32:45 | 1. W.C. STALL IN WOMENS ROOM REQUIRED TO BE PER 11-4.17 | | | FIG. 30(E) WITH LAV IN STALL. | | | | | | 2. PLUMBING PLAN SHOWS HORIZONTAL DRY VENT IN WOMENS | | | ROOM BETWEEN WATER CLOSETS. FBC 2007 PLUMBING 905.3 & | | | 905.4 | | | VENTS SHALL RISE VERTICALLY TO A MINIMUM OF 6 INCHES | | | ABOVE FLOOD LEVEL RIM OF FIXTURE. | | | | | | LARRY WAGNER | | | CHIEF PLUMBING | | | 805-6692 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
N |
Date |
2010-12-27 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2010-12-27 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2010-12-27 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2010-03-22 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2010-03-22 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2010-03-22 |
Time |
16:04 |
Sent To |
|
|
| Notes |
|
|