Plan Review Details - Permit 10020578
| Plan Review Stops For Permit 10020578 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2010-07-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-07-20 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-07-20 |
Time |
14:43 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2010-05-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-05-27 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-05-27 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2010-05-27 11:09:19 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) BUILDING COMMENTS FROM THE FIRST REVIEW HAVE NOT | | | BEEN ADDRESSED. | | | | | | 2) THE TRUSS DRAWINGS THAT WERE SUBMITTED ARE FOR | | | EXPOSURE CATEGORY B AND THE STRUCTURE IS EXPOSURE C. | | | SEE COMMENT #1 FROM THE FIRST REVIEW. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-03-15 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-03-15 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2010-03-15 14:18:27 | 2007 FBC W/2009 REVISIONS | | | COVERED PORCH ADDITION | | | | | | DENIED BY BUILDING | | | | | | 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY 'C' | | | AND ON SHEET A4 OF THE PLANS EXPOSURE 'B' IS SPECIFIED. | | | SEE THE 2009 REVISIONS TO 2004 FBC SECTION | | | R301.2.1.4.3. | | | | | | 2) THE PLANS SPECIFY A 3:12 SLOPE FOR THE ROOF. FBC R | | | 905.2.7 REQUIRES TWO LAYERS OF UNDERLAYMENT ON THE | | | ROOF. PLEASE CORRECT NOTES. | | | | | | 3) FBC R803.2.3.1 REQUIRES THE ROOF SHEATHING TO BE | | | FASTENED WITH 8D RING SHANK NAILS. PLEASE CORRECT | | | NOTES. | | | | | | 4) FBC R320.7 REQUIRES ROOF DOWNSPOUTS ARE REQUIRED TO | | | DISCHARGE A MINIMUM OF 1 FOOT AWAY FROM THE STRUCTURE. | | | PLEASE NOTE ON PLANS. | | | | | | 5) FBC R 703.6.3 REQUIRES A BOND BREAK BETWEEN THE | | | WATER-RESISTIVE BARRIER AND THE STUCCO. SHOW | | | COMPLIANCE. | | | | | | 6) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | GAF ROYAL SOVEREIGN SHINGLES ( NOA NO. 07-1012.02 ) | | | HAVE BEEN SUPERSEDED BY NOA NO. 09-0825.06. PLEASE | | | SUBMIT TWO COPIES OF THE CURRENT PRODUCT APPROVALS. DCA | | | RULE 9B-72 | | | | | | 7) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND | | | APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT. | | | 106.3.3 CITY AMENDMENTS | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-03-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2010-03-08 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2010-03-08 |
Time |
09:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2010-07-15 |
|
|
Cont ID |
|
| Sent By |
vmolina |
Date |
2010-07-15 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
vmolina |
Date |
2010-07-15 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2010-07-15 10:15:57 | GAVE TO RM |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-05-24 |
|
|
Cont ID |
|
| Sent By |
vmolina |
Date |
2010-05-24 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
vmolina |
Date |
2010-05-24 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2010-05-24 12:27:17 | GAVE TO MCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-05-24 |
|
|
Cont ID |
|
| Sent By |
vmolina |
Date |
2010-03-22 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
vmolina |
Date |
2010-03-01 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2010-03-01 16:28:46 | SENT TO R3. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2010-07-22 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2010-07-22 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2010-07-22 |
Time |
10:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2010-03-22 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2010-03-22 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2010-03-22 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2010-03-22 15:46:27 | ZONING PLAN REVIEW | | | | | | PERMIT NO.: 10020578 | | | ADDRESS: 715 MADDOCK STREET | | | CONTRACTOR/CONTACT: GARY DUHANEY | | | TELEPHONE NO.: 954.822.8575 | | | SCOPE OF REVIEW: REAR PORCH ADDITION. | | | | | | REVIEW STATUS: FAILED | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1) THE PERMIT APPLICATION REFERENCES THE INSTALLATION | | | OF A REAR PORCH ADDITION, AS WELL AS A SCREENED | | | CARPORT. PLEASE CLARIFY???THE PLANS DO NOT MAKE ANY | | | REFERENCE TO A CARPORT. | | | | | | 2) PLEASE INDICATE WHERE THE EXISTING A/C UNIT AT THE | | | REAR OF THE PROPERTY WILL BE RELOCATED TO???IT APPEARS | | | THAT THE PROPOSED CONSTRUCTION WILL IMPACT THE LOCATION | | | OF THE EXISTING UNIT. BE SURE TO INDICATE THE PROPOSED | | | SETBACKS FROM THE A/C UNIT TO ALL ADJACENT PROPERTY | | | LINES. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, SENIOR PLANNER | | | CITY OF WEST PALM BEACH | | | PLANNING AND ZONING DEPARTMENT | | | 401 CLEMATIS STREET - P.O. BOX 3366 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1435 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.CITYOFWPB.COM | | | |
|
|
|