Plan Review Details - Permit 10030114
Plan Review Stops For Permit 10030114
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-30 Cont ID  
Sent By jwitmer Date 2010-08-30 Time 14:28 Rev Time 0.55
Received By jwitmer Date 2010-08-30 Time 14:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-18 Cont ID  
Sent By jwitmer Date 2010-03-18 Time 12:50 Rev Time 0.55
Received By jwitmer Date 2010-03-18 Time 12:40 Sent To  
Notes
2010-03-18 12:55:28BUILDING PLAN REVIEW
 PERMIT: 10030114
 ADD: 1700 PALM BEACH LAKES 11TH FLOOR RESTROOMS
 CONT: HOLT LEE CONSTRUCTION
 TEL: (954)270-1894
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET D3 WOMENS RESTROOM INDICATES A PRIVATE
 RESTROOM MISSING THE LAV FROM WITHIN THE STALL. REVIEW
 11-4.17 FIGURE 30E.
  
 2) SHEET D3 MENS RESTROOM MENS LAV PLEASE INDICATE THE
 CLEAR FLOOR SPACE FOR THE LAV. IT APPEARS THAT THE DOOR
 MAY ENCROACH ON THE REQUIRED CLEAR FLOOR SPACE.PLEASE
 REVIEW
 11-4.19.3 30"X48".
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-04-05 Cont ID  
Sent By jleahy Date 2010-04-05 Time 08:15 Rev Time 0.00
Received By jleahy Date 2010-04-01 Time 08:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-09-07 Cont ID  
Sent By wjolin Date 2010-09-07 Time 16:00 Rev Time 0.00
Received By wjolin Date 2010-09-07 Time 16:00 Sent To  
Notes
2010-09-07 16:00:42*****APPROVED*****
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-18 Cont ID  
Sent By mawillia Date 2010-03-18 Time 14:51 Rev Time 0.00
Received By mawillia Date 2010-03-18 Time 14:35 Sent To  
Notes
2010-03-18 14:47:10*****PARTIAL APPROVAL******
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN ALL
 OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-30 Cont ID  
Sent By lmartine Date 2010-08-30 Time 11:31 Rev Time 0.00
Received By lmartine Date 2010-08-30 Time 11:31 Sent To  
Notes
2010-08-30 12:40:43*******************EXPEDITED******************
 B--6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-05 Cont ID  
Sent By jleahy Date 2010-04-01 Time 08:46 Rev Time 0.00
Received By jleahy Date 2010-03-03 Time 10:23 Sent To  
Notes
2010-03-04 10:23:56B--1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-09-17 Cont ID  
Sent By rregueir Date 2010-09-10 Time 13:14 Rev Time 0.00
Received By hmoser Date 2010-09-17 Time 08:11 Sent To  
Notes
2010-09-17 08:21:31PLAN PASS WITH PROVISO
 PLEASE REFER TO SECTION 607.5.5 2007 FBC (M) SHAFT
 INCLOSURE'S SHAFTS SHALL BE PROTECTED WITH LISTED FIRE
 SMOKE DAMPERS. IF THERE ARE EXCEPTIONS PLEASE SUBMIT
 THEM TO THE INSPECTOR AT THE FIRST INSPECTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
2010-09-10 13:15:01PUT BACK ON BOB BOARD FOR HM TO REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-03-23 Cont ID  
Sent By hmoser Date 2010-03-23 Time 13:10 Rev Time 0.00
Received By hmoser Date 2010-03-23 Time 08:19 Sent To  
Notes
2010-03-23 13:16:09 
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-09-09 Cont ID  
Sent By lwagner Date 2010-09-09 Time 13:43 Rev Time 0.00
Received By lwagner Date 2010-09-09 Time 13:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-03-17 Cont ID  
Sent By lwagner Date 2010-03-17 Time 10:28 Rev Time 0.00
Received By lwagner Date 2010-03-17 Time 10:28 Sent To  
Notes
2010-03-17 10:32:451. W.C. STALL IN WOMENS ROOM REQUIRED TO BE PER 11-4.17
 FIG. 30(E) WITH LAV IN STALL.
  
 2. PLUMBING PLAN SHOWS HORIZONTAL DRY VENT IN WOMENS
 ROOM BETWEEN WATER CLOSETS. FBC 2007 PLUMBING 905.3 &
 905.4
 VENTS SHALL RISE VERTICALLY TO A MINIMUM OF 6 INCHES
 ABOVE FLOOD LEVEL RIM OF FIXTURE.
  
 LARRY WAGNER
 CHIEF PLUMBING
 805-6692
 [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2010-12-27 Cont ID  
Sent By jroach Date 2010-12-27 Time 15:42 Rev Time 0.00
Received By jroach Date 2010-12-27 Time 15:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-03-22 Cont ID  
Sent By jroach Date 2010-03-22 Time 16:04 Rev Time 0.00
Received By jroach Date 2010-03-22 Time 16:04 Sent To  
Notes
***NONE***