| Plan Review Stops For Permit 10030102 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2010-04-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-04-27 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-04-27 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2010-04-27 16:01:53 | PROVISO | | | SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE ASPHALT | | | ROOF SHINGLES AND THE FLAT ROOF COVERING. A REVISON FEE | | | WILL BE CHARGED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-03-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-03-17 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-03-17 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2010-03-17 14:01:38 | 2007 FBC W/2009 REVISIONS | | | ADDITION | | | | | | DENIED BY BUILDING | | | | | | 1) BASED ON FBC R301.2.1.4.3, THE STRUCTURE IS LOCATED | | | IN EXPOSURE C AND THE PLANS SPECIFY EXPOSURE B. PLEASE | | | CORRECT AND REVISE COMPONENT AND CLADDING PRESSURES TO | | | REFLECT EXPOSURE C. | | | | | | 2) SPECIFY TERMITE PROTECTION AS REQUIRED BY FBC R320. | | | | | | 3) SUBMIT TWO SETS OF ENERGY CALCULATIONS AS REQUIRED | | | BY FBC 13-101.2.2. | | | | | | 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR EXTERIOR | | | FRENCH DOORS, WINDOWS, ROOFING MATERIALS, CONNECTORS | | | AND STORM PANELS AS REQUIRED BY DCA RULE 9B-72. | | | | | | 5) IF STORM PANELS WILL BE INSTALLED, SUBMIT TWO COPIES | | | OF A KEY PLAN AND INSTALLATION SCHEDULE FOR THEM. | | | SPECIFY ANCHORS, SPACING, MOUNT TYPE, ETC. | | | | | | 6) THE DESIGNER OF RECORD FOR THE PROJECT IS REQUIRED | | | TO REVIEW AND APPROVE THE PRODUCT APPROVALS IN WRITING. | | | CITY AMENDMENTS 106.3.3 | | | | | | 7) SHOW COMPLIANCE WITH FBC R806 FOR ROOF VENTILATION. | | | | | | 8) SPECIFY THE EXTERIOR WALL SHEATHING THAT WILL BE | | | INSTALLED. FBC R602.2.10.3 | | | | | | 9) SHOW COMPLIANCE WITH FBC R703.6.3 FOR THE REQUIRED | | | BOND BREAK BETWEEN THE WATER BARRIER AND THE STUCCO. | | | | | | 10) SHOW COMPLIANCE WITH R703.6.2 AND ASTM C 1063 AND | | | SPECIFY THE FOUNDATION WEEP SCREED AT THE BOTTOM OF THE | | | FRAMED EXTERIOR WALL. | | | | | | 11) SPECIFY THE EXTERIOR WALL INSULATION ON THE PLANS. | | | FBC 13-600 | | | | | | 12) THE VALUE OF THE PROPOSED WORK IS TOO LOW AND HAS | | | BEEN ADJUSTED TO $ 38,298.00 BASED ON ICC BUILDING | | | VALUATION DATA. ADDITIONAL PERMIT FEES ARE DUE. CITY | | | AMENDMENTS 108.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2010-04-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2010-04-12 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2010-04-12 |
Time |
12:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-03-15 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2010-03-15 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2010-03-15 |
Time |
15:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-04-08 |
|
|
Cont ID |
|
| Sent By |
jpapa |
Date |
2010-04-08 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
jpapa |
Date |
2010-04-08 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2010-04-08 16:13:48 | PROVISO: PER THE HISTORIC PRESERVATION DESIGN | | | GUIDELINES HANDBOOK, MECHANICAL EQUIPMENT SHALL NOT BE | | | PLACED IN PUBLIC VIEW. THE MECHANICAL EQUIPMENT SHALL | | | BE RELOCATED TO THE SIDE OR REAR OF THE RESIDENCE. | | | | | | JILLIAN PAPA, HISTORIC PRESERVATION PLANNER | | | (561) 822-1454 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-04-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-04-27 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-04-01 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2010-04-01 09:02:44 | INCOMING SENT TO R-13 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-03-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-03-17 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-03-03 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2010-04-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-04-29 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-04-29 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2010-04-29 15:17:30 | PLANS STAMPED BY PBC / NO IMPACT FEES WERE DUE. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2010-03-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-03-16 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-03-16 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2010-04-27 15:46:23 | PLANS NEED TO BE TAKEN TO PB COUNTY FOR IMPACT FEES. | | | NOTE: OWNER/AGENT NEEDS TO SIGN ENERGY CALCS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2010-04-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-04-27 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-04-27 |
Time |
15:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2010-03-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-03-16 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-03-16 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2010-03-16 16:28:12 | INSTALL MINI SPLIT SYSTEM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2010-04-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-04-27 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-04-27 |
Time |
15:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2010-03-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-03-16 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-03-16 |
Time |
14:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2010-04-08 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2010-04-08 |
Time |
11:57 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2010-04-08 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2010-04-08 14:49:14 | PASSED | | | | | | ANY SHRUBS OR TREES DAMAGED BY CONSTRUCTION SHALL BE | | | REPLACED. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2010-03-16 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2010-03-16 |
Time |
12:57 |
Rev Time |
1.25 |
| Received By |
eschneid |
Date |
2010-03-16 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2010-03-16 13:10:32 | FAILED | | | | | | 1) THE SURVEY PROVIDED WITH THE PLANS DOES NOT | | | ACCURATELY REFLECT THE "EXISTING" CONDITIONS SHOWN ON | | | THE PLANS EX. THE DECK, OR MATCH THE AERIAL ON THE | | | PROPERTY APPRAISER'S WEBSITE, EX. DRIVEWAY. PLEASE | | | PROVIDE A SURVEY THAT IS LESS THAN ONE YEAR OLD. | | | | | | 2) THE PROPERTY IS LOCATED WITHIN THE MF32 ZONING | | | DISTRICT, WHICH REQUIRES A MINIMUM 15 FOOT SETBACK ON | | | BOTH SIDES OF THE HOUSE, NOT THE 7 FEET SHOWN. | | | | | | 3) PLEASE PROVIDE THE ROOF OVERHANG DIMENSION ON THE | | | EAST SIDE OF THE NEW ADDITION. | | | | | | 4) WHAT LANDSCAPE, BOTH TREES AND SHRUBS, IS BEING | | | AFFECTED BY THE LARGER ADDITION? IF TREES ARE TO BE | | | REMOVED, THEN A TREE ALTERATION PERMIT IS REQUIRED. AT | | | LEAST 14 SHRUBS SHALL BE MAINTAINED/PROVIDED ON-SITE. | | | | | | 5) NOTE: IF THE VALUE OF ALL CONSTRUCTION PERMITS FOR | | | THE MAIN HOUSE EXCEEDS $66,581 THEN A LANDSCAPE PLAN IS | | | REQUIRED. | | | | | | 6) PROVIDE THE DIMENSION OF THE A/C EQUIPMENT TO THE | | | PROPERTY LINE. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|